Test-universe-advanced-differential-module-application-note-example-of-use-transformer-enu

43 339 0
Test-universe-advanced-differential-module-application-note-example-of-use-transformer-enu

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

Thông tin tài liệu

Testing Transformer Differential Protection Practical Example of Use Testing Transformer Differential Protection Manual Version: Expl_TDiffProt.ENU.1 - Year 2013 © OMICRON electronics All rights reserved This manual is a publication of OMICRON electronics GmbH All rights including translation reserved The product information, specifications, and technical data embodied in this manual represent the technical status at the time of writing and are subject to change without prior notice We have done our best to ensure that the information given in this manual is useful, accurate, up-to-date and reliable However, OMICRON electronics does not assume responsibility for any inaccuracies which may be present The user is responsible for every application that makes use of an OMICRON product OMICRON electronics translates this manual from the source language English into a number of other languages Any translation of this manual is done for local requirements, and in the event of a dispute between the English and a non-English version, the English version of this manual shall govern Content Preface Application Example Theoretical Introduction to Transformer Differential Protection 2.1 Protection Principle 2.2 Operating Characteristic 2.3 Zero Sequence Elimination 11 2.4 Transformer Inrush 13 Practical Introduction to Transformer Differential Protection Testing 15 3.1 Defining the Test Object 16 3.1.1 3.1.2 3.2 Global Hardware Configuration of the CMC Test Set 26 3.2.1 3.2.2 3.2.3 3.3 Example Output Configuration for Differential Protection Relays 26 Analog Outputs 27 Binary Inputs 27 Local Hardware Configuration for Differential Protection Testing 28 3.3.1 3.3.2 3.4 Device Settings 16 Defining the Differential Protection Parameters 18 Analog Outputs 28 Binary Inputs 28 Defining the Test Configuration 29 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 General Approach 29 Configuration Test 30 Operating Characteristic Test 33 Trip Times Test 36 Inrush Blocking Test 39 Testing Three-Winding Transformer Differential Protection 42 Support 43 Please use this note only in combination with the related product manual which contains several important safety instructions The user is responsible for every application that makes use of an OMICRON product © OMICRON 2013 Page of 43 Preface This paper describes how to test the transformer differential protection function It contains an application example which will be used throughout the paper The theoretical background of transformer differential protection will be explained This paper also covers the definition of the necessary Test Object settings as well as the Hardware Configuration for these tests Finally the Advanced Differential test modules are used to perform the tests which are needed for this protection function Supplements: Sample Control Center file Example_AdvDifferential_Transformer.occ (referred to in this document) Requirements: Test Universe 2.41 or later; Advanced Differential and Control Center licenses Note: © OMICRON 2013 The description of the Differential test module is not a part of this document Page of 43 Application Example 220 kV 400/1 Protection functions (87) Differential Protection (50/51) Definite Time Overcurrent Protection Transformer Differential Relay 600/1 110 kV Figure 1: Feeder connection diagram of the application example © OMICRON 2013 Page of 43 Parameter Name Parameter Value Frequency 50 Hz 160 MVA 231 kV Transformer data 115.5 kV Notes Rated power Rated voltage, Side (used for the calculation of the transformation ratio of the transformer) Rated voltage, Side (used for the calculation of the transformation ratio of the transformer) Yyn0 Vector group 400 A / A CT ratio, Side 600 A / A CT ratio, Side CT data 0.25 Iref Differential characteristic settings 6.0 Iref 0.3 Slope of the differential characteristic 0.7 Slope of the differential characteristic 4.0 Iref Harmonic restraint settings Idiff>, Pick-up value of the differential protection (Iref is a reference current which can be obtained from the relay manual In this case it is the rated current of the transformer) Idiff>>, Second element of the differential protection (there is no stabilization above this value) 20% Idiff Bias current where the first slope ends and the second slope begins 2nd harmonic restraint value (relative to the fundamental frequency differential current) Table 1: Relay parameters for this example Note: © OMICRON 2013 Testing of the Restricted Earth Fault protection function, Thermal Overload protection function, etc is not part of this document Page of 43 2.1 Theoretical Introduction to Transformer Differential Protection Protection Principle The most important components in a power transmission and distribution system are the transformers, the generators and the busbars Usually differential relays are applied as their main protection against shortcircuit faults within the protected area The current differential principle is based on Kirchhoff’s law, i.e the sum of the currents flowing into a conducting network is zero I load side I load side Protected Object Side 1A 0° 1A -120° 1A 120° Side 1A 180° 1A 60° 1A -60° Ph A Protected Object Ph B Ph C Protected Zone Figure 2: Protection principle of the transformer differential protection This principle applies to each phase separately Therefore, the following equation can be calculated for each phase n I i  I1  I   In  i 1 During a fault in the protected zone, a current will flow from one phase to another phase or to ground In this case the sum of the measured currents in at least one phase is not zero Therefore, the relay can detect the fault However, this is only valid if all CT ratios are the same and if the current is not transformed within the protected object The transformation ratio and the vector group of a transformer, as well as the CT ratios and the positions of the CT star-points, will cause problems with the calculation of the current sums Numerical differential relays can calculate these effects and, therefore, compensate for their influence For electromechanical differential relays, interposing transformers have to be used instead Note: © OMICRON 2013 The following parts of this document will only focus on transformer differential protection Page of 43 2.2 Operating Characteristic If the transformer is equipped with an on-load tap changer (OLTC), its transformation ratio varies over the tapping range This changes the ratio of the currents on side and side and thus produces a spill (out-ofbalance) current in the relay Some other effects, such as the current transformer accuracy (including CT saturation), the magnetization of the transformer, etc., also add to this spill current The magnitude of the spill current increases as the load on the transformer increases The differential relay, however, must not operate in this case The corresponding solution and further sources for spill currents will be dealt with in the following sections Idiff = ISide - ISide Sum Current Transformer Tap changer / Leakage Magnetization Iload Figure 3: Natural error currents of the transformer In Figure it can be seen that the magnitude of the spill current (Sum) depends on the transformer load current To compensate for these error currents, the differential protection must be provided with a bias element This bias element depends on the current flowing through the transformer which, under normal conditions, is the load current Note: The calculation method of the bias current depends on the relay manufacturer (see Table 2) Calculation Method Manufacturer Notes ISide  ISide  AEG/ALSTOM/AREVA *), (K1 = 2), e.g PQ7x, P6x Various conventional (electromechanical) relays *) = only valid for two-winding transformers, for three-winding transformers see below SIEMENS (K1=1), e.g 7UT5x/7UT6x GEC (K1=1), e.g series KBCH SEL (k1=2), e.g SEL5 AEG/ALSTOM/AREVA *), (K1 = 2) *) = only valid for three-winding transformers, for two-winding transformers see above I Side K1  ISide  / K1  ISide , ISide max  ISide , ISide   ISide  ISide  cos SEG/Woodward; conventional (electromechanical) relays Elin/VATECH, e.g DRS GE Multilin SR745 ABB Table 2: Selection of different calculation methods for the bias current (depending on the relay manufacturers); The currents are scaled to the nominal current of the transformer © OMICRON 2013 Page of 43 With this value the construction of an operating characteristic is possible Idiff ID>> Characteristic Sum Tripping Blocking Current Transformer Tap changer / Leakage ID> Magnetization Ibias Figure 4: Operating characteristic of a transformer differential protection device As shown in Figure 4, the operating characteristic has to cover the spill currents during normal conditions, thus enabling the device to determine between blocking and operating The design of the operating characteristic (number of line segments, slope, etc.) differs widely between manufacturers and relay types For the following example, the AREVA P633 is used Figure and Figure show the parameters and the tripping characteristic of the P633 Figure 5: Relay settings for the differential operating characteristic (AREVA P633) Idiff Idiff>>> = (072.144) 0.7 ( 6) m= 2( fixe dv alu e) = m2 2.1 07 Idiff> = 0.25 (072.142) 07 0.3 ( m1 = 5) 2.14 IR,m2 = (072.147) Ibias Figure 6: Operating Characteristic for the AREVA P633 © OMICRON 2013 Page of 43 Figure and Figure show the settings and the operating characteristic of the Schweitzer SEL-387 for comparison Figure 7: Relay settings for the operating characteristic (SEL-387) Idiff U87P = = P2 SL SLP 70 % % = 30 O87P = 0.25 IRS1 = Ibias Figure 8: Operating characteristic for the SEL-387 © OMICRON 2013 Page 10 of 43 3.4 Defining the Test Configuration 3.4.1 General Approach When testing the differential protection, the following steps are recommended: > Configuration Test: Testing the wiring and the configuration parameters of the differential protection including transformer data, CT data and zero sequence elimination > Operating Characteristic Test: Verifying the position of all operating characteristic line segments > Trip Times Test: Verifying the trip times of the differential protection elements > Inrush Blocking Test: Verifying the inrush blocking characteristic These tests can be performed with the advanced differential test modules: > Diff Configuration > Diff Operating Characteristic > Diff Trip Time Characteristic > Diff Harmonic Restraint © OMICRON 2013 Page 29 of 43 3.4.2 Configuration Test Differential protection relays are usually set to be very sensitive Therefore, even small differential currents will lead to a trip If the wiring is incorrect or if parameters such as the nominal voltages, the zero sequence elimination, the CT ratios or the CT star-point directions are not set correctly, currents flowing through the protected area may lead to an unwanted operation The configuration test simulates external faults with fault currents flowing through the protected area During these faults the relay must not trip and therefore, this test confirms that the wiring, as well as the above mentioned parameters, are correct General General settings of the test are entered in this tab 1 3 © OMICRON 2013 This setting defines on which side of the transformer the fault and the source should be located for the fault simulation The test time should be set long enough to allow the measured currents from the relay to be read These settings define if the CMC should generate voltages and whether the test should be time synchronized via GPS or IRIG-B In this example neither of these will be necessary The Trigger Logic has to be defined according to the relay configuration Note: If the relay uses multiple trip contacts, they should be linked with OR This way the test will be assessed as failed if any of the trip contacts are triggered Page 30 of 43 Test Data In this tab the test points can be entered 3 Enter the test current and click Add to set a test point The test current will be relative to the nominal current of the fault side The new test point appears in the test point list The fault type can be defined with this setting Note: Only one fault type can be set per test module Add more test modules to the OCC file, if multiple fault types are to be tested The current outputs of the CMC are shown in the single line view © OMICRON 2013 Page 31 of 43 Test This tab is used to assess and document the test 1 2 Note: Define whether you want to enter the measured phase currents or the calculated differential and bias currents For most of the digital differential relays the option Idiff and Ibias is the easiest way to assess the relay behavior Start the test by clicking the Start/continue test button on the toolbar This activates the input fields for the measured currents Now the measured currents can be read from the relay and entered here It should be kept in mind that the current output will be stopped after the test time is elapsed The test current and the status of the test are displayed here The test can be assessed with this option If a trip occurs during the test time, the test will automatically be assessed as failed To test the numerical zero sequence elimination, it is recommended that at least one phase-toground fault is placed at the grounded side of the transformer In order to assess the test, the differential and bias currents that should be measured by the relay must be calculated The necessary formulae can be obtained from the relay manual If these theoretically calculated currents match the currents read out from the relay, the test can be assessed as passed During the test the differential current must be zero in each phase © OMICRON 2013 Page 32 of 43 3.4.3 Operating Characteristic Test This test confirms the operating characteristic of the differential relay Test shots are placed in the operating characteristic diagram and if they are above the operating characteristic, the relay must trip If they are below the characteristic the relay must not trip General General settings of the test are entered in this tab 1 2 If this option remains unselected, a search test will only search within the specified tolerances If, however, this option is selected, the search test will also search outside of the tolerance band In this case the test will always be assessed as passed A pre-fault current can be applied before each test shot This setting activates a voltage output during the test In this example it is not necessary to select the voltage output Select this option if the test should be time synchronized via GPS or IRIG-B For the operating characteristic test, the Trigger Logic has to be defined according to the relay configuration Note: If the relay uses multiple trip contacts, they should be linked with AND This way a test shot will only be assessed as tripped if all of the trip contacts are triggered © OMICRON 2013 Page 33 of 43 Shot Test With the shot test, test shots can be placed in the operating characteristic diagram This can be done by clicking the operating characteristic diagram and then clicking Add to set the previously clicked test shot Alternatively, the test shots can be set by entering the currents Idiff and Ibias manually To test the operating characteristic, test shots can be placed above and below the operating characteristic outside the tolerance band In order to confirm that the operating characteristic is within the specified tolerances, it is recommended that test shot pairs are placed close to the boundary of the tolerance band © OMICRON 2013 Page 34 of 43 Search Test With the search test, vertical search lines can be added by clicking the operating characteristic diagram and then clicking Add or by manually entering the current Ibias of the search line The test module will automatically place test shots along this line to search for the exact position of the operating characteristic With the search test, the exact position of the operating characteristic can be found, whereas with the shot test, it can be quickly confirmed whether the operating characteristic is within the specified tolerance band Note: It is not possible to a shot test and a search test in the same test module Remove all test shots before adding search lines or vice versa Only one fault type can be set per test module If multiple fault types are to be tested, more test modules can be added to the OCC file When testing the operating characteristic it is recommended that each line segment is tested at two different positions (if possible) These test positions should not be too close to each other and also not too close to the corner points of the operating characteristic This ensures that the characteristic settings are assessed properly © OMICRON 2013 Page 35 of 43 3.4.4 Trip Times Test This test confirms the trip times of the differential protection function Therefore, test shots with different differential currents are applied to measure the corresponding trip times Factors 1 Select Use evaluation factors to overwrite the test object tolerances The new tolerances can be entered below as Diff Current Factors and Diff Time Factors In this example it is not necessary to select this function This setting activates a voltage output during the test In this example it is not necessary to select the voltage output © OMICRON 2013 Page 36 of 43 General 2 3 A pre-fault current can be applied before each test shot This setting defines the slope of the test line The resulting test line is also shown in the operating characteristic diagram All the test shots in this test module will be placed on this line Therefore, it is advantageous to have not more than one intersection with the operating characteristic For the majority of differential relays this setting can remain at the default value For the trip times test, the Trigger Logic has to be defined according to the relay configuration Note: If the relay uses multiple trip contacts, they should be linked with AND This way a test shot will only be assessed as tripped if all of the trip contacts are triggered © OMICRON 2013 Page 37 of 43 Test In the test tab the test shots are defined To place a new test shot, either click on the trip time test plane (1) or enter the differential current manually (2) and then click Add Note: Only one fault type can be set per test module If multiple fault types are to be tested, more test modules can be added to the OCC file In order to test the trip time settings of the relay, it is recommended that one test shot is placed above Idiff> and one above Idiff>> (Test Object parameters) This ensures that the trip times corresponding to each differential current element are tested © OMICRON 2013 Page 38 of 43 3.4.5 Inrush Blocking Test This test confirms the operation of the inrush blocking function The test module generates differential currents which contain harmonics which allows the inrush blocking characteristic to be tested General 1 Select this option to apply a post-fault after each test shot During the post-fault period, only fundamental frequency currents without harmonics will be generated Note: If the relay trips during the post-fault, the test will be assessed as passed 2 3 This setting activates a voltage output during the test In this example it is not necessary to select this function For the inrush blocking test, the Trigger Logic has to be defined according to the relay configuration Note: If the relay uses multiple trip contacts, they should be linked with OR This way a test shot will only be assessed as blocked if none of the trip contacts are triggered © OMICRON 2013 Page 39 of 43 Shot Test The shot test applies test shots to the harmonic restraint test plane This plane shows the harmonic blocking characteristic with the differential current and the percentage of the harmonic current To set a new test shot click the test plane and then click Add The differential current and the harmonic percentage can also be entered manually and then Add is clicked to define the test shot This option is used to define the number of the harmonic that should be tested For the inrush blocking in this example, this will be the second harmonic The fault type can be defined with this setting Note: Only one test phase can be set per test module If different phases are to be tested, more test modules can be added to the OCC file © OMICRON 2013 Page 40 of 43 Search Test The search applies test shots along horizontal search lines to determine the harmonic blocking characteristic Apply search lines by clicking on the characteristic and then clicking Add Or by entering the differential current of the search line manually and then clicking Add This option is used to define the number of the harmonic that should be tested For the inrush blocking in this example, this will be the second harmonic If this option remains unselected, a search test will only search within the specified tolerances If, however, it is selected, the search test will also search outside the tolerance band In this case the test will always be assessed as passed The test phase can be defined with this setting Note: Only one test phase can be set per test module If different phases are to be tested, more test modules can be added to the OCC file Note: It is not possible to a shot test and a search test in the same test module Remove all test shots before adding search lines or vice versa When testing the operating characteristic, it is recommended that the characteristic is tested outside the tolerance band just above Idiff> and just below Idiff>> (or at any other parameter that limits the harmonic blocking) © OMICRON 2013 Page 41 of 43 3.4.6 Testing Three-Winding Transformer Differential Protection A test for three-winding transformer differential protection devices uses the same basic steps as the test for two-winding transformer differential protection devices Note: For most three-winding transformer differential relays, it is sufficient to perform the trip times test and the inrush blocking test once However, the stability test and the operating characteristic test must cover each winding of the transformer Side to Side 2: > Stability Test > Operating Characteristic Test > Trip Times Test > Inrush Blocking Test Side to Side 3: > Stability Test > Operating Characteristic Test Note: To test from Side to Side the relay has to be rewired Additionally, the global Hardware Configuration and the local Hardware Configurations of each test module have to be adapted Feedback regarding this application is welcome by email at TU-feedback@omicron.at © OMICRON 2013 Page 42 of 43 Support When you are working with our products we want to provide you with the greatest possible benefits If you need any support, we are here to assist you! 24/7 Technical Support – Get Support www.omicron.at/support www.omicronusa.com/support Offering our customers outstanding support is one of our top priorities At our technical support hotline, you can reach well-educated technicians for all of your questions Around the clock – competent and free of charge Make use of our 24/7 international technical support hotline: +43 59495 4444 Additionally, you can find our Service Center or Sales Partner closest to you at www.omicron.at or www.omicronusa.com Customer Area – Stay Informed www.omicron.at/customer www.omicronusa.com/customer The customer area on our website is an international knowledge exchange platform Download the latest software updates for all products and share your own experiences in our user forum Browse through the knowledge library and find application notes, conference papers, articles about daily working experiences, user manuals and much more OMICRON Academy – Learn More www.omicron.at/academy www.omicronusa.com/academy Learn more about your product in one of the training courses offered by the OMICRON Academy OMICRON electronics GmbH, Oberes Ried 1, 6833 Klaus, Austria, +43 59495 © OMICRON 2014 Page 43 of 43

Ngày đăng: 10/05/2018, 11:03

Mục lục

  • Preface

  • Application Example

  • Theoretical Introduction to Transformer Differential Protection

    • 2.1 Protection Principle

    • 2.2 Operating Characteristic

    • 2.3 Zero Sequence Elimination

    • 2.4 Transformer Inrush

    • Practical Introduction to Transformer Differential Protection Testing

      • 3.1 Defining the Test Object

        • 3.1.1 Device Settings

        • 3.1.2 Defining the Differential Protection Parameters

        • 3.2 Global Hardware Configuration of the CMC Test Set

          • 3.2.1 Example Output Configuration for Differential Protection Relays

          • 3.2.2 Analog Outputs

          • 3.2.3 Binary Inputs

          • 3.3 Local Hardware Configuration for Differential Protection Testing

            • 3.3.1 Analog Outputs

            • 3.3.2 Binary Inputs

            • 3.4 Defining the Test Configuration

              • 3.4.1 General Approach

              • 3.4.2 Configuration Test

              • 3.4.3 Operating Characteristic Test

              • 3.4.4 Trip Times Test

              • 3.4.5 Inrush Blocking Test

              • 3.4.6 Testing Three-Winding Transformer Differential Protection

              • Support

Tài liệu cùng người dùng

Tài liệu liên quan