MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered Voltage Rating Motor control centers are rated for 600 volts This is the maximum voltage that can be applied to a motor control center A motor control center can be connected to a lower voltage A motor control center, for example, might be connected to a three-phase, 480 VAC power supply Horizontal Bus Current Rating The horizontal bus on Siemens motor control centers are made of tin or optional silver plated copper They are available with 600A, 800A, 1200A, 1600A, and 2000A current ratings 47 Vertical Bus The vertical bus on the TIASTAR motor control centers are available with 300A and 600A ratings Bus Bracing Motor control centers must be capable of withstanding the largest potential short-circuit current which can occur in the selected application The amount of short-circuit current available depends on the amount of power available to a facility Short-circuit current can be thousands of times higher than normal current Bus bars must be braced to withstand this potential current Siemens bus bars are braced for 42,000 AIC (ampere interrupting capacity) with optional bracing available to 100,000 AIC 48 Temperature Rise The bus bars are the major current carrying component of the motor control center Before a motor control center is operated, bus bars are at the temperature of the surrounding air This is known as ambient temperature Temperature rises in the motor control center bus bars during operation The combination of ambient temperature and allowed temperature rise equals the maximum temperature of the bus bars NEMA and UL both have standards concerning the maximum temperature rise of bus bars used in motor control centers NEMA limits temperature rise to 65°C based on an ambient temperature of 40°C (104°F), for a maximum operating temperature of 105°C UL limits temperature rise to 50°C based on an ambient temperature of 40°C (104°F), for a maximum operating temperature of 90°C Electrical equipment bearing a UL mark must meet or exceed this standard Siemens motor control centers meet or exceed NEMA and UL standards Bus bars in Siemens motor control centers are tested with a maximum temperature rise of 50°C over 40°C (104°F) ambient 49 Enclosures NEMA defines an enclosure as a surrounding case constructed to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection to the enclosed equipment against specified environmental conditions (NEMA Standard 250 - section 2, definitions) The following brief descriptions cover enclosures available for Siemens motor control centers Type Enclosure 50 Type enclosures are intended for indoor use primarily to provide protection against limited amounts of falling dirt and contact with the enclosed equipment in locations where unusual service conditions not exist Type Gasket Front Type gasketed front, general purpose, indoor enclosure has the same use as Type except the front of the enclosure is gasketed In addition the following parts are gasketed: Unit separator angles Right-hand side of front of units Bottom horizontal cross ties Lip on top plate Pilot-device panel Handle mechanism Bottom horizontal wireway cover plate Side holes are plugged Type 2, Drip-Proof Type 2, drip-proof is an indoor enclosure intended to protect equipment from falling noncorrosive liquids and dirt The enclosure prevents the entrance of dripping liquid at a higher level than the lowest live part within the enclosure This design is a Type gasketed front, or Type 12, with a drip shield mounted on top of the enclosure Type 12 Enclosure Type 12 enclosures are intended for indoor use primarily to provide a degree of protection against circulating dust, falling dirt, and dripping noncorrosive liquids They are not intended to provide protection against conditions such as internal condensation The Type 12 will provide a greater degree of protection than a Type gasketed enclosure The following additional parts are gasketed: Hinged side of doors Top plates Wireway end-covers Rear plates There is no gap between sections, allowing for much greater dust resistance In addition, interconnection holes in the side sheet assemblies are sealed Bottom plates are included 51 Type 3R Enclosure Type 3R enclosures are intended for outdoor use primarily to provide a degree of protection against falling rain and sleet and protection from contact with the enclosed equipment They are not dust, snow, or sleet (ice) proof They will prevent entrance of rain at a level higher than the lowest live part The enclosure has provisions for locking and drainage The enclosure entirely surrounds the motor control center for outdoor operation The Type 3R enclosure is designed to accommodate bottom cable entry and exit only The 3R enclosure is not a walk-in type design NEMA and IEC The International Electrotechnical Commission (IEC) is another organization that defines the degree of protection provided by enclosures NEMA is primarily associated with equipment used in North America IEC is associated with equipment sold in many countries including the United States The IEC designation consists of the letters IP followed by two numbers The first number indicates the degree of protection provided by the enclosure with respect to persons and solid objects entering the enclosure The second number indicates the degree of protection against the ingress of water The following chart provides an equivalent conversion between NEMA and IEC designations 52 NEMA IEC 3R 12 IP10 IP11 IP14 IP52 Classification and Types of Wiring NEMA has established two classification standards (Class I and Class II) and three types of wiring (A, B, and C) used in the construction of motor control centers These are specified by the customer Class I Class I consists of a grouping of combination motor control units in which each starter and motor operates independently of the other starters The factory connects the combination motor control units to the vertical bus but does not provide interconnecting wiring between combination motor control units, different vertical units, or remotely connected devices Diagrams of the individual units only are supplied Class I, Type A Wiring Type A wiring is only available on Class I motor control centers The motor control center manufacturer connects the combination motor control unit to the vertical bus via the stabs on the back of the unit Power is applied to the circuit breaker from the vertical bus The circuit breaker is factory wired to the motor starter The customer connects the motor leads and control wiring to the motor starter There is no interconnecting wiring between combination motor control units 53 Class I, Type B Wiring Typically pilot devices, such as indicator lights, pushbuttons, and selector switches, are used with Class I, Type B wiring Type B wiring is divided into two designations: B-d (-d for connection of load wires directly on starter or contactor terminals) and B-t (-t for connection of load wires to unit mounted load terminal blocks) When Type B-d wiring is specified, terminal blocks are furnished near the wireway for control circuit connections Motor leads are connected directly to the overload relay terminals When Type B-t wiring is specified, terminal blocks are furnished near the wireway for control circuit connections and for motor starter leads Type B-t wiring can be used on starters up to size 54 Class I, Type C Wiring With Type C wiring, a master terminal block is provided in either the top or bottom horizontal wiring gutter The manufacturer of the motor control center brings the control wires from each control unit to the master terminal block The installer is then able to make his wiring connections at the master terminal block With Type C wiring, load wiring for combination motor control units smaller than size (50 HP) are connected to the master terminal block Load wiring for combination motor control units larger than size are connected directly to unit device terminals 55 Class II Class II consists of a grouping of combination motor control units with interwiring and interlocking between the starters to form a complete control system Wiring diagrams, including the interwiring, is furnished Class II is generally specified when a group of motors requires sequencing, interlocking, or interconnecting Class II, Type B Class II, Type B wiring is similar to Class I, Type B wiring Terminal blocks are furnished near the wireway In addition, Class II, Type B wiring includes interconnecting wiring between motor starters 56 Horizontal Bus The horizontal bus is connected to the vertical bus with a two-bolt, U-shaped clamp utilizing spring washers to maintain torque This allows the bolts to be tightened from the front Horizontal bus bars are shielded by a clear polycarbonate cover for safety and easy visibility for inspection Ground Bus 66 A horizontal ground bus is mounted in the bottom 6” of space The horizontal ground bus is standard An optional vertical ground bus can be connected to the horizontal bus When a combination motor control unit is instered into the MCC the vertical ground bus is the first item engaged Likewise, when the unit is removed the vertical ground bus is the last thing to be disengaged Wire Tie Rods Round wire tie rods are located in each vertical wireway to hold wire harnesses in place Pilot Devices Pilot devices are mounted on a panel which latches onto the unit door with a simple tab-and-notch mechanism The pilotdevice panel can be removed from the door and attached to the combination motor control unit for service or unit removal There is room for four 30mm pilot devices on the panel 67 Terminal Blocks Terminal blocks are supplied with Type B and C wiring The terminal blocks are mounted up front on a swing-out side panel The panel is notched so that the terminal block can be placed inside the unit, in a center position, or in the vertical wireway This secures the terminals inside the unit when access is not required, or allows access from the vertical wireway Pull-apart terminals are available as an option Operating Handle The disconnect operating handle has four positions When placed in the “PARK” position the unit door can be opened without the handle interfering The “TRIPPED” position is clearly indicated 68 Racking Lever A racking lever located on each combination motor control unit is used to remove or install the unit When the operator handle is in the “ON” position, a locking pin blocks the racking lever closed When the operator handle is switched to the “OFF” position, the locking pin disengages the racking lever The combination motor control unit can be pulled to a test position The operator handle is placed in “PARK” to completely remove the combination motor control unit The unit is designed so that it cannot be inserted or removed with the operator handle in the “ON” position In the test position the unit can be padlocked in place Ground Clip A copper clip on the side of the combination motor control unit engages the unit support bracket, grounding the unit to the motor control center at all times An optional vertical bus stab is mounted on the unit when a vertical ground bus is used 69 Locking The disconnect operating handle can be locked in the “OFF” position with up to three padlocks High Density Units TIASTAR is also available with high density units High density units are 6” tall A maximum of 12 high density units can be installed in 72” of vertical space High density combination motor control units are available in NEMA size (5 HP) and size (10 HP) To compliment the high density unit, a 24” wide structure is available with an oversized (8” wide) vertical wireway While the 24” wide structure allows for the increased quantity of wires typical of high density applications, they are not required when high density units are used 70 Combination Units High density units have many of the same features as the full size units The disconnect operating handle is mounted sideways When Type B or C wiring is specified, a swing-out terminal block is supplied The motor starter is located behind the terminal block The circuit breaker is located behind the operator handle A unique “swing out” feature permits components to swing out of the unit for easy inspection or maintenance 71 Information Needed to Order MCCs When ordering a motor control center several questions need to be answered The following information will be useful 72 • Voltage, frequency, number of phases, and available fault current of power supply • Incoming power requirements (main circuit breaker, main fusible switch, main lugs only, or splicing to existing MCC) • Amp rating of the horizontal bus and finish material (tin or silver) • Voltage rating and source of control power • Size, type (aluminum or copper), number per phase and location of incoming cables or busway and outgoing cables • Enclosure - Type, finish - Accessibility (front, rear, or both) - Clearance for door swing - Restrictions on height, width, and depth • Horsepower rating and motor design of motors to be controlled • Ampacity of feeder tap units and unit disconnect devices • Type of disconnect for units: thermal-magnetic, instantaneous trip, or fusible • Ground bus requirements • Types of starting method of combination motor-control units, such as FVNR, FVR, 2S1W, 2S2W, PW, or RVAT • Type of control circuit for units • Service entrance requirements • Vertical bus requirements (finish, isolated/insulated, amp rating) • Class and Type of wiring • Additional equipment requirements (transformers, panelboards, transfer switches, PLCs, etc.) • Preferred layout of units • Special features, codes, or restrictions • Customer specifications • Drawing requirements 73 Review 74 The maximum height of an optional pull box for the TIASTAR is inches A maximum of high density units can be mounted in 72” of vertical space High Density units are available in NEMA size and NEMA size The horizontal power bus is located in the 12” of space Isolated and insulated vertical bus design is standard for K bus bracing and all back-to-back structures Vertical space for the TIASTAR motor control center is inches The horizontal ground bus for TIASTAR motor control centers is typically located in the 6” of space TIASTAR back-to-back structures are inches deep Review Answers Review 1) d; 2) TIASTAR; 3) 3; 4) Review 1) Underwriters Laboratories; 2) National Fire Protection Association; 3) 200,000; 4) 430-94 Review 1) B; 2) 80; 3) B; 4) A; ) B Review 1) 10; 2) 3; 3) 200; 4) f; 5) SIRIUS and SIKOSTART Review 1) 2000; 2) 100,000; 3) IP14; 4) a=A, b=B-t, c=B-d, d=C Review 1) 24; 2) 12; 3) and 1; 4) top; 5) 100; 6) 72; 7) bottom; 8) 21 75 Final Exam The final exam is intended to be a learning tool The book may be used during the exam A tear-out answer sheet is provided After completing the test, mail the answer sheet in for grading A grade of 70% or better is passing Upon successful completion of the test a certificate will be issued Questions is the trade name for a Siemens motor control center a b c d Article of the National Electrical Code® requires overcurrent protection for MCCs a b c d Principally contains branch circuit protection Floor-mounted assemblies Common horizontal bus One or more vertical sections The standard height of a vertical section is inches a b c d 76 430.94 240 ICS-1-322 430.97 Which of the following is not a part of the NEMA definition for motor control centers? a b c d SIKOSTART INNOVA PLUS SAMMS TIASTAR 72 40 90 20 The maximum shipping width of a motor control center assembly is inches a b c d According to NEC® Article 430.97, there should be a minimum distance of inch(es) of clearance between a live bus and ground a b c d INNOVA PLUS SENSITRIP III FVNR SIMOCODE-DP A NEMA size controller is rated for HP at 480 volts a b c d 10 10 20 30 is a motor protection device that is designed to work with PROFIBUS-DP a b c d A Class 20 overload relay will trip within seconds when motor current is 600% a b c d 60” 80” 90” 120” 25 50 100 Motor control centers are rated for volts a b c d 480 600 1000 1200 77 11 Up to 30 mm pilot devices can be mounted on the combination motor control unit door of a Siemens TIASTAR motor control center a b c d 12 Siemens motor control centers are manufactured with a maximum temperature rise of over 40°C ambient a b c d 13 all types are available on Class II A B C The primary standards for MCCs are established by a b c d 78 A B-t B-d C Type wiring is not available on Class II motor control centers a b c d 16 No terminal blocks are supplied on Class I, Type wiring a b c d 15 25°C 50°C 65°C 75°C Type B-t wiring can be used on starters up to size a b c d 14 ANSI, IEEE, IEC ANSI, NEC, IEC UL, IEEE, NEMA UL, NEMA, NEC® 17 TIASTAR high density units take up inches of vertical space a b c d 18 Most Siemens plug-in combination motor control units use for quick bus connect and disconnect a b c d 19 pull-apart terminal blocks two-bolt, U-shaped clamp shelf-brackets stab clips To remove a combination motor control unit from a System/89 MCC, the operating handle is placed in a b c d 20 18 12 On Off Park Tripped will allow the use of branch circuit protective units in a motor control center provided their use does not make up a major portion of the motor control center a b c d NEMA (ICS-2-322) NEC® (430.97) NEC® (430.94) UL (845) 79 quickSTEP Online Courses quickSTEP online courses are available at http://www.sea.siemens.com/step The quickSTEP training site is divided into three sections: Courses, Downloads, and a Glossary Online courses include reviews, a final exam, the ability to print a certificate of completion, and the opportunity to register in the Sales & Distributor training database to maintain a record of your accomplishments From this site the complete text of all STEP 2000 courses can be downloaded in PDF format These files contain the most recent changes and updates to the STEP 2000 courses A unique feature of the quickSTEP site is our pictorial glossary The pictorial glossary can be accessed from anywhere within a quickSTEP course This enables the student to look up an unfamiliar word without leaving the current work area 80 [...]... existing MCC) • Amp rating of the horizontal bus and finish material (tin or silver) • Voltage rating and source of control power • Size, type (aluminum or copper), number per phase and location of incoming cables or busway and outgoing cables • Enclosure - Type, finish - Accessibility (front, rear, or both) - Clearance for door swing - Restrictions on height, width, and depth • Horsepower rating and... vertical space required varies with the amperage rating When the main lugs are located on the top, as in the following illustration, the vertical space is taken at the top A motor control center can also have the lugs located at the bottom of the MCC In the following illustration, for example, main lugs rated for 600 amps are located on the top of the MCC In this example 24” of vertical space is required... units The disconnect operating handle is mounted sideways When Type B or C wiring is specified, a swing-out terminal block is supplied The motor starter is located behind the terminal block The circuit breaker is located behind the operator handle A unique “swing out” feature permits components to swing out of the unit for easy inspection or maintenance 71 Information Needed to Order MCCs When ordering... the vertical wireway This secures the terminals inside the unit when access is not required, or allows access from the vertical wireway Pull-apart terminals are available as an option Operating Handle The disconnect operating handle has four positions When placed in the “PARK” position the unit door can be opened without the handle interfering The “TRIPPED” position is clearly indicated 68 Racking Lever... use for quick bus connect and disconnect a b c d 19 pull-apart terminal blocks two-bolt, U-shaped clamp shelf-brackets stab clips To remove a combination motor control unit from a System/89 MCC, the operating handle is placed in a b c d 20 18 12 6 4 On Off Park Tripped will allow the use of branch circuit protective units in a motor control center provided their use does not make... mounted in the bottom 6” of space The horizontal ground bus is standard An optional vertical ground bus can be connected to the horizontal bus When a combination motor control unit is instered into the MCC the vertical ground bus is the first item engaged Likewise, when the unit is removed the vertical ground bus is the last thing to be disengaged Wire Tie Rods Round wire tie rods are located in each... used The space can vary from 12” to 72” In the following illustration a main circuit breaker is used Cable entry can be from the top or bottom of the vertical section 60 Review 5 1 The maximum current rating for a horizontal bus on Siemens motor control center is amps 2 The maximum bus bracing available for a Siemens motor control center is AIC 3 The IEC equivalent of a NEMA Type 3R enclosure... combination motor-control units, such as FVNR, FVR, 2S1W, 2S2W, PW, or RVAT • Type of control circuit for units • Service entrance requirements • Vertical bus requirements (finish, isolated/insulated, amp rating) • Class and Type of wiring • Additional equipment requirements (transformers, panelboards, transfer switches, PLCs, etc.) • Preferred layout of units • Special features, codes, or restrictions... test a certificate will be issued Questions 1 is the trade name for a Siemens motor control center a b c d 2 Article of the National Electrical Code® requires overcurrent protection for MCCs a b c d 3 Principally contains branch circuit protection Floor-mounted assemblies Common horizontal bus One or more vertical sections The standard height of a vertical section is inches a b... center a b c d 12 Siemens motor control centers are manufactured with a maximum temperature rise of over 40°C ambient a b c d 13 all types are available on Class II A B C The primary standards for MCCs are established by a b c d 78 A B-t B-d C Type wiring is not available on Class II motor control centers a b c d 16 3 5 6 7 No terminal blocks are supplied on Class I, Type wiring

Ngày đăng: 28/12/2015, 17:03

Từ khóa liên quan

Tài liệu cùng người dùng

  • Đang cập nhật ...

Tài liệu liên quan