1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Electric Circuits, 9th Edition P45 doc

10 1,5K 1

Đang tải... (xem toàn văn)

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Định dạng
Số trang 10
Dung lượng 321,16 KB

Nội dung

For a four-conductor circuit, we need three wattmeters if the three-phase circuit is unbalanced, but only two wattmeters if it is balanced, because in the latter case there is no current

Trang 1

416 Balanced Three-Phase Circuits

Applying this general observation, we can see that for a three-conductor circuit, whether balanced or not, we need only two wattmeters

to measure the total power For a four-conductor circuit, we need three wattmeters if the three-phase circuit is unbalanced, but only two wattmeters if it is balanced, because in the latter case there is no current in the neutral line Thus, only two wattmeters are needed to measure the total average power in any balanced three-phase system

The two-wattmeter method reduces to determining the magnitude and algebraic sign of the average power indicated by each wattmeter We can describe the basic problem in terms of the circuit shown in Fig 11.20, where the two wattmeters are indicated by the shaded boxes and labeled

W\ and W 2 The coil notations cc and pc stand for current coil and

poten-tial coil, respectively We have elected to insert the current coils of the wattmeters in lines aA and cC Thus, line bB is the reference line for the two potential coils The load is connected as a wye, and the per-phase load

impedance is designated as Z^ = \Z\ /jh This is a general representation,

as any A-connected load can be represented by its Y equivalent;

further-more, for the balanced case, the impedance angle 0 is unaffected by the

A-to-Y transformation

We now develop general equations for the readings of the two wattmeters We assume that the current drawn by the potential coil of the wattmeter is negligible compared with the line current measured by the cur-rent coil We further assume that the loads can be modeled by passive circuit

elements so that the phase angle of the load impedance (0 in Fig 11.20) lies

between -90° (pure capacitance) and +90" (pure inductance) Finally, we assume a positive phase sequence

From our introductory discussion of the average deflection of the wattmeter, we can see that wattmeter 1 will respond to the product of

|V A JJ|, |IaA^ a nd the cosine of the angle between V A B a nd IaA- M w e denote

this wattmeter reading as W h we can write

Wi - I V A B I P U C O S * ,

It follows that

W2 = |VCBI|ICC|COS02

In Eq 11.54,0] is the phase angle between VAB and Ia A, and in Eq 11.55,

0 2 is the phase angle between VCB and Ic(>

To calculate Wj and W 2 , we express 0] and 0 2 in terms of the imped-ance angle 0, which is also the same as the phase angle between the phase voltage and current For a positive phase sequence,

The derivation of Eqs 11.56 and 11.57 is left as an exercise (see Problem 11.34) When we substitute Eqs 11.56 and 11.57 into Eqs 11.54 and 11.55, respectively, we get

h t

+

v i

h

+

v 2

/3

+

v 3

m 1

• 1

• Z

*

General network

Figure 11.19 • A general circuit whose power is

supplied by n conductors

IaA

cc

A

Wi pc4 Z^ = |Z|Z0 VAN

b«-'CN

c+

-•—

c(

N

Figure 11.20 • A circuit used to analyze the

two-wattmeter method of measuring average power

delivered to a balanced load

Trang 2

(11.60)

To find the total power, we add W ] and W 2 ; thus

p T = W ] + W 2 = 2 V L / L C O S ^ C O S 3 0 "

= V 3 V L / L C O S ^ , which is the expression for the total power in a three-phase circuit

Therefore we have confirmed that the sum of the two wattmeter readings

yields the total average power

A closer look at Eqs 11.58 and 11.59 reveals the following about the

readings of the two wattmeters:

1 If the power factor is greater than 0.5, both wattmeters read positive

2 If the power factor equals 0.5, one wattmeter reads zero

3 If the power factor is less than 0.5, one wattmeter reads negative

4 Reversing the phase sequence will interchange the readings on the

two wattmeters

These observations are illustrated in the following example and in

Problems 11.41-11.51

| Computing Wattmeter Readi

Calculate the reading of each wattmeter in

circuit in Fig 11.20 if the phase voltage at

load is 120 V and (a) Z+ = 8• + ;

(b) Z0 = 8 - ;6 ft; (c) Z^ = 5 + ;5 V3 12;

(d) Z s = 10 / - 7 5 ° ft (e) Verify for (a)-(d)

the sum of the wattmeter readings equals the

power delivered to the load

Solution

a) Z (b = 10 /36.87° ft, V L = 120 V 3 V , and

/L = 120/10 = 12 A

W ] = (120V3~)(12) cos (36.87° + 30°)

= 979.75 W,

W 2 = (120 V3)(12) cos (36.87° - 30°)

= 2476.25 W

b) Z & = 10 / - 3 6 8 7 ° ft, V L = 120V^ V, and

/L= 120/10 = 12 A

Wi = (120V3)(12) cos (-36.87° + 30°)

= 2476.25 W,

W 2 = (120V3)(12) cos (-36.87° - 30°)

= 979.75 W

ngs in

the the

6 ft;

and that total

Three-Phase Circuits

c) Z^ = 5(1 + jV3) = 10 / 6 0 ° O, V L = 120V3 V,

a n d /L = 12 A

Wi = (120V5)(12) cos (60° + 30°) = 0,

W 2 = (120 V3)(12) cos (60° - 30°)

= 2160 W

d) Z 4> = 10 / - 7 5 ° ft, V L = 12QV3" V, and

/L = 12 A

Wi = (120V3)(12)cos(-75° + 30°) = 1763.63 W,

W 2 = (120V5)(12) cos (-75° - 30°) = -645.53 W

e) Pr(a) = 3(12)2(8) - 3456 W,

W } +W 2 = 979.75 + 2476.25

= 3456 W,

Pr(b) = Pr(a) = 3456 W,

Wi + W 2 = 2476.25 + 979.75

= 3456 W, /V(c) = 3(12)2(5) = 2160 W,

W t + W 2 = 0 + 2160

= 2160W,

Pr(d) = 3(12)2(2.5882) = 1118.10 W,

Wi + W 2 = 1763.63 - 645.53

= 1118.10W

NOTE: Assess your understanding of the two-wattmeter method by trying Chapter Problems 11.43 and 11.44

Trang 3

418 Balanced Three-Phase Circuits

3-0 line -)

Generator

Plant

4

*)

/

Sub Station

Figure 11.21 A A substation connected to a power

plant via a three-phase line

0.6 O

- A W - /4.8 n

^ Y Y Y V

A

v.„ 13,800 /r\0 y ^3 *~ MW 1.2 MVAR 1.2

n N

Figure 11.22 • A single phase equivalent circuit for

the system in Fig 11.21

Practical Perspective

Transmission and Distribution of Electric Power

At the start of this chapter we pointed out the obligation utilities have to maintain the rms voltage level at their customer's premises Although the acceptable deviation from a nominal level may vary among different utilities

we will assume for purposes of discussion that an allowable tolerance is

± 5.8% Thus a nominal rms voltage of 120 V could range from 113 to

127 V We also pointed out that capacitors strategically located on the sys-tem could be used to support voltage levels

The circuit shown in Fig 11.21 represents a substation on a Midwestern municipal system We will assume the system is balanced, the line-to-line voltage at the substation is 13.8 k V , the phase impedance of the distribu-tion line is 0.6 + /4.811, and the load at the substadistribu-tion at 3 PM on a hot, humid day in July is 3.6 M W and 3.6 magnetizing M V A R

Using the line-to-neutral voltage at the substation as a reference, the single-phase equivalent circuit for the system in Fig 11.21 is shown in Fig 11.22 The line current can be calculated from the expression for the complex power at the substation Thus,

13,800

V3 I*A = (1.2 + /1.2)10*

It follows that

or

I*A = 150.61 + /150.61 A

I a A = 150.61 - /150.61 A The line-to-neutral voltage at the generating plant is

13,800

V3 '0° + (0.6 + /4.8)(150.61 - /150.61)

= 8780.74 + /632.58

= 8803.50/4.12° V

Therefore the magnitude of the line voltage at the generating plant is

|V ab | = V3(8803.50) = 15,248.11V

We are assuming the utility is required to keep the voltage level within

± 5.8% of the nominal value This means the magnitude of the line-to-line

voltage at the power plant should not exceed 14.6 k V nor be less than

13 k V Therefore, the magnitude of the line voltage at the generating plant could cause problems for customers

When the magnetizing vars are supplied by a capacitor bank connected

to the substation bus, the line current I a A becomes

I = 150.61 + /0 A

Trang 4

Therefore the voltage at the generating plant necessary to maintain a

line-to-line voltage of 13,800 V at the substation is

13,800

Van = - ^ - /O: + (0-6 + /4.8)(150.61 + /0)

= 8057.80 + /722.94

= 8090.17/5.13° V

Hence

|Vab| = V3(8090.17) = 14,012.58 V

This voltage level falls within the allowable range of 13 kV to 14.6 kV

NOTE: Assess your understanding of this Practical Perspective by trying Chapter

Problems 11.52(a)-(b) and 11.53, 11.56, and 11.57

Summary

• When analyzing balanced three-phase circuits, the first

step is to transform any A connections into Y connections,

so that the overall circuit is of the Y-Y configuration (See

page 402.)

• A single-phase equivalent circuit is used to calculate the

line current and the phase voltage in one phase of the

Y-Y structure The a-phase is normally chosen for this

purpose (See page 404.)

• Once we know the line current and phase voltage in the

a-phase equivalent circuit, we can take analytical

short-cuts to find any current or voltage in a balanced

three-phase circuit, based on the following facts:

• The b- and c-phase currents and voltages are

identi-cal to the a-phase current and voltage except for a

120° shift in phase In a positive-sequence circuit, the

b-phase quantity lags the a-phase quantity by 120°,

and the c-phase quantity leads the a-phase quantity

by 120° For a negative sequence circuit, phases b and

c are interchanged with respect to phase a

• The set of line voltages is out of phase with the set of

phase voltages by ±30° The plus or minus sign

corre-sponds to positive and negative sequence, respectively

• In a Y-Y circuit the magnitude of a line voltage is

V3 times the magnitude of a phase voltage

• The set of line currents is out of phase with the set of phase currents in A-connected sources and loads by T30° The minus or plus sign corresponds to positive and negative sequence, respectively

• The magnitude of a line current is V 3 times the mag-nitude of a phase current in a A-connected source

or load, (See pages 404-405 and 407-408.)

• The techniques for calculating per-phase average power, reactive power, and complex power are identical

to those introduced in Chapter 10 (See page 410.)

• The total real, reactive, and complex power can be deter-mined either by multiplying the corresponding per phase quantity by 3 or by using the expressions based on line current and line voltage, as given by Eqs 11.36,11.38, and 11.41 (See pages 410 and 411.)

• The total instantaneous power in a balanced three-phase circuit is constant and equals 1.5 times the average power per phase (See page 412.)

• A wattmeter measures the average power delivered to a load by using a current coil connected in series with the load and a potential coil connected in parallel with the load (See page 415.)

• The total average power in a balanced three-phase cir-cuit can be measured by summing the readings of two wattmeters connected in two different phases of the circuit (See page 415.)

Trang 5

420 Balanced Three-Phase Circuits

Problems

AH phasor voltages in the following Problems are stated in

terms of the rms value

Section 11.1

11.1 Verify that Eq 11.3 is true for either Eq 11.1 or

Eq.11.2

11.2 What is the phase sequence of each of the following

sets of voltages?

a) ya = 208 cos (OJ? + 27°) V,

^ = 208 cos (cot + 147°) V,

v c = 208 cos (cot - 93°) V

b) v a = 4160 cos (cot - 18°) V,

v b = 4160 cos (cot - 138°) V,

?;c = 4160 cos (cot + 102°) V

11.3 For each set of voltages, state whether or not the

volt-PSPICE ages form a balanced three-phase set If the set is

bal-anced, state whether the phase sequence is positive or

negative If the set is not balanced, explain why

a) v a = 139 cos 377? V,

v b = 139 cos (377? + 120°) V,

v c = 139 cos (377? - 120°) V

b) v d = 381 cos 377? V,

v b = 381 cos (377? + 240°) V,

v c = 381 cos (377? + 120°) V

c) v a = 2771 sin (377? - 30°) V,

v b = 2771 cos 377? V,

v c = 2771 sin (377? + 210°) V

d) v A = 170 sin (cot + 30°) V,

v b = - 1 7 0 cos cot V,

v c = 170 cos (cot + 60°) V

e) v a = 339 cos cot V,

% = 339 cos (cot + 120) V,

v c = 393 cos (cot - 120°) V

f) v A = 3983 sin (cot + 50°) V,

v b = 3983 cos (cot - 160°) V,

v c = 3983 cos (cot + 70°) V

Section 11.2 11.4 Refer to the circuit in Fig 11.5(b) Assume that there

are no external connections to the terminals a,b,c Assume further that the three windings are from a balanced three-phase generator How much current will circulate in the A-connected generator?

Section 11.3 11.5 A balanced three-phase circuit has the following

characteristics:

• Y-Y connected;

• The line voltage at the source, Vab, is

240 V3~/90° V;

• The phase sequence is negative;

• The line impedance is 4 -I- /5 £l/<f>',

• The load impedance is 76 + /55 ft/cf)

a) Draw the single phase equivalent circuit for the a-phase

b) Calculated the line current in the a-phase c) Calculated the line voltage at the load in the a-phase

11.6 Find the rms value of I„ in the unbalanced

three-phase circuit seen in Fig PI 1.6

Figure PI 1.6

0.1 n /0.8ft a 0.4 ft /3.2 ft A 59.5 ft /76 ft

->WV »****"¥"> 0 /yy*^ ( V Y Y > 0 ' W W

0.1ft /0.8 ft b 0.4 ft /3.2 ft B 39.5 ft /26 ft

- • "VS/V r r v Y > 9 V W —

M ^ 240/-240/-120° V

0.1ft /0.8 ft c 0.4 ft /3.2 ft C 19.5 ft / l i f t

- • /vW «^w> » VW rvw>_

N

Trang 6

11.7 The time-domain expressions for three line-to-neutral

voltages at the terminals of a Y-connected load are

v AN = 7620 cos (W + 30°) V,

v m = 7620 cos (a)t + 150°) V,

'»CN = 7620 cos (cot - 90") V

What are the time-domain expressions for the three

line-to-line voltages v Aii , I>BO and VQA?

11.8 a) Is the circuit in Fig PI 1.8 a balanced or

unbal-PSPICE anced three-phase system? Explain

MULTISIM

b) Find I„

Figure PI 1.8

^2()0 /0!V

11.9 The magnitude of the line voltage at the terminals

of a balanced Y-connected load is 6600 V The load

impedance is 240 - /70 0/<£ The load is fed from a

line that has an impedance of 0.5 + /4 0/(£

a) What is the magnitude of the line current?

b) What is the magnitude of the line voltage at

the source?

11.10 a) Find I„ in the circuit in Fig PI 1.10

c) FindVA B

d) Is the circuit a balanced or unbalanced

three-phase system?

11.11 The magnitude of the phase voltage of an ideal

balanced three-phase Y-connected source is

125 V The source is connected to a balanced Y-connected load by a distribution line that has an

impedance of 0.1 + /0.8 Cl/<j) The load impedance

is 19.9 + /14.2 Cl/4> The phase sequence of the

source is acb Use the a-phase voltage of the source as the reference Specify the magnitude and phase angle of the following quantities: (a) the three line currents, (b) the three line voltages at the source, (c) the three phase voltages at the load, and (d) the three line voltages at the load

Section 11.4 11.12 A balanced, three-phase circuit is characterized as

follows:

• Y-A connected;

• Source voltage in the c-phase is 2 0 / - 9 0 ° V;

• Source phase sequence is abc;

• Line impedance is 1 + / 3 CL/<f>;

• Load impedance is 117 — /99 12/(/)

a) Draw the single phase equivalent for the a-phase b) Calculate the a-phase line current

c) Calculate the a-phase line voltage for the three-phase load

11.13 An acb sequence balanced three-phase Y-connected

source supplies power to a balanced, three-phase

A-connected load with an impedance of 12 + /9 fl/4>

The source voltage in the b-phase is 2 4 0 / - 5 0 ° V

The line impedance is 1 + /1 fl/4> Draw the single

phase equivalent circuit for the a-phase and use it

to find the current in the a-phase of the load

11.14 A balanced A-connected load has an impedance of

864 — /252 Q,/(f) The load is fed through a line hav-ing an impedance of 0.5 4- /4 Q/<f) The phase

volt-age at the terminals of the load is 69 kV The phase sequence is positive Use VA B as the reference a) Calculate the three phase currents of the load b) Calculate the three line currents

c) Calculate the three line voltages at the sending end of the line

Figure P11.10

0.4 ft /212 a 1.6 n

- v w - /4 ft - A l V i r 7811

/54 a

O Till (FV

/1.6 b 2.6 0 /2.4 ft B 77 fl /56 O

— • W V o o o r > 1 w ^

0.2 ft /1.2 ft c 0.8 ft /3.8 ft C 79 ft /55 ft

N

Trang 7

422 Balanced Three-Phase Circuits

11.15 A balanced Y-connected load having an

imped-ance of 72 + /21 Cl/(f) is connected in parallel with

a balanced A-connected load having an

imped-ance of 150/0° Q,/<f> The paralleled loads are fed

from a line having an impedance of /1 0/4> The

magnitude of the line-to-neutral voltage of the

Y-load is 7650 V

a) Calculate the magnitude of the current in the

line feeding the loads

b) Calculate the magnitude of the phase current in

the A-connected load

c) Calculate the magnitude of the phase current in

the Y-connected load

d) Calculate the magnitude of the line voltage at

the sending end of the line

11.16 In a balanced three-phase system, the source is a

bal-anced Y with an abc phase sequence and a line voltage

Va b = 208/50° V The load is a balanced Y in

paral-lel with a balanced A.The phase impedance of the Y is

4 + / 3 il/cf) and the phase impedance of the A is

3 - /9 0./4) The line impedance is 1.4 -I- /0.8 Oj4>

Draw the single phase equivalent circuit and use it to

calculate the line voltage at the load in the a-phase

11.17 The impedance Z in the balanced three-phase

cir-cuit in Fig PI 1.17 is 100 - /75 O Find

a) IAB> I B O and I C A ,

b) IaA* \ ^ and IcC,

c) Iba, Icb, and Iac

Figure P11.17

13.2/-120° kV

11.18 For the circuit shown in Fig PI 1.18, find

PSPKE a) the phase currents IA B, IRC, and IC A

b) the line currents IaA, IbB, and FcC

when Z, = 2.4 - /0.7 ft, Z2 = 8 + /6 Q, and

Z3 = 20 + / 0 ft

Figure P11.18

a A

480/-120° V

11.19 A three-phase A-connected generator has an

inter-nal impedance of 9 -(- /90 mft/<jf> When the load is removed from the generator, the magnitude of the terminal voltage is 13,800 V The generator feeds a A-connected load through a transmission line with

an impedance of 20 + /180 m f t / $ The per-phase impedance of the load is 7.056 + /3.417 ft

a) Construct a single-phase equivalent circuit b) Calculate the magnitude of the line current c) Calculate the magnitude of the line voltage at the terminals of the load

d) Calculate the magnitude of the line voltage at the terminals of the source

e) Calculate the magnitude of the phase current in the load

f) Calculate the magnitude of the phase current in the source

11.20 A balanced three-phase A-connected source is

shown in Fig PI 1.20

a) Find the Y-connected equivalent circuit

b) Show that the Y-connected equivalent circuit delivers the same open-circuit voltage as the original A-connected source

c) Apply an external short circuit to the terminals

A, B, and C Use the A-connected source to find the three line currents Ia A, IbB, and IcC

d) Repeat (c) but use the Y-equivalent source to find the three line currents

Figure PI 1.20

• A

2.7 O

/13.511

4156/-120° V

• C

11.21 The A-connected source of Problem 11.20 is

con-nected to a Y-concon-nected load by means of a bal-anced three-phase distribution line The load

Trang 8

impedance is 1910-/636 fl/<f) and the line

imped-ance is 9.1 + /71.5(2/0

a) Construct a single-phase equivalent circuit of

the system

b) Determine the magnitude of the line voltage at

the terminals of the load

c) Determine the magnitude of the phase current

in the A-source

d) Determine the magnitude of the line voltage at

the terminals of the source

11.27 The three pieces of computer equipment described

below are installed as part of a computation center Each piece of equipment is a balanced three-phase load rated at 208 V Calculate (a) the magnitude of the line current supplying these three devices and (b) the power factor of the combined load

• Hard Drive: 4.864 kW at 0.79 pf lag

• CD/DVD drive: 17.636 kVA at 0.96 pf lag CPU: line current 73.8 A, 13.853 kVAR

11.28 Calculate the complex power in each phase of the

unbalanced load in Problem 11.18

Section 11.5

11.22 In a balanced three-phase system, the source

has an abc sequence, is Y-connected, and

Van = 120/20° V The source feeds two loads, both

of which are Y-connected The impedance of load 1

is 8 + /6 il/cf) The complex power for the a-phase

of load 2 is 600/36° VA Find the total complex

power supplied by the source

11.23 A balanced three-phase source is supplying 60 kVA

at 0.6 lagging to two balanced Y-connected parallel

loads The distribution line connecting the source to

the load has negligible impedance Load 1 is purely

resistive and absorbs 30 kW Find the per-phase

impedance of Load 2 if the line voltage is 120 V5 V

and the impedance components are in series

11.24 A three-phase positive sequence Y-connected

source supplies 14 kVA with a power factor of 0.75

lagging to a parallel combination of a Y-connected

load and a A-connected load The Y-connected load

uses 9 kVA at a power factor of 0.6 lagging and has

an a-phase current of 1 0 / - 3 0 ° A

a) Find the complex power per phase of the

A-connected load

b) Find the magnitude of the line voltage

11.29 A balanced three-phase distribution line has an

impedance of 1 + /8 fl/</> This line is used to sup-ply three balanced three-phase loads that are con-nected in parallel The three loads are L! = 120 kVA at 0.96 pf lead, L2 = 180 kVA at 0.80 pf lag, and L3 = 100.8 kW and 15.6 kVAR (magnetizing) The magnitude of the line voltage at the terminals of the loads is 2400 V3 V

a) What is the magnitude of the line voltage at the sending end of the line?

b) What is the percent efficiency of the distribution line with respect to average power?

11.30 The line-to-neutral voltage at the terminals of the

balanced three-phase load in the circuit shown in Fig PI 1.30 is 1200 V At this voltage, the load is absorbing 500 kVA at 0.96 pf lag

a) Use VA N as the reference and express Ina in polar form

b) Calculate the complex power associated with the ideal three-phase source

c) Check that the total average power delivered equals the total average power absorbed

d) Check that the total magnetizing reactive power delivered equals the total magnetizing reactive power absorbed

11.25 The total apparent power supplied in a balanced,

three-phase Y-A system is 4800 VA The line

volt-age is 240 V If the line impedance is negligible and

the power factor angle of the load is - 5 0 ° ,

deter-mine the impedance of the load

11.26 Show that the total instantaneous power in a

bal-anced three-phase circuit is constant and equal to

1,5V m I m cos 0$, where V m and I m represent the

maximum amplitudes of the phase voltage and

phase current, respectively

Figure PI 1.30

0.18 fi J iA4n

# Vs/V ^VY-r>_

:-/180 a

0.18 0 /1.44«

— / y y V e-v-Y-v>_

0.18 a /1-440

* W V i^r>nr\_

A

500 kVA

0.% pf lag

-•C

Trang 9

4 2 4 Balanced Three-Phase Circuits

PSPICE

MULTISIM

11.31 a) Find the rms magnitude and the phase angle of

IC A in the circuit shown in Fig PI 1.31

b) What percent of the average power delivered by

the phase source is dissipated in the

three-phase load?

Figure PI 1.31

/2 ft a 1.5 ft

-•—'vw-f^J 1365/0!

6

565/0° V

/2 0 b i.5r>

1365/-120° V

1365/120° V

/2 ft

:85.5 0 /114 a

B 85.5 XI

!yii4n

:85.5 ft

;/ii4 n

c 1.5 ft

11.32 At full load, a commercially available 100 hp,

three-phase induction motor operates at an efficiency of

97% and a power factor of 0.88 lag The motor is

sup-plied from a three-phase outlet with a line-voltage

rating of 208 V

a) What is the magnitude of the line current drawn

from the 208 V outlet? (1 hp = 746 W.)

b) Calculate the reactive power supplied to

the motor

11.33 Three balanced three-phase loads are connected in

parallel Load 1 is Y-connected with an impedance

of 400 + /300 ft/0; load 2 is A-connected with an

impedance of 2400 - /1800 ft/<£; and load 3 is

172.8 + /2203.2 kVA The loads are fed from a

dis-tribution line with an impedance of 2 + /16 fl/cj)

The magnitude of the line-to-neutral voltage at the

load end of the line is 24 V 3 kV

a) Calculate the total complex power at the

send-ing end of the line

b) What percentage of the average power at the

sending end of the line is delivered to the loads?

11.34 A three-phase line has an impedance of

0.1 + /0.8 Cl/(f) The line feeds two balanced

three-phase loads connected in parallel The first

load is absorbing a total of 630 kW and absorbing

840 kVAR magnetizing vars The second load

is Y-connected and has an impedance of

15.36 - /4.48 0,/4> The line-to-neutral voltage at

the load end of the line is 4000 V What is the

magnitude of the line voltage at the source end of

the line?

11.35 A balanced three-phase load absorbs 96 kVA at a

lagging power factor of 0.8 when the line voltage at the terminals of the load is 480 V Find four equiva-lent circuits that can be used to model this load

11.36 The total power delivered to a balanced

three-phase load when operating at a line voltage of

2400 V3 V is 720 kW at a lagging power factor of 0.8 The impedance of the distribution line

sup-plying the load is 0.8 + /6.4 Q,/<fi Under these

operating conditions, the drop in the magnitude

of the line voltage between the sending end and the load end of the line is excessive To compen-sate, a bank of A-connected capacitors is placed

in parallel with the load The capacitor bank is designed to furnish 576 kVAR of magnetizing reactive power when operated at a line voltage

of 2400 V3 V

a) What is the magnitude of the voltage at the sending end of the line when the load is operat-ing at a line voltage of 2400 V3 V and the capac-itor bank is disconnected?

b) Repeat (a) with the capacitor bank connected c) What is the average power efficiency of the line

in (a)?

d) What is the average power efficiency in (b)? e) If the system is operating at a frequency of 60 Hz, what is the size of each capacitor in microfarads?

11.37 A balanced bank of delta-connected capacitors is

connected in parallel with the load described in Assessment Problem 11.9 The effect is to place a capacitor in parallel with the load in each phase The line voltage at the terminals of the load thus remains at 2450 V The circuit is operating at a fre-quency of 60 Hz.The capacitors are adjusted so that the magnitude of the line current feeding the paral-lel combination of the load and capacitor bank is at its minimum

a) What is the size of each capacitor in microfarads? b) Repeat (a) for wye-connected capacitors

c) What is the magnitude of the line current?

11.38 A balanced three-phase source is supplying 150 kVA

at 0.8 pf lead to two balanced Y-connected parallel loads The distribution line connecting the source to the load has negligible impedance The power associ-ated with load 1 is 30 + /30 kVA

a) Determine the types of components and their impedances in each phase of load 2 if the line voltage is 2500 V 3 V and the impedance compo-nents are in series

b) Repeat (a) with the impedance components in parallel

Trang 10

11.39 The output of the balanced positive-sequence

three-phase source in Fig PI 1.39 is 41.6 kVA at a

lagging power factor of 0.707 The line voltage at

the source is 240 V

a) Find the magnitude of the line voltage at the load

b) Find the total complex power at the terminals of

the load

Figure P11.39

Balanced

three-phase'

source

0.04 n / ° -0 3 n

W V /-Y-YV^_

0.04 a / ° - 0 3 n

—Vs/V /"YVY-N—

0.04 0 /0-°3 U

—VvV o r - o r ^

Balanced

"•three-phase load

11.43 The two wattmeters in Fig 11.20 can be used to

compute the total reactive power of the load

a) Prove this statement by showing that

V3(W 2 - Wj) = V 3 VL/Ls i i i V b) Compute the total reactive power from the wattmeter readings for each of the loads in Example 11.6 Check your computations by cal-culating the total reactive power directly from the given voltage and impedance

11.44 The two-wattmeter method is used to measure the

power at the load end of the line in Example 11.1 Calculate the reading of each wattmeter

11.45 The wattmeters in the circuit in Fig 11.20 read as

follows: W x = 40,823.09 W, and W 2 = 103,176.91 W

The magnitude of the line voltage is 2400 V 5 V The phase sequence is positive Find Z^

Section 11.6

11.40 Derive Eqs 11.56 and 11.57

11.41 In the balanced three-phase circuit shown in

Fig PI 1.41, the current coil of the wattmeter is

con-nected in line aA, and the potential coil of the

wattmeter is connected across lines b and c Show

that the wattmeter reading multiplied by V 3 equals

the total reactive power associated with the load

The phase sequence is positive

Figure PI 1.41

11.46 a) Calculate the reading of each wattmeter in the

circuit shown in Fig PI 1.46 The value of Z^ is

4 0 / - 3 0 ° a

b) Verify that the sum of the wattmeter readings equals the total average power delivered to the A-connected load

Figure PI 1.46

24Q/W V |

a •

K m

D •

r

-C'

±

cc

[

[

W

1

1

pcj

A

B

C

Z<b

z*

z*

N

b l ±

Wi

-1-) »_| /-YVV^

240/120o~V~

4 ^ 240/-120° V

-•

W,

+ ™ ~ l-\c

11.42 The line-to-neutral voltage in the circuit in

Fig PI 1.41 is 680 V, the phase sequence is positive,

and the load impedance is 16 - j 12 0 / $

a) Calculate the wattmeter reading

b) Calculate the total reactive power associated

with the load

11.47 The two-wattmeter method is used to measure

the power delivered to the unbalanced load in Problem 11.18 The current coil of wattmeter 1 is placed in line aA and that of wattmeter 2 is placed in line bB

a) Calculate the reading of wattmeter 1

b) Calculate the reading of wattmeter 2

c) Show that the sum of the two wattmeter read-ings equals the total power delivered to the unbalanced load

Ngày đăng: 06/07/2014, 16:20

TỪ KHÓA LIÊN QUAN

w