1. Trang chủ
  2. » Tất cả

D0101-218.PDF

11 2 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Cấu trúc

  • 除灰MCC动力 cable sizing (新)

  • 除灰MCC动力电缆cable sizing(1-12)

Nội dung

21 Jan 2015 Yang Sirui Qin Gaoyuan Sun Jingyu Zhou Xiang DH1/A3-C2/DE/E/1097 23 MAY.2014 Yang Sirui Qin Gaoyuan Sun Jingyu Zhou Xiang DH1/A3-C2/DE/E/0956 15 APR.2014 Yang Sirui Qin Gaoyuan Sun Jingyu Zhou Xiang DH1/A3-C2/DE/E/0828 MAR.2014 Yang Sirui Qin Gaoyuan Sun Jingyu Zhou Xiang First issue DATE PREPARED BY CHECKED BY REVIEWED BY APPROVED BY DESCRIPTION OWNER VIETNAM ELECTRICITY THERMAL POWER PROJECT MANAGEMENT BOARD CONSULTANT POWER ENGINEERING CONSULTING JOINT STOCKCOMPANY CONTRACTOR DONGFANG ELECTRIC CORPORATION LIMITED SUBCONTRACTOR GUANGDONG ELECTRIC POWER DESIGN INSTITUTE EVN Ref No.: DH1/TD/795/023/001/00 DEC Ref No.: DH1_DDBSE3_D_0101_218 PROJECT: Document Status: DUYEN HAI THERMAL POWER PLANT PROJECT CONTRACT NO.: DH1-30032010 FOR APPROVAL Document Title: Cable Sizing Study For 400V/230V Cable Of Air Compressing MCC Document No.: Rev.: F4281S-D0101-218 DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study CONTENTS General Introduction Reference Documents 3 Cable Sizing Criteria Cable Installation Method Voltage Drop Current Carrying Capacity Short Circuit Calculation ATTACHMENT Table of Cable Sizing Calculation DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study General Introduction The purpose of this document is to show the cable selection methods for cable sizing and cable voltage drop calculation for MV and LV Power Cable including 6.6kV AC power cable and 0.6/1kV AC power cable.data Input: For sizing of the cables the following conditions will apply: a) Soil temperature for cables Not less than 30 °C at 1m depth direct buried or indirect buried ducts b) Soil thermal resistivity (Refer 1.2 °C cm/W ~(converts Kevin Unit According to SSP E- 210 Cable and 1.2Km/W) wire, item 3.2.2-Cable rating) c) Group de-rating According to Manufacture’s IEC 60087 or recommendations (which ever method gives the lowest result) d) temperatures for different In the air :30°C applications In the soil: 30°C Reference Documents - EPC Contract Technical Specification (Part VII) - POWER CABLE LIST (F4281S-D1114) - Short-Circuit Analysis Report (F4281S-D0101-203) - Documents for Relevant Load List (F4281S-D0310-201,202,203) - Technical specification for power cables(DH1-DE-A3-TD-E-0094) Cable Sizing Criteria  IEC60364-5-52Electrical_installations_of_buildings_– DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study Part_5-52Selection_and_erection_of_electrical_equipment_– Wiring_systems  IEC 60502 Power cables with extruded insulation and their accessories for rated voltages from kV up to 30 kV  IEC 60909-0 Short-circuit currents in there-phase a.c systems – calculation of currents  IEC 60909-1 Short-circuit currents in there-phase a.c systems – Factors for the calculation  IEC 60909-2 Electrical equipments – Data for Short-circuit current calculations  IEC 60909-3 Short-circuit currents in there-phase a.c systems – currents during two separate  EC 60909-4 Short-circuit currents in there-phase a.c systems – Examples for the calculation of short-circuit currents  IEC 60332-3-23 Tests on electrical cables under fire conditions - part 324 Test for vertical flame spread of vertically  Manual of power cable Cable is sized to fulfill the criteria of both current-carrying capacity and voltage drop Cable Installation Method The following method or their combinations is generally used to install cables:  On multi-level cable trays/cable ladder which are inside trenches  In conduit  In free air, on trays, brackets, ladders, etc  In cable ducts which are underground  Underground installation: All cables shall be run in PVC pipes encased concrete duck bank DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study  Above ground installation: All cables shall be run in Cable tray/Cable ladder/Conduits made of hot dipped galvanized steel with cover Covers will be provided wherever mechanical protection is required According to the cable tray/Cable ladder/Conduit routing Drawings All calculation for specific cables are based on the installation method that has the most stringent cable sizing requirements in its cable route Voltage Drop 5.1 Voltage Drop Of Normal Operation State The voltage drop is calculated in percentage of the rated nominal voltage The Calculation checks whether the voltage drop is within the required voltage drop tolerance, namely 3% of rated nominal voltage Voltage drop is defined by: ∆U(V) = √3 × I × L(R cos ∅ + X sin ∅) Where:  R and X (_/km) are the resistance and reactance of a cable per kilometer; R apply for the cable resistance of 90℃ The converting process for resistance from 20℃ to 90℃ is as following: ρ: Cable resistance for meter mm2 cable (Ω) ρ = ρ0 (1 + α(θcore − 20) ρ0 : cable resistance for meter mm2 cable (Ω) at 20℃ ρ0 =0.01851 for copper α: Temperature factor; α = 0.00393, for copper θcore : Conductor maximum temperature in rated conditions (℃) In this study, θcore = 90℃ will be used  Ur is the nominal voltage of the distribution board The default value is 230V for single phase and 400V for three –phase circuit  n is the number of conductors in parallel per phase; DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study  L (km) is the length of the conductor;  U x is the voltage drop values by phase system, cross section and formation of the cable according to the most common Cos  0.85 value used for this calculation According to above equation, if the result calculated by I,b' satisfies the specification, the result calculated by I b is also satisfaction 5.2 Voltage Drop Of Starting Motor State The voltage drop is calculated in percentage of the rated nominal voltage The Calculation checks whether the voltage drop is within the required voltage drop tolerance, namely 5% of rated nominal voltage Voltage drop is defined by: ∆U(V) = √3 × I × n × L(R cos ∅ + X sin ∅) Where: R and X (_/km) are the resistance and reactance of a cable per kilometer; R apply for the cable resistance of 90℃ “n” (Starting Current/Normal Current ) and cos ∅ (Starting Power Factor ) is chosen according to the following table Motor Rating >25kW <25kW Starting Current/Normal Current 6 Starting Power Factor 0.4 0.3 Current Carrying Capacity The current-carrying capacity of cable is according to the following manufacturer data of document F4281-GEDI-P-ZP-0076-0 Specification document of Jiangsu Jiangyang Cable Co., Ltd which is issued in letter No DH1-DE-A3-E-13-5338 DH!-DE-A3-TD-E-0084 Technical Specification of Power Cables which is issued in letter No DH1-DE-A3-E-13-0189 DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study  k is a coefficient equal to: -2 for single phase two wires system; -√3 for three phase four wires system;  I b' (A) is the current drawn by the connected load considered to correction factors  For cable installed in cable tray Ib′ = k1 ∗ k ∗ k ∗ ICable Capacity k1: is the correction factor refer to IEC 60502-2 TABLE B10 k2: is the correction factor for adjacent cables, refer to Chinese Standard GB50217-2007 Table D.0.6, k3:  is the Assymetrical Factor For cable installed in conduct under ground Ib′ = k ∗ k ∗ k ∗ k ∗ k ∗ ICable Capacity k4: is the correction factor refer to IEC 60502-2, P64 TABLE B10 k5: is the correction factor refer to IEC 60502-2, P65 TABLE B13 k6: is the correction factor refer to IEC 60502-2, TABLE B.17 k7 is the correction factor refer to Chinese Standard GB50217-2007 Table D.0.6, I b is the current drawn by the connected load without consideration to correction factors Short Circuit Calculation The short circuit capacity of the cables are calculated based on the following: I = kxS/√𝐭 where t = Permissible break time after fault in seconds DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study S = Conductor cross section in mm2 I = Current on dead short circuit in A K = Constant.143 for XLPE- insulated copper wire DUYEN HAI THERMAL POWER PROJECT Cable Sizing and Cable Voltage Drop Study ATTACHMENT Table of Cable Sizing Calculation DUYEN HAI THERMAL POWER PLANT PROJECT Cable Sizing From(Source point) NO To(Destination point) Description Location Description Location Input Power(kW) Power factor (Rated) Installed current carrying Capacity Correction factor Load Information KKS Identity of Cable Installed current/load current Power factor (Starting) Ur(V) Ib (A) Starting Current/Normal Current Type of Installation K1 K2 K3 K4 K5 K6 K7 K Ib'(A) (%) Voltage (kV) Cable Construction Size of cable (mm2) Cable Capacity of 50 Degree (A) Cable Capacity of 30 Degree (A) L (km) n R(Ohm/km)at 20 Deg R(Ohm/km)at 90 Deg Minimum cable size S= Io√t/k (thermal stability) Cable Voltage Drop Steady state Cable Voltage Drop Motor Starting Busbar Voltage Drop Steady state Busbar Voltage Drop Motor Starting Total Voltage Drop Steady state Total Voltage Drop Motor Starting X(Ohm/km) ⊿Usc (%) ⊿Umc (%) ⊿Usb (%) ⊿Umb (%) ⊿Ust (%) ⊿Umt (%) (kArms) (second) (mm2) Cable Information Short circuit current Protection device Trip time ABLM5111 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM01A Heater of 400V A0BLL Swtich Cabinet A0BLL00 0.85 0.3 400 1.70 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 108.811 6407.833 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 165 201 0.45 4.61 5.878 0.0897 1.657 4.214 2.000 10.000 3.657 14.214 0.087 0.15 ABLM5121 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM01B Control box of Drain Pump A0ETP00GH001 15 0.85 0.3 400 25.47 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 165.697 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.062 1.83 2.333 0.0823 1.364 3.560 2.000 10.000 3.364 13.560 1.586 0.15 ABLM5131 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM01C Control box of Overhead Crane in the Air Compressor House A1UTF00GP401 In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X6 46 56 0.064 3.08 3.927 0.085 1.435 3.678 2.000 10.000 3.435 13.678 0.914 0.15 ABLM5132 Control box of Overhead Crane in the Air Compressor House A1UTF00GP401 Overhead Crane in the Air Compressor House Overhead Crane in the Air Compressor House In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X6 46 56 0.01 3.08 3.927 0.085 1.659 4.253 2.000 10.000 3.659 14.253 0.791 0.15 ABLM5141 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM01D Lighting Distribution Box in the Air Compressor House In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.027 1.83 2.333 0.0823 0.594 1.550 2.000 10.000 2.594 11.550 3.629 0.15 10 ABLM5231 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM02C Control box of #1 No Heat Regenerative Dryer In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.082 4.61 5.878 0.0897 0.091 0.230 2.000 10.000 2.091 10.230 0.477 0.15 ABLM5241 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM02D Control box of #1 Dryer A0ETP10AT011 10.11 0.85 0.3 In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.022 1.83 2.333 0.0823 0.326 0.851 2.000 10.000 2.326 10.851 4.446 0.15 10 ABLM5251 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM02E Control box of #2 Dryer A0ETP10AT021 10.11 0.85 0.3 400 17.17 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 245.842 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.024 1.83 2.333 0.0823 0.356 0.929 2.000 10.000 2.356 10.929 4.079 0.15 10 ABLM5261 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM02F Control box of #3 Dryer A0ETP10AT031 10.11 0.85 0.3 400 17.17 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 245.842 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.029 1.83 2.333 0.0823 0.430 1.122 2.000 10.000 2.430 11.122 3.381 0.15 10 ABLM5271 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM02G Control box of #4 Dryer A0ETP10AT041 10.11 0.85 0.3 400 17.17 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 245.842 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.035 1.83 2.333 0.0823 0.519 1.354 2.000 10.000 2.519 11.354 2.804 0.15 11 ABLM5281 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM02H Heater of 400V A0BLZ Swtich Cabinet A0BLZ00 0.85 0.3 400 1.70 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 1398.073 0.6/1kV Cu/XLPE NH-YJV22-0.6/14X4 36 44 0.384 4.61 5.878 0.0897 1.414 3.596 2.000 10.000 3.414 13.596 0.102 0.15 A0QFA32AT001 0.3 0.85 0.3 400 0.51 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 4660.242 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.087 4.61 5.878 0.0897 0.096 0.244 2.000 10.000 2.096 10.244 0.450 0.15 A1UTF00GP001 A0QFA31AT001 9.1 9.1 15 0.3 0.85 0.85 0.85 0.85 0.3 0.3 0.3 0.3 400 400 400 400 400 15.45 15.45 25.47 0.51 17.17 / / / / / / / / / / 1 1 0.91 0.91 0.91 0.91 0.91 0.99 0.99 0.99 0.99 0.99 1 1 0.6 0.6 0.6 0.6 0.6 0.541 0.541 0.541 0.541 0.541 30.335 30.335 42.205 23.741 42.205 196.311 196.311 165.697 4660.242 245.842 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV 12 ABLM5331 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM03C Control box of #2 No Heat Regenerative Dryer 13 ABLM5341 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM03D Maintenance Box in the Air Compressor House A1UTF00GP301 30 0.85 0.4 400 50.94 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 89.027 174.759 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X35 135 165 0.064 0.524 0.668 0.0780 0.817 2.990 2.000 10.000 2.817 12.990 5.248 0.15 14 14 ABLM5351 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM03E Control box of #5 Dryer A0ETP10AT051 10.11 0.85 0.3 400 17.17 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 245.842 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.05 1.83 2.333 0.0823 0.741 1.935 2.000 10.000 2.741 11.935 1.966 0.15 Ventilating Distribution Box in the Air Compressor House A1UTF00GP201 15 0.85 0.3 400 25.47 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 165.697 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.027 1.83 2.333 0.0823 0.594 1.550 2.000 10.000 2.594 11.550 3.629 0.15 10 A0ETP10AT101 10.11 0.85 0.3 400 17.17 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 245.842 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.076 1.83 2.333 0.0823 1.127 2.941 2.000 10.000 3.127 12.941 1.295 0.15 In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.076 4.61 5.878 0.0897 0.084 0.214 2.000 10.000 2.084 10.214 0.515 0.15 In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.044 1.83 2.333 0.0823 0.652 1.703 2.000 10.000 2.652 11.703 2.233 0.15 6 In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.049 1.83 2.333 0.0823 0.727 1.896 2.000 10.000 2.727 11.896 2.006 0.15 In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.055 1.83 2.333 0.0823 0.816 2.128 2.000 10.000 2.816 12.128 1.788 0.15 In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.081 1.83 2.333 0.0823 1.201 3.134 2.000 10.000 3.201 13.134 1.215 0.15 15 ABLM5361 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM03F 16 ABLM5371 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM03G Control box of #10 Dryer ABLM5431 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM04C Control box of #3 No Heat Regenerative Dryer ABLM5441 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM04D Control box of #6 Dryer ABLM5451 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM04E Control box of #7 Dryer ABLM5461 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM04F Control box of #8 Dryer ABLM5471 AIR COMPRESSING HOUSE MCC A0BLM00 A0BLM04G Control box of #9 Dryer 17 18 19 20 21 A0QFA33AT001 A0ETP10AT061 A0ETP10AT071 A0ETP10AT081 A0ETP10AT091 0.3 10.11 10.11 10.11 10.11 0.85 0.85 0.85 0.85 0.85 0.3 0.3 0.3 0.3 0.3 400 400 400 400 400 0.51 17.17 17.17 17.17 17.17 / / / / / / / / / / 1 1 0.91 0.91 0.91 0.91 0.91 0.99 0.99 0.99 0.99 0.99 1 1 0.6 0.6 0.6 0.6 0.6 0.541 0.541 0.541 0.541 0.541 23.741 42.205 42.205 42.205 42.205 4660.242 245.842 245.842 245.842 245.842 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV 22 ABLL5121 WASHING PUMP HOUSE MCC A0BLL00 A0BLL01B Control box #1 Mixer、 #2 Mixer、#1 Aid Dosing Pump、#2 Aid Dosing Pump A0ETN50GH001 19.4 0.85 0.3 400 32.94 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 54.735 166.151 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X16 83 101 0.013 1.15 1.466 0.0789 0.233 0.623 2.000 10.000 2.233 10.623 11.569 0.15 15 23 ABLL5131 WASHING PUMP HOUSE MCC A0BLL00 A0BLL01C Control box of Electric Crane in the Washing Pump House A0UTF00GP401 8.3 0.85 0.3 400 14.09 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 168.442 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.015 4.61 5.878 0.0897 0.459 1.166 2.000 10.000 2.459 11.166 2.603 0.15 24 ABLL5132 Control box of Electric Crane in the Washing Pump House A0UTF00GP401 Electric Crane in the Washing Pump House Electric Crane in the Washing Pump House 8.3 0.85 0.3 400 14.09 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 168.442 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.01 4.61 5.878 0.0897 0.764 1.943 2.000 10.000 2.764 11.943 1.563 0.15 25 ABLL5141 WASHING PUMP HOUSE MCC A0BLL00 A0BLL01D Lighting Distribution Box in the Washing Pump House A0UEV00GP001 0.85 0.3 400 8.49 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 279.615 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.024 4.61 5.878 0.0897 0.442 1.124 2.000 10.000 2.442 11.124 1.628 0.15 26 ABLL5211 WASHING PUMP HOUSE MCC A0BLL00 A0BLL02A Control box of #1 Metering Pump Control box of #1 Metering Pump 1.1 0.85 0.3 400 1.87 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 1270.975 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.067 4.61 5.878 0.0897 0.271 0.690 2.000 10.000 2.271 10.690 0.584 0.15 27 ABLL5212 Control box of #1 Metering Pump Control box of #1 Metering Pump #1 Metering Pump #1 Metering Pump 0.55 0.85 0.3 400 0.93 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 2541.950 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.015 4.61 5.878 0.0897 0.166 0.422 2.000 10.000 2.166 10.422 0.477 0.15 28 ABLL5213 Control box of #1 Metering Pump Control box of #1 Metering Pump #2 Metering Pump #2 Metering Pump 0.55 0.85 0.3 400 0.93 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 2541.950 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.015 4.61 5.878 0.0897 0.166 0.422 2.000 10.000 2.166 10.422 0.477 0.15 A0BLL02B Control box of #1 Sealing Water Pump Sealing Water Pump A0ETN20GH001 30 0.85 0.4 400 50.94 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 72.540 142.396 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X25 110 134 0.022 0.727 0.927 0.0801 0.388 1.385 2.000 10.000 2.388 11.385 10.763 0.15 13 A0BLL02C Control box of #1 Drain Pump for Washing Pump House AOETN10GH004 15 0.85 0.3 400 25.47 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 165.697 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.013 1.83 2.333 0.0823 0.286 0.746 2.000 10.000 2.286 10.746 7.452 0.15 10 A0BLL02D Control box of #1、#2 、#3 Drain Pump for Sedimentation Tank AOETN10GH006 22.5 0.85 0.3 400 38.21 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 72.540 189.862 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X25 110 134 0.106 0.727 0.927 0.0801 1.401 3.894 2.000 10.000 3.401 13.894 2.320 0.15 A0BLL02E Maintenance Box in the Washing Pump House In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X35 135 165 0.019 0.524 0.668 0.078 0.243 0.888 2.000 10.000 2.243 10.888 16.330 0.15 32 A0BLL02F Ventilating Distribution Box in the Washing Pump House In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.024 1.83 2.333 0.0823 0.528 1.378 2.000 10.000 2.528 11.378 4.079 0.15 A0BLL02G Heater of 400V A0BLM Swtich Cabinet In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.45 4.61 5.878 0.0897 1.657 4.214 2.000 10.000 3.657 14.214 0.087 0.15 A0BLZ01B Motor of Sewage pump in the Daily Oli Area In cable tray and Conduit Cu/XLPE NH-YJV22-0.6/14X4 36 44 0.02 4.61 5.878 0.0897 0.552 1.405 2.000 10.000 2.552 11.405 1.953 0.15 A0BLZ01C Control box of Lifting Device for Daily Fuel Oil House A3UEJ00GP401 9.1 0.85 0.3 In cable tray and Conduit Cu/XLPE NH-YJV22-0.6/14X10 64 78 0.006 1.83 2.333 0.0823 0.080 0.209 2.000 10.000 2.080 10.209 15.431 0.15 10 Lifting Device for Daily Fuel Oil House Lifting Device for Daily Fuel Oil House 9.1 0.85 0.3 In cable tray and Conduit Cu/XLPE NH-YJV22-0.6/14X10 64 78 0.013 1.83 2.333 0.0823 0.254 0.662 2.000 10.000 2.254 10.662 5.138 0.15 29 30 31 32 33 34 35 36 37 ABLL5221 ABLL5231 WASHING PUMP HOUSE MCC A0BLL00 WASHING PUMP HOUSE MCC A0BLL00 ABLL5241 WASHING PUMP HOUSE MCC A0BLL00 ABLL5251 WASHING PUMP HOUSE MCC A0BLL00 ABLL5261 WASHING PUMP HOUSE MCC A0BLL00 ABLL5271 WASHING PUMP HOUSE MCC A0BLL00 ABLZ5121 ABLZ5131 ABLZ5132 A0BLZ01B A0BLZ01C Control box of Lifting Control box of Lifting Device for Daily Fuel Device for Daily Fuel Oil House Oil House A0UEV00GP301 A0UEV00GP201 A0BLM00 A0EGR80AP001 30 15 7.5 0.85 0.85 0.85 0.85 0.4 0.3 0.3 0.3 400 400 400 400 400 400 50.94 25.47 1.70 12.74 15.45 15.45 / / / / / / / / / / / / 1 1 1 0.91 0.91 0.91 0.91 0.91 0.91 0.99 0.99 0.99 0.99 0.99 0.99 1 1 1 0.6 0.6 0.6 0.6 0.6 0.6 0.541 0.541 0.541 0.541 0.541 0.541 89.027 42.205 23.741 23.741 42.205 42.205 174.759 165.697 1398.073 186.410 273.128 273.128 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV DUYEN HAI THERMAL POWER PLANT PROJECT Cable Sizing From(Source point) NO Description 38 39 40 41 42 43 44 To(Destination point) Load Information ABLZ5141 ABLZ5151 ABLZ5221 ABLZ5231 ABLZ5241 ABLZ5251 ABLZ5261 A0BLZ01D A0BLZ01E A0BLZ02B A0BLZ02C A0BLZ02D A0BLZ02E A0BLZ02F Ib (A) Starting Current/Normal Current Type of Installation K1 K2 K3 K4 K5 K6 K7 K Ib'(A) (%) Voltage (kV) 0.85 0.3 400 8.49 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 279.615 0.6/1kV Cu/XLPE 0.85 0.3 400 25.47 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 165.697 0.6/1kV In cable tray and Conduit In cable tray and Conduit In cable tray and Conduit In cable tray and Conduit In cable tray and Conduit Location Input Power(kW) A0BLZ01D Lighting Distribution Box for Daily Fuel Oil House A3UEJ00GP001 A0BLZ01E Ventilating Distribution Box for Daily Fuel Oil House A3UEJ00GP201 15 A0BLZ02B #1 Turbine Motor of Circulating Pump A0BLZ02C #2 Turbine Motor of Circulating Pump A0BLZ02D #3 Turbine Motor of Circulating Pump A0BLZ02E #1 Fan for Mechanical Draft Cooling Tower A0BLZ02F #2 Fan for Mechanical Draft Cooling Tower A0PTA12AN001 11 0.85 0.3 0.85 0.3 A0PCC12AP001 A0PCC13AP001 A0PTA11AN001 22 22 11 Power factor (Rated) 0.85 0.85 0.85 0.85 0.3 0.3 0.3 0.3 400 400 400 400 400 37.36 37.36 37.36 18.68 18.68 / / / / / / / / / / 1 1 0.91 0.91 0.91 0.91 0.91 0.99 0.99 0.99 0.99 0.99 1 1 0.6 0.6 0.6 0.6 0.6 0.541 0.541 0.541 0.541 0.541 72.540 72.540 72.540 42.205 42.205 194.177 194.177 194.177 225.951 225.951 Cable Construction 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV 0.6/1kV Size of cable (mm2) Cable Capacity of 50 Degree (A) Cable Capacity of 30 Degree (A) L (km) n R(Ohm/km)at 20 Deg R(Ohm/km)at 90 Deg Minimum cable size S= Io√t/k (thermal stability) Cable Voltage Drop Steady state Cable Voltage Drop Motor Starting Busbar Voltage Drop Steady state Busbar Voltage Drop Motor Starting Total Voltage Drop Steady state Total Voltage Drop Motor Starting X(Ohm/km) ⊿Usc (%) ⊿Umc (%) ⊿Usb (%) ⊿Umb (%) ⊿Ust (%) ⊿Umt (%) (kArms) (second) (mm2) Cable Information Ur(V) Description 22 Installed current/load current Power factor (Starting) Location A0PCC11AP001 Installed current carrying Capacity Correction factor KKS Identity of Cable Short circuit current Protection device Trip time NH-YJV22-0.6/14X4 36 44 0.008 4.61 5.878 0.0897 0.147 0.375 2.000 10.000 2.147 10.375 4.860 0.15 Cu/XLPE NH-YJV22-0.6/14X10 64 78 0.008 1.83 2.333 0.0823 0.176 0.459 2.000 10.000 2.176 10.459 11.856 0.15 10 Cu/XLPE NH-YJV22-0.6/14X25 110 134 0.062 0.727 0.927 0.0801 0.801 2.227 2.000 10.000 2.801 12.227 3.947 0.15 11 Cu/XLPE NH-YJV22-0.6/14X25 110 134 0.064 0.727 0.927 0.0801 0.827 2.299 2.000 10.000 2.827 12.299 3.825 0.15 10 Cu/XLPE NH-YJV22-0.6/14X25 110 134 0.066 0.727 0.927 0.0801 0.853 2.370 2.000 10.000 2.853 12.370 3.711 0.15 10 Cu/XLPE NH-YJV22-0.6/14X10 64 78 0.05 1.83 2.333 0.0823 0.807 2.105 2.000 10.000 2.807 12.105 1.966 0.15 Cu/XLPE NH-YJV22-0.6/14X10 64 78 0.054 1.83 2.333 0.0823 0.871 2.274 2.000 10.000 2.871 12.274 1.821 0.15 45 ABLZ5271 A0BLZ02G A0BLZ02G #3 Fan for Mechanical Draft Cooling Tower A0PTA13AN001 11 400 18.68 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 225.951 0.6/1kV Cu/XLPE NH-YJV22-0.6/14X10 64 78 0.058 1.83 2.333 0.0823 0.936 2.442 2.000 10.000 2.936 12.442 1.695 0.15 46 ABLZ5281 A0BLZ02H A0BLZ02H Maintenance Box for Daily Fuel Oil House A3UEJ00GP301 30 0.85 0.4 400 50.94 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 89.027 174.759 0.6/1kV Cu/XLPE NH-YJV22-0.6/14X35 135 165 0.008 0.524 0.668 0.078 0.102 0.374 2.000 10.000 2.102 10.374 30.719 0.15 35 47 ABHC5211 400/230V ASH HANDLING PC I A0BHC02A #1 Flush Water Pump control box A0ETN10GH001 110 0.85 0.4 400 186.79 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 227.513 121.802 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X150+1X70 345 421 0.014 0.124 0.158 0.0279 0.157 0.599 2.000 10.000 2.157 10.599 41.995 0.15 114 48 ABHC5221 400/230V ASH HANDLING PC I A0BHC02B #2 Flush Water Pump control box A0ETN10GH002 110 0.85 0.4 400 186.79 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 227.513 121.802 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X150+1X70 345 421 0.012 0.124 0.158 0.0279 0.134 0.514 2.000 10.000 2.134 10.514 43.358 0.15 117 49 ABHC5311 400/230V ASH HANDLING PC I A0BHC03A Air Compressor Room MCC A0BLM00 120 0.85 0.4 400 203.77 In cable tray 0.91 0.6 / / / / 0.546 309.746 152.007 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X240+1X120 465 567 0.161 0.0754 0.096 0.0269 1.214 4.989 2.000 10.000 3.214 14.989 12.863 0.15 35 50 ABHC5321 400/230V ASH HANDLING PC I A0BHC03B Flush Water Pump House MCC A0BLL00 81 0.85 0.4 400 137.55 In cable tray 0.91 0.6 / / / / 0.546 203.167 147.709 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X120+1X70 305 372 0.02 0.153 0.195 0.0274 0.202 0.753 2.000 10.000 2.202 10.753 35.523 0.15 96 51 ABHC5331 400/230V ASH HANDLING PC I A0BHC03C Auxilliary Boiler House MCC Auxilliary Boiler House MCC 116.67 0.85 0.4 400 198.12 In cable tray 0.91 0.6 0.97 / / / / 0.530 222.917 112.518 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X150+1X70 345 421 0.11 0.124 0.158 0.0279 1.305 4.993 2.000 10.000 3.305 14.993 12.095 0.15 33 52 ABHC5332 400/230V ASH HANDLING PC I A0BHC03C Auxilliary Boiler House MCC Auxilliary Boiler House MCC 116.67 0.85 0.4 400 198.12 In cable tray 0.91 0.6 0.97 / / / / 0.530 222.917 112.518 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X150+1X70 345 421 0.11 0.124 0.158 0.0279 1.305 4.993 2.000 10.000 3.305 14.993 12.095 0.15 33 53 ABHC5333 400/230V ASH HANDLING PC I A0BHC03C Auxilliary Boiler House MCC Auxilliary Boiler House MCC 116.67 0.85 0.4 400 198.12 In cable tray 0.91 0.6 0.97 / / / / 0.530 222.917 112.518 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X150+1X70 345 421 0.11 0.124 0.158 0.0279 1.305 4.993 2.000 10.000 3.305 14.993 12.095 0.15 33 ABHC5411 400/230V ASH HANDLING PC I A0BHC04A Heater of 400/230V A0BHD In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.03 4.61 5.878 0.0897 0.110 0.281 2.000 10.000 2.110 10.281 1.303 0.15 ABHC5421 400/230V ASH HANDLING PC I A0BHC04B Daily Oil Area Thermal Distribution Cabinet Daily Oil Area Thermal Distribution Cabinet In cable tray and Conduit Cu/XLPE NH-YJV22-0.6/14X50 165 201 0.394 0.387 0.493 0.0313 1.842 4.978 2.000 10.000 3.842 14.978 1.179 0.15 ABHC5441 400/230V ASH HANDLING PC I A0BHC04D Auxilliary Boiler House Control System Auxilliary Boiler House Control System In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.129 1.83 2.333 0.0823 1.892 4.938 2.000 10.000 3.892 14.938 0.763 0.15 ABHC5451 400/230V ASH HANDLING PC I A0BHC04E Slag Handling Control System Slag Handling Control System 0.85 0.3 400 8.49 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 30.335 357.285 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X6 46 56 0.028 3.08 3.927 0.085 0.345 0.884 2.000 10.000 2.345 10.884 2.087 0.15 Slag Handling System Slag Handling System Flush Water Pump House Flush Water Pump House Thermal Distribution Thermal Distribution Cabinet Cabinet 10 0.85 0.3 400 16.98 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 248.546 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.028 1.83 2.333 0.0823 0.411 1.072 2.000 10.000 2.411 11.072 3.501 0.15 25 0.85 0.3 400 42.45 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 171.459 403.888 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X95+1X50 260 317 0.443 0.193 0.246 0.0284 1.735 4.986 2.000 10.000 3.735 14.986 2.084 0.15 54 55 56 57 A0BHD00 15 10 0.85 0.85 0.85 0.3 0.3 0.3 400 400 400 1.70 25.47 16.98 / / / / / / 1 0.91 0.91 0.91 0.99 0.99 0.99 1 0.6 0.6 0.6 0.541 0.541 0.541 23.741 108.811 42.205 1398.073 427.189 248.546 0.6/1kV 0.6/1kV 0.6/1kV 58 ABHC5461 400/230V ASH HANDLING PC I A0BHC04F 59 ABHC5471 400/230V ASH HANDLING PC I A0BHC04G Air Compressor Room Thermal Distribution Cabinet 60 ABHC5481 400/230V ASH HANDLING PC I A0BHC04H Daily Oil Area MCC Daily Oil Area MCC 94.8 0.85 0.4 400 160.98 In cable tray 0.91 0.6 / / / / 0.546 309.746 192.414 0.6/1kV Cu/XLPE NH-YJV22-0.6/13X240+1X120 465 567 0.204 0.0754 0.096 0.0269 1.215 4.994 2.000 10.000 3.215 14.994 10.424 0.15 28 61 ABHD5211 400/230V ASH HANDLING PC I I A0BHD02A #3 Flush Water Pump control box A0ETN10GH003 110 0.85 0.4 400 186.79 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 227.513 121.802 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X150+1X70 345 421 0.021 0.124 0.158 0.0279 0.235 0.899 2.000 10.000 2.235 10.899 37.255 0.15 101 62 ABHD5311 400/230V ASH HANDLING PC I I A0BHD03A Air Compressor Room MCC A0BLM00 120 0.85 0.4 400 203.77 In cable tray 0.91 0.6 / / / / 0.546 309.746 152.007 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X240+1X120 465 567 0.161 0.0754 0.096 0.0269 1.214 4.989 2.000 10.000 3.214 14.989 12.863 0.15 35 63 ABHD5321 400/230V ASH HANDLING PC I I A0BHD03B Flush Water Pump House MCC A0BLL00 81 0.85 0.4 400 137.55 In cable tray 0.91 0.6 / / / / 0.546 203.167 147.709 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X120+1X70 305 372 0.021 0.153 0.195 0.0274 0.212 0.791 2.000 10.000 2.212 10.791 34.766 0.15 94 64 ABHD5411 400/230V ASH HANDLING PC I I A0BHD04A Heater of 400/230V A0BHC A0BHC00 0.85 0.3 400 1.70 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 23.741 1398.073 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X4 36 44 0.03 4.61 5.878 0.0897 0.110 0.281 2.000 10.000 2.110 10.281 1.303 0.15 ABHD5421 400/230V ASH HANDLING PC I I A0BHD04B Daily Oil Area Thermal Distribution Cabinet Daily Oil Area Thermal Distribution Cabinet In cable tray and Conduit Cu/XLPE NH-YJV22-0.6/14X50 165 201 0.39 0.387 0.493 0.0313 1.823 4.927 2.000 10.000 3.823 14.927 1.191 0.15 ABHD5441 400/230V ASH HANDLING PC I I A0BHD04D Auxilliary Boiler House Control System Auxilliary Boiler House Control System In cable tray and Conduit Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.13 1.83 2.333 0.0823 1.907 4.976 2.000 10.000 3.907 14.976 0.757 0.15 65 66 A0CDQ01 15 10 0.85 0.85 0.3 0.3 400 400 25.47 16.98 / / / / 1 0.91 0.91 0.99 0.99 1 0.6 0.6 0.541 0.541 108.811 42.205 427.189 248.546 0.6/1kV 0.6/1kV Cu/XLPE 68 ABHD5461 400/230V ASH HANDLING PC I I A0BHD04F 69 ABHD5471 400/230V ASH HANDLING PC I I A0BHD04G ABHD5481 400/230V ASH HANDLING PC I I 70 A0BHD04H Slag Handling System Slag Handling System Flush Water Pump House Flush Water Pump House Thermal Distribution Thermal Distribution Cabinet Cabinet Air Compressor Room Thermal Distribution Cabinet Daily Oil Area MCC A0CDQ01 Daily Oil Area MCC 10 0.85 0.3 400 16.98 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 42.205 248.546 0.6/1kV Cu/XLPE ZR-YJV22-0.6/14X10 64 78 0.022 1.83 2.333 0.0823 0.323 0.842 2.000 10.000 2.323 10.842 4.446 0.15 25 0.85 0.3 400 42.45 In cable tray and Conduit / / 0.91 0.99 0.6 0.541 171.459 403.888 0.6/1kV Cu/XLPE ZR-YJV22-0.6/13X95+1X50 260 317 0.441 0.193 0.246 0.0284 1.728 4.964 2.000 10.000 3.728 14.964 2.093 0.15 Cu/XLPE NH-YJV22-0.6/13X240+1X120 465 567 0.203 0.0754 0.096 0.0269 1.209 4.970 2.000 10.000 3.209 14.970 10.471 0.15 28 94.8 0.85 0.4 400 160.98 In cable tray 0.91 0.6 / / / / 0.546 309.746 192.414 0.6/1kV

Ngày đăng: 28/10/2019, 16:54

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN