The device collect 128 points for each cycle wave to get A/D sampling for CT, PT and DC transmitter, and calculate the AC monitoring value of current, voltage, active power, reactive pow
Trang 1EDCS-8000 Series of Power System Integrated
Trang 2Copyright: Chongqing New Century Electrical Co., Ltd
This instruction is applicable to the protection program of the following version:
EDCS-82201 General monitoring device version V1.**
UPDATING RECORD OF INSTRUCTION’S VERSION
Technical support: Tel: (023)68694458 Fax: (023)68626689
The first version prints in Mar 2010
Trang 3IMPORTANT INSTRUCT
Thank you for purchased production made by Chongqing New Century Electrical Co., Ltd For safe, correct and effective usage of these devices, please read the important information below
Please read the instruction carefully, and adjust, test or manipulate under the instruction’s prescript
To protect the device, do not insert or withdraw the module, touch chip and element when the power on
Please use reliable, high accuracy test instrument and device to test and measure the device
Accident analysis requires original records, the device version information, and field fault process description
If there is any abnormal or repaired requirement, please make contact with us
Trang 5CONTENTS
PART ONE TECHNICAL INSTRUCTION 1
1 GENERAL 1
1.1 APPLICATION 1
1.2 CHARACTERISTIC 1
1.3 FUNCTIONCONFIGURATION 1
2 TECHNICAL PARAMETERS 3
2.1 ENVIROMENTALPARAMETER 3
2.2 RATEDPARAMETERS 3
2.3 PERFORMANCEINDEX 3
2.4 OUTPUTNODECAPACITY 4
2.5 COMMUNICATIONINTERFACE 4
2.6 INSULATIONPERFORMACE 4
2.7 ELECTROMAGNETICCOMPATIBILITYCHARACTERISTICS 5
2.8 MECHANICALPROPERTIES 5
3 EDCS-82201 GENERAL MONITORING DEVICE 6
3.1 FUNCTIONPRINCIPLE 6
3.2 DEVICESETTING 15
3.3 DEVICEHARDWARE 32
PART TWO INSTRUCTION FOR USE 39
1 OPERATION INSTRUCTION 39
1.1 THEKEYS 39
1.2 THEMENU 39
2 DEVICE OPERATIONS 44
2.1 NORMALOPERATINGSTATE 44
2.2 ABNORMALINFORMATIONDISPOSA 45
3 INSTALLATION INSTRUCTIONS 47
3.1 PACKAGINGOPENINGINSPECTION 47
3.2 INSTALLATIONNOTICE 47
4 CIRCUIT TEST 48
4.1 TESTNOTICE 48
4.2 ACLOOPCHECK 48
4.3 INPUTCONTACTCHECK 48
4.4 OUTPUTCONTACTCHECK 48
4.5 MAINBOARDJUMPERSETTING 49
4.6 DEVICEUNITTEST 49
Trang 65 PRINT ACTION REPORT 51
6 TRANSPORTATION AND STORAGE 51
7 APPENDIX 52
7.1 CHASSISSTURCTURE 52
7.2 COMMUNICATIONCONNECTION 53
7.3 ORDERNOTICE 56
Trang 7PART ONE TECHNICAL INSTRUCTION
1.1 APPLICATION
EDCS-8220 general monitoring device is a new generation of new substation integrated automation system To meet the subustation integrated automation requirement of national gride and some non-electric industry, it adopt new computer technique, network comunication technique and the latest international standard in the view of comprehensive solution of substation automation based on several years development and reaserch experience of substation integrated automation.The device is suitable for 110kV and below voltage grade of various substation
1.2 CHARACTERISTIC
1) Large screen LCD and full-Chinese menu design, more humanized debug and operation 2) Full-Chinese display and printing for event and setting values, discarding character expressing
3) High-performance 32 bit microprocessor with large capacity RAM and FLASH RAM bring powerful data processing and storage ability; keeping in FLASH RAM, data wouldn’t lose after power interrupt
4) Adopting CAN net as internal communication network, data information pass in and out fluently
5) Two kind of time checking mode: IRIG-B code and background communication
6) Clean and beautiful sealed aluminum case with Strong anti-electromagnetic interference, vibration resistance, well adapted harsh electricity environment
7) Perfect self-checking function meeting the requirement of status overhaul
1.3 FUNCTION CONFIGURATION
1) Printing
2) Monitoring
3) Synchronization
4) TV fuse fail and TA disconnection alarm
5) Zero-sequence over-voltage alarm
6) Frequency over-limit monitoring
7) Remote logic latching
8) Power quality monitoring
9) Continuous monitoring and recording odd harmonics at most 31 times
Trang 8The detailed configurations of each model device see the following table:
Device function
Trang 9DC power: 220V or 110V(please indicate when ordering) Allowable deviation:-20%~+20%
AC voltage: 100 / 3V(Rated phase voltage Un);
AC current: 5A or 1A(Rated phase current In, please indicate when ordering);
Rated frequency: 50Hz
Overload capacity:
Current loop: 1.2 times of rated current, continuous working
Voltage loop: 1.4 times of rated voltage, continuous working
Power dissipation:
Current loop: Not more than 0.5 VA /Phase (when Rated value is 5A)
Not more than 0.5 VA /Phase (when Rated value is 1A) Voltage loop:Not more than 0.5 VA /Phase (when Rated value is 100V)
Not more than 0.5 VA /Phase (when Rated value is 100/ V)
DC loop: Normal, not more than 30 W
Trip, not more than 35W
2.3 PERFORMANCE INDEX
1) AC voltage monitoring
Monitoring range: 0~100.0V(Phase)
Monitoring accuracy: 0~80.0V, error≤±0.2%
2) AC current monitoring
Monitoring range: 0~5A
Monitoring accuracy: during 0~1.00A, error≤±0.01A;during1.00~5.00, error≤±0.2%
3) Power monitoring: error≤±0.5%
4) DC collection monitoring: error≤±0.5%
5) Frequency monitoring
Monitoring range: 45.00~55.00Hz
Monitoring accuracy: error≤±0.02Hz
6) Switch value deflection resolution is no more than 1ms
3
Trang 102.4 OUTPUT NODE CAPACITY
Signal node capacity:
Allowable long-term utilize current 5A
Sever current 0.3A(DC220V, V/R 1ms)
Switch closing/tripping output node capacity:
Allowable long-term utilize current 8A
Sever current 0.3A(DC220V, V/R 1ms)
Other output relay node capacity:
Allowable long-term utilize current 5A
Sever current 0.2A(DC220V, V/R 1ms)
2.5 COMMUNICATION INTERFACE
3 communication ports are supported: CAN or RS-485, and Ethernet Power industry standard DL/T667-1999 (IEC60870-5-103), XSJ-7000DH and Modbus can be choosen for communication protocol Communication speed can be set
2.6.2 DIELECTRIC STRENGTH
In normal testing ambient atmosphere, the device is robust enough to withstand an AC voltage-endurance test at 2000V, 50Hz(rated insulation voltage>63V), 0.5kV, 50Hz(rated insulation voltage≤63V), and lasting for 1min, yet without breakdown or flashover phenomenon
In the course of trial, when a test loop is powered on the others are connected to ground with equal potential
2.6.3 Impulse voltage
In normal atmosphere environment, between energized and non-energized sections as well as between those circuits with no electric connections, the device is able to withstand a short-time inrush voltage test with 1.2/50μs standard lightning surge, for the circuit of which voltage is less than 63V, the test voltage is 1kV, and for that more than 63V, the test voltage is 5kV
Trang 112.6.4 MOISTURE-HEAT RESISTANT
At highest test temperature: +40, after two cycles (48 H) test time, the insulation of each regulated part of device are no less than 1.5 measured by a mega ohmmeter at 500V open-circuit voltage, and it can withstand 75% voltage of the dielectric strength test, without breakdown or flashover phenomenon
2.7 ELECTROMAGNETIC COMPATIBILITY CHARACTERISTICS
Pulse group anti-interference:meet the protocol of IEC 60255-22-1(GB/T 14598.13) Electrostatic discharge disturbance: meet the protocol of IEC 60255-22-2(GB/T 14598.14) Radiation electromagnetic field disturbance: meet the protocol of IEC 60255-22-3(GB/T 14598.9)
Fast transient interference and pulse group interference: meet the protocol of IEC 60255-22-4(GB/T 14598.10)
Surge immunity: meet the protocol of IEC 61000-4-5(GB/T 14598.18)
Radiofrequency field inductive conduction disturbance anti-interference: meet the protocol of IEC 61000-4-6(GB/T 14598.17)
Power current interference: meet the protocol of IEC 60255-22-7(GB/T 14598.19)
The electromagnetic launch limit: meet the protocol of IEC 60255-25(GB/T 14598.16)
Trang 123 EDCS-82201 GENERAL MONITORING DEVICE
3.1 FUNCTION PRINCIPLE
3.1.1 REMOTE MONITORING UNIT
TV/TA converts strong voltage and current into 5A/1A and 100V alternating waveforms is converted into suitable small signals for computer sampling by high accurate convertor, which are sent to A/D after filtering and become digital signal, finally enter into CUP for calculation The device collect 128 points for each cycle wave to get A/D sampling for CT, PT and DC transmitter, and calculate the AC monitoring value of current, voltage, active power, reactive power, active kwh, reactive kwh, power factor, frequency and etc according to discrete expression of N times equal interval sampling
AC collection input and output are as follows:
Input: Ua, Ub, Uc, U0, Ux, Ia, Ib, Ic, 3I0
Calculate: Ua, Ub, Uc, Uab, Ubc, Uca, U0, Ia, Ib, Ic, I0, P, Q, CosΦ, f, ±kwh, ±kvarh, 31 times harmonic component。
DC collection input are 0-5V, 1-5V signals, output after converting are as follows:
DC1, DC2, DC3, DC4, DC5, DC6。
AC sampling principle is equal interval sampling for a continuous waveform; according to the sampling theorem the sampling points of a sine wave can describe the characters of the sine wave completely Actually voltage and current cannot be pure sine wave and it must include higher harmonics Thus more sampling points more accurate, however, for the limit of hardware actual condition, it is impossible to add sampling points infinitely, so our device choose sampling
of 128 points
As each cycle doing N points sampling, frequency tracking calculation is necessary, or sampling as per 50Hz cycle will arise error because power frequency is unequal to 50Hz The device do frequency tracking calculation and equal interval sampling after adjust sampling period
Remote monitoring includes two-meter method and three-meter method and the monitoring method is shown in the figure:
Trang 13For two-meter method monitoring, voltage input are Ua, Ub, Uc, while calculation amount adopted are Uab and Ucd, and current input are Ia,Ic The calculation formula is as follow:
Q cb c ab a
2 2
Q P
P COS
Where, Ucb is the RP value of line voltage Ubc
Ф1 is angle that phase current lag line voltage Ua, Ф2 is angle that phase current Ic lag line voltage Ucb
For three-unite method monitoring, voltage input are Ua,Ub, Uc, and current input are Ia,
Ib, Ic The calculation formula is as follows:
c c
c b b
b a a
aI COS U I COS U I COS
U
c c c b b b a a
aI SIN U I SIN U I SIN
U
FIG 3-1 Two-meter method monitoring connection
(voltage adopt YY connection)
FIG 3-2 Three-meter method monitoring connection
(voltage adopt YY connection)
Ub Ua
Trang 142 2
Q P
P COS
Where, Φ is the angle I lagged U
For two-meter VV connection monitoring, voltage input are Uav, Ubc, and current input are
Ia, Ic
3.1.2 DC COLLECTION
Sampling signals: DC collection DC1, DC2, DC3, DC4, DC5, and DC6 Device can complete the monitoring of 6 DC collections which can be voltage input or current input (current input is extended function) Electrical isolation between DC input and CPU control system is achieved through DC/DC converter DC collection is calculated according to the maximum and minimum of setting values
3.1.3 REMOTE COMMUNICATION UNIT
Remote communication is introduced by null node, converted into digital signal after photoelectric isolation and then enters into device to acquire status signal and deflection signal For the filter circuit within the collection of remote communication data, the scanning time of the CUP to remote communication is 0.3125ms to guarantee its resolution less than 1ms, and record start as deflection begin, thus the signal collection can prevent the contact chatter In addition, each signal collection has filed-setting limit to make sure the accuracy of signal function After device confirm the status deflection, the first deflection record time is regarded as the remote communication deflection time Its time sequence is shown as figure:
Uab Ubc
*
B C
*
FIG 3-3 Two-meter method monitoring connection
(voltage adopt VV connection)
Trang 15The upper computer can define the remote communication data name displayed on the device by configuration tool and cut the number of remote communication data according to the actuality, after the definition; download it into the monitoring device through network port The device display program can call the remote communication data name to display and print the remote communication data SOE
3.1.4 REMOTE CONTROL UNIT
Control operation is ordered by dispatching or local monitoring, and control unit is mainly responsible for the reception and return to check the order, then according to the correct order to output corresponding control information, i.e., output the order for switch tripping or closing Each remote control output is controlled by CPU, and the operation steps include: select, return
to check and execute, which achieve the output checking of relay, guarantee the safe and available executing of remote control Moreover, the device has hardware self-checking latching function which can prevent error output for hardware damage
3.1.5 INTEGRAL ENERGY FUNCTION
Basic calculation of kwh:
Active kwh calculation formula:
Reactive kwh calculation formula:
Where wh0 and VARh0 are the initial value of active and reactive kwh, the accumulative value of the energy before this period, and ΔWh and ΔVARh are the energy increment during this period
Calculate once per minute, then:
Where K is the time interval to calculate kwh, K=60/n, n is the times of calculation per minute, e.g if n=1200, i.e., calculate 20 times per second and K=0.05 Pi is the average of P in every time interval, i.e., average in 0.05s, ΔWh and is the active kwh increment of 1 minute
wh wh Pdt wh
wh t 0
0 0
VARh VARh
Qdt VARh
100036003600
1 60
0
FIG 3-3 Remote communication data sequence chart
Input
Optical coupler output
Trang 16Similarly:
Figure out Wh and VARh according to the formula, where, the unit of P is W and unit of Q
is VAR kWh is kilowatt-hour (i.e degree) and kVAR is kilovar All of them are secondary value of active and reactive kwh, which multiply the product of TA, TV changing ratio to convert into first value
3.1.6 SYNCHRONIZATION FUNCITON
According to settings closing operation can be no check, synchronization check and no-voltage check, and synchronization check only or no-voltage check only, however, here only explain the operation process of synchronization check closing
3.1.6.1 ENTER THE SYNCHRONIZATION CHECK CLOSING PROGRAM
In local method, receive the closing order from management SCM, or in remote method, receive closing order from upper computer, then set corresponding KK as 1(KK is one of EEPROM), after receive confirmed signal, enter to operate closing program
3.1.6.2 NO CHECK CLOSING OPERATION
If configuration no check, the unit will close directly without assessing the differential condition of voltage and frequency after receive the closing order from upper computer or unit
3.1.6.3 NO-VOLTAGE CHECK CLOSING OPERATION
If monitoring configuration is no-voltage check closing, after enter into the closing program, device send out closing order instantly and closing the breaker when line voltage Ux<Uwyzd
(Uwyzd is no-voltage check setting value)or bus voltage Um, Um<Uwyzd
3.1.6.4 SYNCHRONIZATION CHECK CLOSING
If configuration is synchronization check closing, and voltage of both sides are higher than low-voltage blocking value, synchronization check closing operation will be done as the follow steps:
1) Voltage difference check: if there is voltage on both side, find out voltage difference If Ux
is from A,B line voltage(Ux is from analogy of Ubc/Uca), ΔU=Uab–Ux If Ux is from A phase voltage(Ux is from analogy of Ub/Uc), ΔU=Ua–Ux If ΔU ≤Utc (Utc is voltage difference setting value), it is regarded as qualified If ΔU Utc, and it still cannot meet the requirement during the return time of synchronization, that means communication cannot meet the synchronization condition and have to exit the operation procedure of closing 2) Frequency difference check: if voltage difference is qualified, find out frequency difference
Δf =f1–f2, if Δf ≤ftc(ftc is frequency difference setting value), it is qualified and will go
to phase difference check If Δf ftc, and it cannot meet the requirement during the return time of synchronization, that means communication cannot meet the synchronization
Trang 17condition and have to exit the operation procedure of closing
3) Synchronization check closing: go for synchronization check after both voltage and frequency difference qualified Compare the time difference of square wave rising edge between bus voltage and line synchronization voltage to find out phase difference, calculating once per cycle(about 20ms),and the calculate formula is Tm is bus voltage cycle, while Δt is the time difference of square wave rising edge of both side voltage, and the both unit is ms, so Φc=0.36°fm·Δt。When phase difference is changed from
1800 to 1600 , calculate the closing ahead angle Φt, and the calculate formula is Φt=
×360°=0.36·Δf·tht (Tc is slip dispatch period, is ahead time of synchronization)
4) Calculate the variable quantity of phase difference for each period: calculate phase difference Φc each period after find out Φt To make sure complete the synchronization check closing in a slip dispatch period and that the phase difference of both side voltage close to 0 as closing, predicting closing time is adopted, and the concrete operation is as follow: calculate the variable quantity ΔΦc of a period (the time when calculate the two phase difference)phase difference Φc by slip dispatch period Tc and bus voltage period
Tm, and the formula is :
360 /
yc c
should deduct the procedure operation time from frequency sampling to figure out tyc Stop closing operation and communicate to exit synchronization information if it yet cannot meet the synchronization condition during synchronization return time Monitoring frequency and voltage difference should be together with phase difference check, and it should be exit and communicate exiting reason if frequency or voltage difference changes to unsatisfied the condition
C
htT t
T t
Trang 187) When enter into synchronization check, if ΔUvoltage difference setting value,
Δffrequency difference setting value, Φc≤20 and no less than 20 times distinguish in 1s all satisfy the condition, it is regarded as loop network power supply and instant closing is available
Note: for this device the synchronization function is fixed on remote control 1 closing
3.1.7 ANALOG CALIBRATION
For the hardware in the device, all the components in each channel are fixed parameter Thus the disparity of channel component parameter (current, voltage convertor, resistance in filter circuit, capacitance etc.) cause amplitude and phase error of each channel AC collection coming from the AC sampling data after fourier-transform To make sure the accuracy of sampling, software calibration for A/D channel is necessary The principle is: the amplitude of AC coming from the AC sampling data after fourier-transform multiply a calibration coefficient Kx, and add a calibration angle φx in phase angle to eliminate the effect to AC signals because of different channel component parameter The A/D channel calibration is the process to figure out calibration coefficient Kx of channel amplitude and phase calibration angle φx The channel calibration for this device includes manual and automatic, and the first one is to input channel calibration coefficient and angle by MMI
Attentions: Channel calibration is very important and only input the gradeⅡpassword of user can the main microcontroller enter into channel calibration To avoid big error of sampling value because of too large AC signal or damage of some channel component, which may cause abnormal of calibration value Kxi and φxi, the amplitude calibration coefficient is limited in 0.850~1.150, and phase calibration angle φxi is limited in ±8.00°
1) Accuracy automatic modulation
Accuracy automatic modulation is used in device maintenance, which is to add a rated value in each channel and input an equal value to exterior from clavier, then press ―OK‖, herein this coefficient is read-in EEPROM The accuracy automatic modulation also includes phase modulation (Debug at factory, user does not do it)
2) Accuracy manual modulation
It is the extension for the first function When manual modulation is needed, add a rated value in channel and calculate the coefficient between rated value and displayed value to read-in EEPROM, finally modulate the accuracy
3.1.8 TA DISCONNECT AND TV FUSE FAILURE
3.1.8.1 TV FUSE FAILURE ALARM
TV single phase disconnect discrimination: at TV fuse failure, both phase and line voltage amplitude and phase changed, according to it, the discrimination is as follow:
Positive-sequence voltage is less than 30V and any other phase current is more than
Trang 190.04In
Negative-sequence voltage is more than 8V
Meeting any above term, TV fuse fail will be alarmed 10s later, while clear TV fuse fail sign after voltage recover (three phases voltage is higher than 50V, phase difference of voltage is less than 100)
Illustration: there is no positive-sequence and negative-sequence voltage calculation and
TV fuse fail discrimination when the device calculates power by VV connection or two-meter method
3.1.8.2 TA DISCONNECT ALARM
max 1
2 0 04
3 I In K I
here: In is secondary rated current(1A or 5A); I2 is negative-sequence current;
Imax is maximum current; K1 is macro definition, take as 0.25
In operation, satisfy all terms for TA disconnect discrimination, and continuous 3ms discrimination meet the terms will come to TA disconnect
TA disconnect recover and handling
max 1
2 0 04
3 I In K I
Handling for TA disconnects recover: after disconnect, clear the sign of TA disconnect when continuous 60ms discriminate as TA disconnect recover
Illustration: there is no positive-sequence and negative-sequence voltage calculation and
TA disconnect discrimination when the device calculates power by VV connection or two-meter method
3.1.9 ZERO-SEQUENCE OVER-VOLTAGE ALARM
3.1.9.1 ZERO-SEQUENCE OVER-VOLTAGE ALARM LOGIC
Zero-sequence voltage component operating criterion:
U0>Uozd
Here, U0 is zero-sequence voltage; Uozd is setting value for zero-sequence voltage
3.1.9.2 ZERO-SEQUENCE OVER-VOLTAGE ALARM LOGIC DIAGRAM
Here, t01 is ZS over-voltage 1 time setting value,t02 is ZS over-voltage 2 time setting value
Trang 203.1.10 COMPATIBLE APPLICATION INSTRUCITON
The device can be applied with line protection device of 110kV and below voltage level, power plant, bus and substation which need amount display and printing about switching state
3.1.13 FAULT MONITORING FUNCTION
In operation, when control circuit disconnect, read-in control circuit disconnect state signal from input When change 1 to 0, communicate input change information after discriminated as meeting the terms by setting time limit When change 0 to 1, communicate input change information after discriminated as meeting the terms by setting time limit
In operation, when control power abnormal, and read-in control power abnormal state signal When change 1 to 0, communicate input change information after discriminated as meeting the terms by setting time limit When change 0 to 1, communicate input change information after discriminated as meeting the terms by setting time limit
In operation, when SF6 air pressure abnormal, read-in SF6 air pressure abnormal state signal When change 1 to 0, communicate input change information after discriminated as meeting the terms by setting time limit When change 0 to 1, communicate input change information after discriminated as meeting the terms by setting time limit
In operation, when spring operating mechanism without energy storage, read-in spring operating mechanism without energy storage state signal When change 1 to 0, communicate input change information after discriminated as meeting the terms by setting time limit When change 0 to 1, communicate input change information after discriminated as meeting the terms
by setting time limit
Above are common input fault monitoring In device actual use, define the remote communication data after learning about the on-site use
Trang 213.2 DEVICE SETTING
The design of the device function is according to the largest configuration as shown in the following setting value Here includes system value, auxiliary value, factory value (output setting and output matrix etc.) and also internal value area
The purpose of internal value area is: initialize for software and hardware of device
Used for first value display
Used for first value display
Used for first value display
Used for first value display
Used for first value display
The following is operation mode control command 1, ―√‖or ―1‖ means pickup, and ―×‖or ―0‖ means exit
Illustration:
Bus voltage 1st value: Bus voltage transformer 1st rated voltage
Bus voltage 2nd value: Bus voltage transformer 2nd rated voltage
Line voltage 1st value: Line voltage transformer 1st rated voltage
Line voltage 2nd value: Line voltage transformer 2nd rated voltage
Zero sequence voltage 1st value: Zero-sequence voltage transformer 1st rated voltage Zero sequence voltage 2nd value: Zero-sequence voltage transformer 2nd rated voltage Measuring current 1st value: Measuring current transformer 1st rated current
Measuring current 2nd value: Measuring current transformer 2nd rated current
Zero sequence current 1st value: Zero-sequence current transformer 1st rated current Zero sequence current 2nd value: Zero-sequence current transformer 2nd rated current When measuring current transformer 2nd rated current is 1A, the range of measuring current 1st value is 1~2000A
Trang 22The following is operation mode control command 1, ―√‖or ―1‖ means pickup, and ―×‖or ―0‖ means exit
Trang 233.2.3 REMOTE SIGNALING SETTING
3.2.3.1 REMOTE SIGNAL SETTING 1
RANGE
SETTING
3.2.3.2 REMOTE SIGNAL SETTING 2
RANGE
SETTING
Trang 2413 Remote signal 31 anti-jitter time 0.01~0.99s 0.01s 100ms
3.2.3.3 REMOTE SIGNAL SETTING 3
RANGE
SETTING
3.2.3.4 REMOTE SIGNAL SETTING 4
RANGE
SETTING
Trang 258 Remote signal 62 anti-jitter time 0.01~0.99s 0.01s 100ms
The following is operation mode control command 1, ―√‖or ―1‖ means pickup, and ―×‖or ―0‖ means exit
Trang 263.2.5 OUTPUT CONFIGURATION
RANGE
SETTING
Trang 2735 Output 35 return time 0.00~100.00s 0.01s
Illustration:
Value is set well by factory according to concrete application project
The setting time is 0.01~99.99s:
Drive output as soon as the operating condition is satisfied If operating condition return then output will return, and if operating condition doesn’t return in the setting return time, output will be remained till the setting return time (Analog event and premonitory signal relay can operate automatic return repeatedly, which is mainly used for driving alarm bell and bugle) Setting time is 100.00s:
Drive output as soon as the operating condition is satisfied, and it won’t return untill receive the return order from unit or upper computer.(output of analog event signal relay cannot operate repeatedly and its continuing operating will be active only after return, which is mainly used for where light indicator is needed)
Setting time is 0.00s:
Drive output as soon as the operating condition is satisfied, whereas if no satisfaction it will return automatically after 120ms delay (Mainly analogy the operating features of single conventional relay component is applied in testing and real monitoring of TA and TV disconnect without the signal alarm of operating output, which is corresponding to the alarm sign in device)
3.2.6 OUTPUT MATRIX
Trang 30DO01 DO02 DO03 DO04 … … … DO39 DO40