EDCS-8000 Series of Power System Integrated Automatic Device EDCS-8150 STATION TRANSFORMER PROTECTION AND MONITORING DEVICE INSTRUCTIONMANUAL V2.30 Chongqing New Century Electrical Co., Ltd VERSION ANNOUNCEMENT Copyright: Chongqing New Century Electrical Co., Ltd This instruction is applicable to the protection program of the following version: EDCS-81502 Station transformer protection and monitoring device V2.** EDCS-81503 Station transformer protection and monitoring device V2.** UPDATING RECORD OF INSTRUCTION’S VERSION NO Instruction Version Updating abstract Updating date 10 The instruction and production may have a little change, please check the practical production and the instruction’s version Technical support: Tel:(023)68694458 The second version prints in 10, 2010 More information please access http://www.cqnec.com.cn HU Fax:(023)68626689 U IMPORTANT INSTRUCT Thank you for purchased production made by Chongqing New Century Electrical Co., Ltd For safe, correct and effective usage of these devices, please read the important information below Please read the instruction carefully, and adjust, test or manipulate under the instruction’s prescript To protect the device, not insert or withdraw the module, touch Chip and element when the power on Please use dependable, high accuracy test instrument and equipment for test and measure to device Accident analysis need to original records, the device version information, and field fault process description If there is any abnormal or need repaired, please make contact with us CONTENTS PART ONE TECHNICAL INSTRUCTION 1 SUMMARIZE 1.1 APPLICATION 1.2 CHARACTERISTIC 1.3 FUNCTION DEPLOYMENT TECHNICAL PARAMETERS 2.1 ENVIROMENTAL PARAMETER 2.2 RATED PARAMETERS 2.3 PERFORMANCE INDEX 2.4 COMMUNICATION INTERFACE 2.5 INSULATION PERFORMACE 2.6 ELECTROMAGNETIC COMPATIBILITY CHARACTERISTICS 2.7 MECHANICAL PROPERTIES EDCS-81502 STATION TRANSFORMER PROTECTION AND MONITORING DEVICE 3.1 FUNCTION PRINCIPLE 3.2 DEVICE SETTING 17 3.3 DEVICE HARDWARE 27 EDCS-81503 STATION TRANSFORMER PROTECTION AND MONITORING DEVICE 42 4.1 FUNCTION PRINCIPLE 42 4.2 DEVICE SETTING 73 4.3 DEVICE HARDWARE 739 PART TWO INSTRUCTION FOR USE 85 OPERATION INSTRUCTION 85 1.1 THE KEYS 85 1.2 THE MENU 85 DEVICE OPERATIONS 90 2.1 NORMAL OPERATIONAL MODE STATUS 90 2.2 ABNORMAL INFORMATION PROCESSING 91 INSTALLATION INSTRUCTIONS 93 3.1 BOX OPENING CHECK 93 3.2 INSTALLATION NOTICE 93 CIRCUIT DEBUG SYLLABUS 94 4.1 TEST NOTICE 94 4.2 ACCIDENT ANALYSIS NOTICE 94 4.3 AC LOOP CHECK 95 4.4 INPUT CONTACT CHECK 95 I 4.5 OUTPUT CONTACT CHECK 95 4.6 DEVICE UNIT TEST 95 PRINT ACTION REPORT 995 TRANSPORTATION AND STORAGE 995 APPENDIX 100 7.1 CHASSIS STRUCTURE 100 7.2 COMMUNICATION CONNECTION 102 7.3 DEVICE CONFIGURATION TABLE AND ORDERING INSTRUCTION 105 7.4 PROTECTION VALUE SETTING FORM 106 II NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual PART ONE TECHNICAL INSTRUCTION SUMMARIZE 0B 1.1 APPLICATION 10B EDCS-8150 Station Transformer Protection and Monitoring System, which is used for3~ 35kV voltage class low current earthed system or low resistance earthed station transformer or earthed transformer protection and control system series, can be installed by screen, also by local at switch cabinet 1.2 CHARACTERISTIC 1B 1) Powerful function, hardware platform, versatility 2) Full configuration design, powerful programmable function 3) Advanced technology, patented de vice structure 4) Run stably and reliably, high anti-interference ability 5) Friendly interface, event recorded fully, operate safely 6) Convenient and flexible communication network way 1.3 FUNCTION DEPLOYMENT 12B TYPE NAME IEEE code 50,67,27,59,47 50,67,27,59,47 50,67,27,59,47 51 50N1T 50N2T 50N3T 46T1 46T2 Protection function Over-current Ⅰ stage protection Over-current II stage protection Over-current III stage protection Inverse time limit over-current protection Zero-sequence over-current Ⅰ stage protection Zero-sequence over-current II stage protection Zero-sequence over-current III stage protection negative-sequen ce over-current Ⅰ stage protection negative-sequen ce over-current II stage protection EDCS-81502 EDCS-81503 Station Transformer Protection and Control System Station Transformer Protection and Control System √ √ √ √ √ √ √ √ √ NEW CENTURY RELAYS Positive-sequen ce inverse time limit protection Low-voltage 27 protection Zero-sequence 59N over voltage protection Non-electrical 50T quantity protection 51 Overload alarm Backup 79R auto-switch-in Residual current 67N earthed-line selection Measure and control function 51 EDCS-8150 Station transformer protection & monitoring device instructionmanual √ √ √ √ √ √ √ √ √ Self-diagnosis √ √ Control circuit disconnection monitor √ √ Fault wave recorded √ Event recorded √ √ Remote and local operation √ √ Telemetering, telecommunication √ √ Remote control √ √ Independent operational circuit √ √ Binary input(standard/expanded) 9/19 9/19 Binary output(standard/expanded) 5/12 5/12 Hardware configuration Communication interface Chassis structure Voltage transformer connection mode CAN(485)/Ethernet CAN(485)/Ethernet 5U 19"/3 or 6U 19"/3 6U 19"/3 YY YY NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual TECHNICAL PARAMETERS 1B 2.1 ENVIROMENTAL PARAMETER 13B Operation Temperature: 0~40℃ Limited Temperature: -10~55℃ Storage and Transport: -25~70℃ 2.2 RATED PARAMETERS 14B DC power: 220V or 110V (please indicate when ordering); Allowable deviation: -20%~+20%; AC voltage: 100 / V (Rated phase voltage Un); AC current: 5A or 1A (Rated phase current In, please indicate when ordering); Rated frequency: 50Hz Overload capacity: Current loop: times of rated current, continuous working 10 times of rated current, Allow 10 seconds 40 times of rated current, Allow second Voltage loop: 1.5 times of rated voltage, continuous working Power dissipation: Current loop: Not more than 0.5 VA /Phase (when Rated value is 5A) Not more than 0.5 VA /Phase (when Rated value is 1A) Voltage loop: Not more than 0.5 VA /Phase (when Rated value is 100V) Not more than 0.5 VA /Phase (when Rated value is 100/ V) DC loop: Normal, not more than 10 W Trip, not more than 15 W 2.3 PERFORMANCE INDEX 15B 2.3.1 OVER-CURRENT PROTECTION 39B Current value range: 0.20In~10.00In (In TA 2nd rated current, the same below) Current value error: ≤±3% or ±0.03A Time value range: 0.00s~100.00s Time value error: ≤±1% or ±35ms 2.3.2 ZERO-SEQUENCE OVER-CURRENT PROTECTION 40B Current value range: 0.10A~100.00A Current value error: ≤±3% or ±0.03A NEW CENTURY RELAYS Time value range: 0.00s~100.00s Time value error: ≤±1% or ±35ms 2.3.3 NEGATIVE-SEQUENCE OVER-CURRENT PROTECTION 41B Current value range: 0.10A~100.00A Current value error: ≤±3% or ±0.03A Time value range: 0.00s~100.00s Time value error: ≤±1% or ±35ms 2.3.4 POSITIVE-SEQUENCE INVERSE TIME LIMIT PROTECTION 42B Reference value range: 0.10A~15.00A Reference value error: ≤±3% or ±0.03A Time constant value range: 0.00s~100.00s Time constant value error: ≤±1% or ±35ms 2.3.5 LOW VOLTAGE PROTECTION 43B Voltage value range: 2.00V~70.00V Voltage value error: ≤±3% or ±0.1V Time value range: 0.00s~100.00s Time value error: ≤±1% or ±35ms 2.3.6 ZERO-SEQUENCE OVER-VOLTAGE PROTECTION 4B Voltage value range: 2.00V~160.00V Voltage value error: ≤±3% or ±0.1V Time value range: 0.00s~100.00s Time value error: ≤±1% or ±35ms 2.3.7 NON ELECTRICITY PROTECTION 45B Time value range: 0.00s~100.00s Time value error: ≤±1% or ±35ms 2.3.8 EDCS-8150 Station transformer protection & monitoring device instructionmanual BACKUP AUTO-SWITCH-IN FUNCTION 46B With voltage value range: 50.00V~250.00V Losing voltage value range: 20.00V~250.00V Voltage value range: ≤±3% Time value range: ≤±1% or ±45ms NEW CENTURY RELAYS 10 11 12 13 14 15 16 17 18 19 EDCS-8150 Station transformer protection & monitoring device instructionmanual Zero-sequence over-current III stage action Zero-sequence over-current III stage alarm Positive-sequence over-currentⅠ stage act Positive-sequence over-current II stage action Positive-sequence inverse time limit action Low voltage action Zero-sequence voltage action Zero-sequence voltage alarm Non electrical action Non electrical alarm Non electrical action Non electrical alarm Non electrical action Non electrical alarm over over quantity quantity quantity quantity quantity quantity As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above As above 20 Auto-switch-in action As above As above 21 Overload alarm As above As above 22 Over voltage alarm As above As above 23 Low voltage alarm As above As above 88 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual INSTALLATION INSTRUCTIONS 3.1 BOX OPENING CHECK 1) Open the package, to check whether the device appearance is intact 2) inspects to ensure the certificate, supporting documents, attachments, spare parts and other requirements in line with the order as well as the type, name, number and so on described in packing list 3) If you have any questions, please contact with the factory in time 3.2 INSTALLATION NOTICE 3.2.1 1) INSTALLATION Protection screen (cabinet) must be reliable grounding, in which are equipped with ground copper, are required to submit the grounding net reliably 2) Devices should be firmly fixed on the screen (cabinet), and connected screws should be fastened 3) The grounding terminals of various devices and the earth of screen (cabinet) must be reliably connected to the grounding bus bar and system earth with the ground wire 4) Possibly, the device should be used shielded cable, ground the shielding layer in the switching field and the control room at the same time, and the phase current line and neutral line should be placed within the same cable 5) The current transformer secondary circuit only grounds in the protection cabinet 6) Wiring installations should comply with the requirements of wiring diagram 3.2.2 CONNECTION OF SHIELDING GROUND 86B ! The device is provided with "shielding ground" terminal which must be connected to earth A well-low-impedance grounding line is an effective guarantee that prevents the device from the interference of surge and transient pulse The switchgear panel connecting shaft cannot be as a grounding circuit, and the grounding resistance should be less than Ω or not Note: The bad shield grounding could lead to permanent damage to the device in operation, so it should not be put into use before affirming the device to be grounded reliably 89 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual CIRCUIT DEBUG SYLLABUS 4.1 TEST NOTICE 1) Before the test, please read of the debug syllabus and the manual 2) As little as possible draw device module, not touch the module circuit, does not draw module with power 3) the electric iron, screen cabinet and oscillograph must be grounded and reliable 4) Before the trial, Check the screen cabinet and installations there is an obvious injury or screw loosening n-service transit, particularly, the TA loop in screw and lace which does not allow the slightest relaxation 5) Check the procedure check code and the formation of the time 6) Before communication test, please check that device protocol set, communication address, communication rate, information version, soft version etc whether or not match background configuration set 7) After testing, please notice that clamp device plug-in board and plug, remove test wire and test brace and so on, recover device external connecting line, correctly set and check device value, control word, platen and so on parameter and configuration, to meet device safe running requirement 8) After testing with electrify, the device must be checked that whether running parameter and running state is conforming to the fact or not Ensure that device and system both are normal 4.2 ACCIDENT ANALYSIS NOTICE In order to go on accident analysis conveniently, specially suggest that user should save device action report Eliminate device report or frequently test to cover former fault information, go against that user and factory go on ex post analysis and responsibility confirm In order to save reliably former fault information, refer to the following method: 1) Before testing, the information of the device internal storage and background storage is saved wholly 2) The stored information includes device running report, device self-check report, device parameter and value and every operational record 3) Other scene information also should be recorded, includes fault process, protection device light state, main screen display content, if having damaged module, need to observe module state carefully when changing module(include peculiar smell, burned mark and so on) 4) Device local information connect printer to print if possible, the information of monitor background should be stored in order to prevent being covered 90 NEW CENTURY RELAYS 5) EDCS-8150 Station transformer protection & monitoring device instructionmanual If having special situation, please inform manufacturers to get and save fault information 4.3 AC LOOP CHECK 31B 1) Zero drift check In the terminal voltage loop within a short circuit and then disconnect the current loop enter into the "operating conditions" menu "sampling parameters" sub-menu to view voltage and current zero-drift value, the requirements, I≤0.01In, U ≤ 0.01Un 2) Sampling accuracy test Entered the "operating conditions" menu "sampling parameters" sub-menu and joined the rated current of protection screen terminals respectively, the sample should be equal with the actual value amount showed in the LCD screen, the deviation is less than ± % 4.4 INPUT CONTACT CHECK 32B Entered the "operating conditions" menu "sampling parameters" sub-menu and simulated the conduction of contact Screen in the protection screen respectively, the volume of state showed in the liquid crystal display should be changed, while a detailed report recorded the changing 4.5 OUTPUT CONTACT CHECK 3B Through the device interface of the "open test" command can also be carried out with the check value Should be made the breaker switch for a close and a tripping transmission tests and confirm the breaker action correctly Command mode: disconnect the connection with secondary circuit of external device control loop, enter "device test" menu "open test" sub-menu, operate the corresponding output, and use the multi-meter to check the situation connected to the relay contacts 4.6 DEVICE UNIT TEST 34B OVER-CURRENT Ⅰ STAGE PROTECTION 4.6.1 87B 1) Set “Over-currentⅠstage” soft platen as“1” 2) Input the current that is larger than over-current I stage protection value to every protection current channel; over-current I stage protection should act and send information by setting delay OVER-CURRENT Ⅱ STAGE PROTECTION 4.6.2 8B The same as over-currentⅠ stage protection 4.6.3 1) OVER-CURRENT III STAGE PROTECTION 89B When over-current protection is selected as fixed time-lag way, set “over-currentⅢ stage inverse time limit” control word as“0”, the same as 4.6.1 over-current Ⅰ stage protection 91 NEW CENTURY RELAYS 2) EDCS-8150 Station transformer protection & monitoring device instructionmanual When over-current protection is selected as inverse time limit way, set “over-currentⅢ stage inverse time limit” control word as “1”, the action delay should be same as the delay calculated according to inverse time limit character ZERO-SEQUENCE OVER-CURRENT Ⅰ STAGE PROTECTION 4.6.4 90B 1) Set “Zero-sequence over-current Ⅰ stage” soft platen as“1” 2) Input the current that is larger than zero-sequence I stage protection value to zero-sequence current channel, zero-sequence I stage protection should act and send information by setting delay 4.6.5 ZERO-SEQUENCE OVER-CURRENT II STAGE PROTECTION 91B The same as zero-sequence over-current Ⅰ stage protection 4.6.6 1) ZERO-SEQUENCE OVER-CURRENT III STAGE PROTECTION 92B When zero-sequence over-current III stage protection is selected as fixed time-lag way, set “zero-sequence Ⅲ stage inverse time limit” control word as“0”, the same as zero-sequence over-currentⅠ stage protection 2) When zero-sequence over-current III stage protection is selected as inverse time limit way, set “zero-sequence Ⅲ stage inverse time limit” control word as “1”, the action delay should be same as the delay calculated according to inverse time limit character NEGATIVE SEQUENCE OVER-CURRENT Ⅰ STAGE PROTECTION 4.6.7 93B 1) Set “Negative sequence over-currentⅠ stage” soft platen as “1” 2) Input the current to three phases protection current channel that makes that negative sequence current is larger than negative sequence I stage protection value, zero-sequence over-current I stage protection should act and send information by setting delay 4.6.8 NEGATIVE SEQUENCE OVER-CURRENT II STAGE PROTECTION 94B The same as 4.6.7 negative sequence over-currentⅠ stage protection 4.6.9 POSITIVE SEQUENCE INVERSE TIME LIMIT PROTECTION 95B 1) Set “Positive sequence inverse time limit protection” soft platen as “1” 2) Input the current to three phase protection current channel that makes that positive sequence current is larger than positive sequence inverse time limit protection value, the action delay should be same as the delay calculated according to inverse time limit character, positive sequence inverse time limit protection should act and send information by delay 92 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual 4.6.10 LOW VOLTAGE PROTECTION 96B 1) Set “Low voltage protection” soft platen as“1”; “TWJ” is “0”; “TV disconnection” is“0” 2) Input the voltage to three phases voltage channel that makes that line voltage is smaller than low voltage value, low voltage protection should act and send information by setting delay 4.6.11 ZERO-SEQUENCE OVERVOLTAGE PROTECTION 97B 1) Set “Zero-sequence overvoltage protection” soft platen as“1” 2) Input the voltage to three phases voltage channel that makes that zero-sequence voltage is larger than zero-sequence overvoltage protection value, zero-sequence overvoltage protection should act and send information by setting delay 4.6.12 NON ELECTRICITY PROTECTION 98B 1) Set “Non electricity” soft platen as “1” 2) Set “non electricity” input as “1”, non electricity protection should send information by setting delay 4.6.13 TV DISCONNECTION 9B 1) Set “TV disconnection detection” control word as“1” 2) Only add signal voltage 57.7V, should send information by 10s delay 4.6.14 OVERVOLTAGE ALARM 10B 1) Set “overvoltage alarm” soft platen as“1” 2) Input the voltage to 1# station A phase voltage channel that makes that A phase voltage is larger than overvoltage value, overvoltage protection should send alarm signal by setting delay 4.6.15 LOW VOLTAGE ALARM 10B 1) Set “low voltage alarm” soft platen as“1” 2) Add voltage to 1# station and 2# station three phases voltage to make them larger than low voltage value, then drop one phase to 0, low voltage protection should send alarm signal by setting delay 4.6.16 OVERLOAD ALARM 102B 1) Set “overload alarm” soft platen as“1” 2) Add current to 1# station A phase current to make it larger than overload value, overload protection should send alarm signal by setting delay 93 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual 4.6.17 BACKUP AUTO-SWITCH-IN 103B 3) Set “Backup auto-switch-in total on/off”, “Auto-switch-in way 1” control word as“1” 4) Set 1#TWJ and 2#TWJ as “0”, 1#KKJ and 2#KKJ as “1”, bus TWJ as “0” and KKJ as“0” Add three phases voltage to1# and 2# to make larger than with voltage value, then drop 1# voltage to 0, after device trips, immediately set 1#TWJ as 1, then device should act and send information by backup auto-switch-in action time 4.6.18 SWITCH TRANSMISSION TEST 104B Input “over-current I stage” soft platen, “over-current Ⅰ stage latching by repeated voltage” control word as“0”, “over-current Ⅰ stage latching by direction” control word as “0” Input tripping output platen, input the current that larger than over-current I stage value, imitate the fault to go on switch transmission test 4.6.19 LOAD TEST 105B Line is running with load, enter “run condition” menu to check whether protection sampling amplitude and phase relation are correct or not 94 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual PRINT ACTION REPORT 7B Available through the menu to print device information, including the following: 1) Action event report; 2) Action event parameters; 3) The fault waveform recorded; 4) Device value modify records; 5) Device switchs operate records 6) Device switchs chang records TRANSPORTATION AND STORAGE 8B Devices should be stored indoors that the temperature is -25 ℃ ~ +70 ℃, relative humidity not more than 95 % and the ambient air does not contain corrosive, flammable, explosive and dangerous things Avoid severe vibration, shock and collision in conveying 95 NEW CENTURY RELAYS 9B EDCS-8150 Station transformer protection & monitoring device instructionmanual APPENDIX 7.1 CHASSIS STRUCTURE 35B 7.1.1 A1 TYPE PANEL LAYOUT 106B EDCS-8150 A 10 11 12 13 14 ACT A KM+ SGXH-1 SGXH-2 KKJ-1 KKJ-2 BHR BTR SH ST TZXQ HWJHZXQ TWJKM- 24V B 10 11 12 OPERATE + B KZDX-1 KZDX-2 ALM-1 ALM-2 24V+ 24VVR+ VRG00 A A A A 10 11 12 COM2 10 11 12 13 14 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 COM1 B 10 11 12 13 14 DI10 DI11 DI12 DI13 DI14 DI15 DI16 DI17 DI18 DI19 GPS-A GPS-B CANH/ 485A CANL/ 485B 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ETHERNET DO6-1 DO6-2 DO7-1 D07-2 B B D08-1 10 DO1-1 DO8-2 DO9-1 DO9-2 DO10-1 DO10-2 DO11-1 DI11-2 DO12-1 DO12-2 DO1-2 DO2-1 DO2-2 DO3-1 DO3-2 DO4-1 DO4-2 DO5-1 DO5-2 重庆新世纪电气有限公司 FIG 7-1 panel layout 7.1.2 107B FIG 7-2 Terminals layout (Rear View) A1 TYPE DEVICE INSTALLATION 196.9 176.9 13.3 142.5 4-M4) FIG.7-3 Vertical view plans 96 FIG.7-4 Screen broached plans NEW CENTURY RELAYS 7.1.3 EDCS-8150 Station transformer protection & monitoring device instructionmanual A2 TYPE PANEL LAYOUT 108B EDCS-8150 A 10 11 12 13 14 15 16 17 18 ACT A KM+ SGXH-1 SGXH-2 KKJ-1 KKJ-2 BHR BTR SH ST TZXQ HWJHZXQ TWJKMBTWJ-1 BTWJ-2 KZDX-1 KZDX-2 24V B 10 11 12 OPERATE + B YXBJ-1 YXBJ-2 ALM-1 ALM-2 24V+ 24VVR+ VRG00 A A A A 10 11 12 13 14 15 16 17 18 19 20 COM2 DI10 DI11 DI12 DI13 DI14 DI15 DI16 DI17 DI18 DI19 10 11 12 13 14 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 COM1 GPSA GPSB CANH/ 485A CANL/ 485B ETHERNET B B B B 10 11 12 13 14 15 16 DO7 DO7 DO8 DO8 DO9 DO9 DO10 DO10 DO11 DO11 DO12 DO12 10 11 12 13 14 15 16 DO1 DO1 DO2 DO2 DO3 DO3 DO4 DO4 DO5 DO5 DO6 DO6 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 重庆新世纪电气有限公司 FIG 7-5 Panel layout 7.1.4 109B FIG 7-6 Terminals layout (Rear View) A2 TYPE DEVICE INSTALLATION 262±0.15 259.1±0.15 230.3 250.3 +0.2 251-0 13.3 142.5 4-? 110±0.15 127±0.15 4-M4 +0.2 143.5-0 FIG 7-7 Vertical view plans FIG 7-8 Screen broached plans 97 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual 7.2 COMMUNICATION CONNECTION 36B 7.2.1 COMMUNICATION NET OF CAN PORT 10B DCS-8000 series of protection measuring devices use CAN industry field bus, the connection of the network adopted shielded twisted pair wire is illustrated in Fig.7-9 Computer or comm server CAN EDCS-81501 CANH CANH 13 EDCS-81502 CANL CANH 14 13 EDCS-81503 CANL CANH 14 13 CANL 14 CANL R G00 G00 G00 G00 FIG 7-9 CAN communication connection chart In order to improve communication quality, the following suggestions for users reference: 1) Recommend: 500k (distance≤90m), 250k (distance≤180m), 125k (distance≤300m), 50k (distance≤800m), 20k (distance≤2000m) 2) Communication lines must be connected fast and reliably The communication in whole system will be affected if the connection of communication lines is bad, disconnected, shorted-circuit or the configuration of communication parameters is not right 3) Only one resistor of 120 Ω is permitted to connect with the device side of the bus in a whole CAN network of system Because communication bus and matching resistor makes a loop, it effectively prevent the self-excited oscillation on the bus to influence the communication 4) The shield ground G00 of the communication network should be connected with the shield ground of computer 5) Wiring in Fig.7-9 is an example used PCL-841CAN bus communication cards The CAN signal is transmitted by the short frame that the valid bytes count to 8, with the result that the transmitting time is short, interfered probability is low The function of automatic close will cut off the contact of the node with bus when the node communication is severity mistake so that the communication and other nodes on the bus are not uninfluenced So the anti-interference ability is very strong The CAN bus can work in peer-to-peer, any node can send information at any time to all others on bus, it can structure many host systems 7.2.2 THE COMMUNICATION NETWORK VIA RS-485 1B EDCS-8000 series device can use RS-485 to compose communication network that the protocol is IEC-60870-5-103 The transmitting medium of RS-485 is shielded twisted pair wire, and the communication distance can reach to 1200 meters, being a lot of the devices link up to a RS-485 bus or the baud rate is higher, the distance will accordingly shorten The EDCS-8000 series generally be slave in the system, the master could be a PC or a communication management device etc 98 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual If the master is not provided with RS-485 port but only the RS-232, the RS-232/485 convertor would be used (a kind of equipment used for transforming the interface level between RS-232 and RS-485) In fact, RS-485 net may be various topology structures, take the RS-422/485 communication car (PCL-745) for example The line form connection, which is connecting the devices of EDCS-8000 series to the communication network one after another from the place of master to the end, is suitable for the situation that the devices are fixed concentration and there is expanding demand in future In figure 7-10, Rt is an anti-reflective resistor which resistance must match for the cable impedance Generally be 120Ω Computer or comm server EDCS-81501 485 A A B EDCS-81502 B A 0 G00 G00 EDCS-81503 B A B G00 R G00 FIG 7-10 RS-485 communication connection chart To improve the quality of communication, the following suggestions for users reference: 1) Quality of shielded twisted pair is very important, and it is recommended the shielded twisted pair with AWG22 (0.25mm2) diameter, which two wires with different colors 2) Communication lines must be connected fast and reliably The communication in whole system will be affected if the connection of communication lines is bad, disconnected, shorted-circuit or the configuration of communication parameters is not right 3) Pay more attention to the single point grounding of the screen; the so-called single-point grounding means that on the screen of one communication line one and only one point is earthed Grounding at both ends will bring the ground loop current, resulting in inducing noise interference on the communication cable 4) On one communication line, the RS-485 ports must be the A (+) connected to A (+), B (-) to B (-), not be reverse 5) Communication lines should be away from the sources of electromagnetic interference, such as strong electricity lines, as far as possible 99 NEW CENTURY RELAYS 7.2.3 EDCS-8150 Station transformer protection & monitoring device instructionmanual CONNECTION OF ETHERNET NETWORK 12B Use cross-twisted-pair to connect a device to the other Ethernet card; Use direct-twisted-pair to connect a device to network equipment (such as switch) RJ-45 white orange orange white green blue white blue green white brown brown RJ-45 RJ-45 white orange white orange green orange white brown white green blue green white blue white blue orange blue white brown white brown brown brown FIG 7-11 Cross-twisted pair connections RJ-45 white orange orange white green green white blue blue white brown brown FIG 7-12 Direct twisted pair connections To improve the quality of communication, the following suggestions for users reference: 1) Choose ultra five types shielded high-quality cable 2) Communication cables must be connected imprisonment, reliable, joint bad, disconnected, short-circuit or shorted, and communications parameters set incorrectly happen can affect normal communication of the whole system 3) The color of two crystal connection is not more than one, but it can get the best effect if using the figure color 100 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual 7.3 DEVICE CONFIGURATION TABLE AND ORDERING INSTRUCTION 37B 7.3.1 DEVICE CONFIGURATION TABLE 13B Order number Location EDCS-8150 - 1 1 1.Device type Device type:seclet according to technical instruction or operating instruction 2.Chassis structure Chassis structure:5U S1 19 inch Chassis structure:6U S1 19 inch Power supply way DC control power supply(DC220V)(standard layout) DC control power supply(DC110V) AC control power supply(AC220V) 4.IO module Not configure module(standard layout) Configure module 5.TA secondary rated current TA secondary rated current:5A TA secondary rated current:1A 6.Communication way Communication way:CAN(standard layout) Communication way:485 Communication way:Ethernet Control way Not configure control circuit(standard layout) Control circuit with no holding(standard layout) Control circuit with holding EDCS-81500-110111 Standard layout DC220V 5U EDCS-81501-110111 EDCS-81502-110111 EDCS-81503-110111 7.3.2 ORDERING NOTICE 14B Power supply □220V DC □110V DC □other System voltage level □110kV □35kV □10kV Switching voltage □220V DC □24V DC □other Rated AC current Device size □5A U V U □other kV □1A mm × mm × mm Device color 101 NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instructionmanual 7.4 PROTECTION VALUE SETTING FORM 38B 7.4.1 EDCS-81503 DEVICE PROTECTION VALUE SETTING FORM 15B Project name: circuit name: Device name: circuit number: 1) Protection setting NO THE NAME OF SETTING SETTING SAMBOL THE RANGE OF SETTING THE STEP OF SETTING Control word - 0000-FFFF Control word - 0000-FFFF Control word - 0000-FFFF Overvoltage value Ugyd 220.00V~300.00V 0.01V Overvoltage time Tgy 0.00s~100.00s 0.01s Low voltage value Udyd 100.00V~220.00V 0.01V Low voltage time Tdy 0.00s~100.00s 0.01s With voltage value Uyy 50.00V~250.00V 0.01V Losing voltage value Uwyz 20.00V~300.00V 0.01V 10 Check no current value Iw 0.20A~5.00A 0.01A Th 0.00s~30.00s 0.01s 11 Backup auto-switch-in action time 12 Overload value Igfh 0.10A~100.00A 0.01A 13 Overload time Tgfh 0.00s~100.00s 0.01s NOTES If having no special remark, the setting word is set“1”, mean function input,“0”mean withdrawal TV disconnection detection Manual 2) trip no latching AUTO-SWITCH-IN TVDX 0/1 STBBS 0/1 Soft platen setting NO THE NAME OF SETTING THE RANGE OF SETTING THE STEP OF SETTING NOTES If having no special remark, the setting word is set“1”, mean function input,“0”mean withdrawal 102 Auto-switch-in way 0/1 Auto-switch-in way 0/1 Auto-switch-in way 0/1 Auto-switch-in way 0/1 Overvoltage alarm 0/1 Low voltage alarm 0/1 Overload alarm 0/1 ... OF INSTRUCTION S VERSION NO Instruction Version Updating abstract Updating date 10 The instruction and production may have a little change, please check the practical production and the instruction s... ORDERING INSTRUCTION 105 7.4 PROTECTION VALUE SETTING FORM 106 II NEW CENTURY RELAYS EDCS-8150 Station transformer protection & monitoring device instruction manual PART ONE TECHNICAL INSTRUCTION. .. Electrical Co., Ltd This instruction is applicable to the protection program of the following version: EDCS-81502 Station transformer protection and monitoring device V2.** EDCS-81503 Station transformer