TTĐH THÔNG TIN-VNPT NGHỆ AN HƯỚNG DẪN CÀI ĐẶT THAM SỐ CÁC LOẠI TỦ NGUỒN I- TỦ NGUỒN EMERSON PS48300-3B/2900, PS48300-3/2900-X1 HOẶC TỦ EMERSON DÙNG CARD ĐIỀU KHIỂN M500 Password vào tủ: 1- Cài đặt tham số ắc quy, Rect, AC, DC Main Menu Menu level Menu level Giá trị đặt Menu level Mode Auto Batt String Số tổ ắc quy Batt Selection Tổng dung lượng ắc Capacity quy LLVD Enable Y BLVD Enable Y LVD Setting LVD Mode Voltage LVD VOLTAGE->LLVD 44 LVD VOLTAGE->BLVD 43.2 Float 54 Boost 56 Battery Charge Limit 0.100C10 Setting Over 0.300C10 Temp Battery Temp None Center Temp 25 Settings Temp Comp 72mV/C/Str BATTERY TEMP Temp Comp 70 ALARM->Over BATTERY TEMP 35 ALARM->High BATTERY TEMP ALARM-Low OverVolt 280 LowVolt 180 AC UnderVolt 80 Setting Theo thực tế (3 AC Input Phase Phase) Over 58.5 DC Low 47.5 Settings Under 47.5 Rect Walk-in Y Settings Enable TTĐH THÔNG TIN-VNPT NGHỆ AN Walk-in Time Interval Start Basic Sys Settings Advance Set Date Set Time Save Enable Cycle Duration tủ DC: 120; tủ DC: DC1 (60), DC2 (120) 10s Ngày Giờ Y 168h 2- Cài đặt tham số cảnh báo Main Menu Settings Menu level Alarm Settings Menu level Alarm Level Alarm Type Mains Failure Multi-Rect Fails Rect Not Respond Rect AC Fault Rect Over Temp Rect Failure Rect Protect Rect Fan Fails Rect Derated DC Under Voltage DC Voltage Low Temp High Alarm Out Relay 3 3 3 3 2 TTĐH THÔNG TIN-VNPT NGHỆ AN II- CÀI ĐẠT THAM SỐ TỦ NGUỒN EMERSON NETSURE 701 Pass: 640275 1- Cài đặt tham số ắc quy, AC, DC Main Menu level Menu level Menu level Giá trị đặt Menu Sys Mode Auto Bat Fuse Số tổ ắc quy Basic Settings Tổng dung lượng ắc Capacity quy Bat Shunt Y LVD1 Enable Y LVD2 Enable Y LVD Settings LVD1 Volt 44 LVD2 Volt 43.2 Float 54 Bat Settings Boost 56 Charge Limit 0.100C10 Over 0.300C10 Temp BattTemp Temp None Center Temp 25 Temp Comp Coeff 72mV/C Settings Batt T H2 70 Batt T H1 35 Batt T L1 OverVolt 280 LowVolt 180 Input Settings UnderVolt 80 Theo thực tế (3 Phase AC PH Phase) LowVolt1 47.5 DC Settings LowVolt2 47.5 Walk-in On Y tủ DC: 120; tủ Rect Settings Walk-in T DC: DC1 (60), DC2 (120) Interval T 10s Set Date Ngày Sys Settings Set Time Giờ Y Energy Save Enable Saving Cyc Period 168h TTĐH THÔNG TIN-VNPT NGHỆ AN 2- Cài đặt tham số cảnh báo Main Menu level Menu level Menu Settings Alarm Settings Alarm Level Alarm Type Input Failure Rect Overload Rect InputFail Rect TempHigh Rect Fail Rect Protect Rect FanFail Rect Derated Rect HVSD Rect Loadshare DC Volt LowDC Volt Low Temp High Temp High Out Relay 3 3 3 3 2 7 TTĐH THÔNG TIN-VNPT NGHỆ AN III- CÀI ĐẶT THAM SỐ TỦ NGUỒN EMERSON NETSURE 731 1- Kết nối máy tính với card điều khiển tủ nguồn dây LAN Sử dụng trình duyệt web để kết nối Sử dụng địa kết nối: 192.168.100.100 (đặt địa máy tính 192.168.100.101) Account/ Password: admin/640275 2- Cài đặt tham số ắc quy, Rect, AC, DC Battery Charger LVD Signal Float Charger Voltage Equalize Charger Voltage Battery Current Limit Over Current Limit Temp Comp Coefficient EQTemp Comp Coefficient Over Voltage Over Voltage Under Voltage Under Voltage Batt1 Rate Capacity LVD LVD Mode LVD Voltage LVD LVD Mode LVD Voltage Value 54 56 0.10C10 0.30C11 72.0 mV/deg.C 72.0 mV/deg.C 57 58.5 47.5 47.5 Dung lượng ắc quy Enable Voltage 44 Enable Voltage 43.2 3- Cài đặt tham số cảnh báo Alarm Name AC Input Fail Rect Temperature High Rectifier Fail HVSD Rectifier Protected Fan Fail Current Limit Rectifier Communication Fail Derated Multiple Rectifiers Fail Mains Failure Under voltage Under voltage Relay Number IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO3 IB1-DO1 IB1- DO2 IB1- DO2 TTĐH THÔNG TIN-VNPT NGHỆ AN IV- TỦ NGUỒN AGISSON TP48300A (Card điều khiển CPMU01) Password: 0001 1- Cài đặt tham số ắc quy, Rect, AC, DC Main menu Menu level Menu level Ngày Time Giờ Eng Setting AC Setting UnderVolt DC Setting UnderVolt Batt Setting LVD Setting Battery Setting Value Date System Setting Setting Menu level Charge Temp Coeff Rect Slepp Yes Rect Exch Sleep days Best Effi Point 80% Setting Menu level Alarm Setting Menu level Relay Relate Chế độ tiết kiệm lượng Pass: 11 180V Batt String Cap Cap LLVD Enable BLVD Enable LLVD BLVD Float Boost Cyc BC Duration Curr Limit 47.5 Tổng số tổ ắc quy Dung lượng tổ Dung lượng tổ Yes Yes 44 43.2 54 56 30 day 0.10C10 Temp Comp Basic Batt Temp Comp 72mV/C High Temp Alarm 35C 2- Cài đặt tham số cảnh báo Main menu Note Alarm RelateRelay AC_OFF DC_Low_Volt Rect_Fail Single_Rect_Fail Multi_Rect_Fail Rect_Comm_Fail Batt_Temp_Alarm 3 Chế độ bù nhiệt TTĐH THÔNG TIN-VNPT NGHỆ AN V- TỦ NGUỒN HUAWEI TP48300B N04C2 Password: 00001 1- Cài đặt tham số ắc quy, Rect, AC, DC Vào Main Menu thực cài đặt tham số sau Menu level Menu level Basic Parameter LLVD Parameters AC&DC Volt.Para Power System Sensor Config Para Energy Saving Menu level AC Type LLVD Enable LLVD mode LLVD Voltage LLVD Con.Volt AC UnderVolt Thres DC UnderVolt Thres DC Ultra UnderVolt Thres Ambient Temp Sensor Batt Temp Sensor Note Three Phases Yes Voltage Mode 44 50V 180V 47.5 47.5 Yes Yes Walk - in enable tủ DC: 120S tủ DC: DC1:60s; DC2:120s Hibernation Enable Yes Hibernation Mode Intelligent Mode Best Efficiency Pt 80% Hiber Stop Duration 168h Rate Capacity Basic Parameter FC Voltage EC Voltage Charge Limit Coef BLVD Enable Cắm dây sensor nhiệt vào Temp1 Cắm dây sensor Yes nhiệt vào Batt temp Walk - in enable Battery1 connected Battery2 connected Battery Value Chế độ tiết kiệm lượng Yes Yes Tổng dung lượng acquy 54 56 0.1C10 Yes Giới hạn dòng nạp acquy TTĐH THƠNG TIN-VNPT NGHỆ AN Temp Comp Para BLVD Parameters Temp Prot Para TC Coefficient 72mV/degC Nominal Temperature BLVD mode BLVD Voltage BLVD Con Volt Voltage Mode 43.2 50V HT Alarm Thres 35degC Chế độ bù nhiệt acquy 25 degC Ngưỡng cảnh báo nhiệt độ cao 2- Cài đặt tham số cảnh báo Trên card điều khiển: Vào Main Menu->Parameters Settings->Alarm Parameters->Do Dry Contact Para DO dry contact ALM1 Alarm Action ALM2 Alarm Action ALM3 Alarm Action ALM4 Alarm Action ALM5 Alarm Action ALM6 Alarm Action ALM7 Alarm Action ALM8 Alarm Action Open Open Open Close Close Close Open Close Sự cố tủ nguồn DC DC thấp Sự cố Rect Nhiệt độ cao Chỉ mở Open tiếp điểm sử dụng, lại để Close Trên card điều khiển: Vào Main Menu->Parameters Settings->Alarm Parameters->Alarm Config Menu level Menu level Power System Alarm config Rectifier Alarm Setting Rectifier Group Alarm Setting Battery group alarm setting Menu level Alarm Enable Alarm Severity Relay AC Failure Enable Major ALM1 AC Ph.L1 Failure AC Ph.L2 Failure AC Ph.L3 Failure DC Ultra Undervolt DC Undervolt Enable Enable Enable Enable Enable Major Major Major Critical Critical ALM1 ALM1 ALM1 ALM2 ALM2 Rectifier Fault Enable Major ALM3 Rectifier Power Failure Enable Major ALM3 Rectifier Missing Enable Major ALM3 Batt High Temp Enable Major ALM7 Batt Very HT Enable Major ALM7 TTĐH THÔNG TIN-VNPT NGHỆ AN VI- TỦ NGUỒN POWER ONE Password: 1234 Menu level Menu level Alarm Limits Adjust Limits Menu level Low Voltage High Voltage Over Voltage Load/Battery Disconnect Partial disconnect Load/Battery Reconnect High Load Temperature Alarm High Temperature Alarm Low Batt Cur Limit Battery Current limit Battery Current limit Temperation Compensation Battery Setting Select Adjust U1-U4 U1 Normal Voltage U2 Boost Voltage Giá trị 47.5 57.4 58.5 43.2 44 51 80 35 On Tổng dung lượng ắc quy chia 10 Battery Capacity Tổng dung lượng ắc quy 54 56 ... Alarm Out Relay 3 3 3 3 2 TTĐH THÔNG TIN-VNPT NGHỆ AN II- CÀI ĐẠT THAM SỐ TỦ NGUỒN EMERSON NETSURE 701 Pass: 640275 1- Cài đặt tham số ắc quy, AC, DC Main Menu level Menu level Menu level Giá... Password: 00001 1- Cài đặt tham số ắc quy, Rect, AC, DC Vào Main Menu thực cài đặt tham số sau Menu level Menu level Basic Parameter LLVD Parameters AC&DC Volt.Para Power System Sensor Config Para Energy... DC1 (60), DC2 (120) Interval T 10s Set Date Ngày Sys Settings Set Time Giờ Y Energy Save Enable Saving Cyc Period 168h TTĐH THÔNG TIN-VNPT NGHỆ AN 2- Cài đặt tham số cảnh báo Main Menu level Menu