YK 6 On load voltage regulating controller Operation Instruction Guizhou Changzheng Electric Co ,Ltd Welcome to use On Load Tap Changer of Guizhou Changzheng! Please read the operating instructions of[.]
YK-6 On-load voltage regulating controller Operation Instruction Guizhou Changzheng Electric Co.,Ltd Welcome to use On Load Tap Changer of Guizhou Changzheng! Please read the operating instructions of this product before you put the on load tap changer into service Please pay special attention to the following items: Check and accept the products according to the packing list when receiving products Keep the evidence if there are any damages during transportation in order to claim compensation from the responsible party and protect your rights The tap changer only can be used with the transformer which specified in the order You need to consult with our company in advance if you want to change the purpose of this product The installation, put into operation, maintenance and repair of the product should be complied with the operating instructions and relevant provisions of security All data in this manual may be different in details from the tap-changer that we delivered We reserve the right to change without notice Content General introduction………………………………………………1 Main technical parameters…………………………………………1 Panel drawings……………………………………………………2 Outline and installation method………………………………3 Controller wiring…………………………………………………4 Controller interface and parameter settings…………………6 Operation and maintenance………………………………………15 File and spare parts………………………………………………15 Notice to customer…………………………………………………15 10 Appendix: MODBUS communication protocol…………………15 2019.5.10 General introduction 1.1 Safety instructions Personnel engaged in the installation, commissioning, operation, maintenance and repair of this unit must: - Qualified professional qualifications - Strict compliance with the operating instructions of this manual Illegal operation or misuse may result in: - serious personal injury - Damage to the device and the user's equipment - Reduce the efficiency of this unit This instruction emphasized some important matters of safety instruction in four ways Warning Give the word of “Warning” when ignoring a requirement will cause the life damage of operator This is a warning of danger to life and health, disregarding this warning can lead to the serious or fatal injury Careful Give the word of “Careful” when ignoring a requirement will lead to the damage to the equipments This information indicates particular danger to this device or other equipment of the user, but the serious or fatal injury can’t be excluded Caution In order to emphasize at any time, the word of “Caution” will be used, remind it should be careful when operating according to the requirements of “Warning” and “Caution” Note These are additional explanations for a certain subject 1.2 Application YK-6 On-load voltage regulating controller (Hereinafter referred to as the controller) application for remote to tap changer This controller main use for ZD motor driver unit, controller’s main faction is make local controller communicate with local ZD motor driver unit by communication line or optical fiber Main technical parameter No Specification Work power Power loss Connection method with MDU Technical parameter AC 85 ~ 265V ,50/60Hz Above7W set RS485 communicate port; set optical fiber: multimode ,62.5/125μm,ST Contact, wave length 820nm, maximum transmission distance 1kM。 table Note The above two are used to communicate with the local control module ZDK controller, mutually standby, follow the MODBUS protocol 4 Automatic pressure regulating function Switch output Switch input 11 12 Sampling voltage Set voltage Voltage regulation accuracy Delay time Actual voltage AC 0-500V Range: AC 85-460V, step 1V Range: 0.1-9.9%, step 0.1% Range: 5-180s, step 1s Range: 0-500V group BCD code group status signal group alarm signal 1→ N, N → 1, STOP instruction input Passive normally open contact output (contact load capacity: 1A / 240V AC, 0.5A / 24V DC, 0.3A / 220V DC) Passive normally open contact (Input by external device) Communication group RS485 (A, B) communication port Interface group TCP / IP 100M network port (RJ45) Display method 4.3-inch touch screen Tap position, tap position action status various parameter settings Parameter display: various status signals, Display content local body failure, temperature, the number of operations Log records query Working Indoor, ℃ ~ +40 ℃, relative humidity ≤ environment RH95% non-condensing Installation Screen cabinet installation method Panel drawing 3.1 Front panel diagram (Figure 1) Touch screen Button 3.2 Back panel diagram (Figure 2) Outline and installation 4.1 Outline as show as Figure Figure (both sides of the bracket locking installation method diagram) 4.3 Hole Size: 151×76 Caution: When the front panel screws are fixed, you need to drill Φ5 holes on the cabinet 5.Controller wiring Figure (Circuit block diagram) 7107 4.2 Installation method can be used screws to install fixed for the front panel,also can be used on both sides of the bracket locking installation (Figure 4) 5.1 Working power connection Working power AC 85 ~ 265V, 50 / 60Hz Note When using DC power access special order, and +, - can not be confused 5.2 Controller and motor drive unit connection The connection between controller and electric mechanism is provided with RS485 communication port and optical fiber interface These two ports are used for communication with ZDK controller of local ZD motor control unit and are mutually standby Routine recommended RS485 communication port, the use of optical interface to be special orders X3 terminal shown in Table Table Terminal Terminal Terminal Signal Note number labeling meaning type X3-1 A X3-2 B X3-3 G Communication Interface RS485 Follow the MODBUS protocol G for the shield connection Note When operating with the YK-6, the local ZD motor-internal change-over switch must be placed in the "remote controlled state." 5.3 X1 input, output terminals shown in Table Table Terminal Terminal number labeling Terminal meaning Signal type X1-1 A X1-2 B X1-3 D-COM Tap position BCD code COM X1-4 D01 Tap position bit BCD code 20 X1-5 D02 Tap position bit BCD code 21 X1-6 D04 Tap position bit BCD code 2 X1-7 D08 Tap position bit BCD code 23 X1-8 D10 Tap position bit BCD code20 X1-9 D20 Tap position tens BCD code21 X1-10 S-COM Limit output common Communication Interface RS485 BCD code output Status signal Note Follow the MODBUS protocol Passive normally open contact (Contact load capacity: 1A / 240V AC, 0.5A / 24V DC, 0.3A / 220V DC) X1-11 LMT1 Min position limit output X1-12 LMTN Max position limit output X1-13 RUN Run signal output X1-14 I-R Remote command state X1-15 I-D Motor drive command status X1-16 I-L Local (controller) instruction status X1-17 I-A Automatic control instructions state X1-18 W-COM Alarm signal common X1-19 STEP-OU T Out of step alarm X1-20 FAULT Fault alarm X1-21 1→N Remote command input (1 → N) X1-22 STOP Remote command input (stop) X1-23 N→1 Remote command input (N → 1) X1-24 R-COM Remote command input common output Alarm signal output Passive normally open contact Remote input (Input by external device) Prompt: Communication Interface RS485 transmission tap position, operation instructions signal, a variety of status signals, alarm signals, etc; Parallel control can also be used to connect with other YK-6 controller to achieve parallel operation function; Use RS485 interface to participate in parallel the number of controllers up to units 5.4 TCP / IP (RJ45) network port to transmit the tap position, operation command signals, various status signals, alarm signals, etc., for connection with other intelligent devices (LED) The network port can also be used with another YK-6 controller port to connect to run in parallel functions Prompt: The maximum number of controllers that can parallel connection and using network ports is 5.5 When sampling the voltage input, connect the potential transformer PT, the access range is AC 0-500V Prompt: Only the realization of automatic voltage regulator control access to the sampling voltage 5.6 Ground mark " " must be reliably grounded 6.Controller interface and parameter settings The controller uses 4.3-inch LCD touch 6.1 Turn on the main interface Power on the controller after the main interface appears Setting Search Alone Manual System fault: When controller detects a fault in local electric mechanism, mark is displayed and flashes, otherwise the mark is not displayed on the interface Communication failure: When controller has a problem with local electric mechanism communication connection, the the interface does not display this mark mark is displayed and flashes, otherwise Prompt: In all the settings and query interface are blocked → N, N → 1, STOP instruction operation, only in the main interface can be instruction operation 6.2 User interface Setting Search Alone Manual Run ID: Displayed while the tap switch is running Displayed displayed when N→1 6.3 Query Interface After touching the mark when 1→N, on the home screen, the query interface is displayed Prohibit operation Parameter Log Prohibit operation 6.4 Real-time parameter display interface When the “Parameter” icon is touched on the query interface, the real-time parameter display interface is displayed 参数 Parameter 工作状态 Working status 远方 Remote 锁定状态 Lock state 解锁 unlock 指令选择 Instruction selection 手动 Manual 运行状态 Running status 到位 in place 操作次数 Number of operations 58118 控制状态 Control status 就绪 ready 最小分接 Min tap 故障形式 Fault type 最大分接 Max tap 17 就地温度 Local temp 31℃ 通讯地址 Communication address 实际电压 Actual voltage 217.2V 连动位置 9a、9c This interface reflects various real-time parameters of the local motor driver unit and the YK-6 controller Working status: There are three kinds of status: local, stop, and remote Instruction selection: There are three states: manual, automatic, and remote Lock state: There are two states, unlock and lock (For external access blocking signal detection) Running status: There are two kinds of status, they are in place and running Control status: There are two kinds of status: ready and fault Fault type: There are three types of status, namely, open/closed, power failure, and self-test failure Communication address: The communication address between this controller and the local ZDK controller It is set to "1" at the factory 6.5 Log Display Interface When the "Log" icon is touched on the query interface, the log display interface is displayed Log display Time Event NO 10 step Page up Page down There are a maximum of 10,000 log records Users can query records of operations or failures for a long time as needed 6.6 Parameter Setting Interface After to touching the displayed on the home screen, the parameter setting interface is Parameter Setting Working model Instruction selection Time setting Net parameter Prohibit operation Disable operation identification: " " mark appears during all parameter setting, and latch → N, N → 1, STOP instruction operation 6.7 Working Mode Selection Interface The operating mode selection interface is displayed after touching the "operation mode" mark under the parameter setting interface Working Mode Selection Alone Parallel master Parallel slave Prohibit operation Confirm In this interface, the "Alone" mode is the default setting of the controller When parallel control is required, "parallel master" or "parallel slave" is selected 6.8 Communication Address Setting Interface When the “parallel slave” icon is touched under the operation mode selection interface, the communication address setting interface is displayed Communication address Prohibit operation Confirm In parallel operation, when the controller is set to "parallel master", the controller communication address defaults to 01; when the controller is set to "parallel slave", the communication address needs to be reset, and all slave address codes participating in the parallel connection must not be repeated 6.9 instruction selection interface When the “Instruction Select” icon is touched under the parameter setting interface, the command selection interface is displayed Instruction selection Manual Auto Remote Prohibit operation The "Manual" mode under this interface is the controller default setting 6.10 Automatic Mode Parameter Setting Interface The automatic mode parameter setting interface is displayed after touching the "automatic" mark on the instruction selection interface Confirm Setting value Setting parameter Unit Range Step size Content Setting voltage Precision of voltage regulation Delay Prohibit operation Only the setting value field needs to be set in this interface Delay time setting: Set according to the required operating frequency of the switch in the range of 5-180S; set the delay time, it must be more than 10 seconds Under the premise of guaranteeing the power supply quality, set the delay time as long as possible This can avoid frequent tap changer operation and extend the life of the switch Setting voltage and voltage regulation accuracy settings: Connect a sampling voltage of 100V; adjust the output voltage of the regulator so that the output voltage deviates from the ±2.5% voltage value of the 100V sampling voltage, that is: Lower limit voltage = setting voltage - setting voltage × pressure regulation accuracy; The upper limit voltage = setting voltage + setting voltage × precision of voltage regulation; Example: setting voltage is 100V, voltage regulation accuracy is set to 2.5%; Then: the lower limit voltage = 100V-100V × 2.5% = 97.5V; The upper limit voltage = 100V + 100V × 2.5% = 102.5V; When the sampling voltage is lower than the set lower limit voltage, the controller itself issues a "1→N" command; When the sampling voltage is higher than the set upper limit voltage, the controller itself issues an "N→1" command; After the delay time set by the controller is delayed (for example, 10 seconds delay), the switch shall switch to the corresponding 1→N or N→1 direction synchronously, and adjust the voltage to “set voltage”=“actual” The output voltage" realizes the automatic control of the output voltage of the transformer system 6.11 Auto-adjusting the main interface Setting Search Alone Auto Setting voltage Actual voltage When the YK-6 controller operates in the auto-regulation mode, a real-time histogram will appear below the number of tap positions Both sides of the histogram display the real-time values of the setting voltage and the actual voltage when the sampling voltage is within the setting range The bar graph is green when there is no need to regulate the voltage, and it is red when it is out of the setting range When the sampling voltage exceeds the setting range and the corresponding delay time is performed, the pressure adjustment command is automatically issued 6.12 Parallel Voltage Regulator Main Interface Setting Search Parallel unit Parallel master Manual Out of step When the YK-6 controller is operating in the shunt regulator mode, the mark is displayed on the left side of the screen When the controller participating in the parallel connection loses synchronization, the mark is displayed at the bottom right of the interface Prompt: After the mark is displayed, all → N, N → 1, and STOP instructions are operated, and the controller sends an out-of-step alarm signal Synchronization corrections need to be set up to be manually corrected individually 6.13 Participate in parallel interface After touching the mark on the main interface of the parallel voltage regulator, the participating parallel interface is displayed 参与并联控制器 Participating in parallel control 从机 Slave 通讯地址 Communication address 通讯状态 Communication state 故障 Faulf 分接位置 Tap position 00 并联状态 Parallel state 失步 Out of step This screen shows all slaves participating in parallel control Prompt: Working mode selection "parallel main" also need to participate in the parallel number of slaves to choose from Prompt: It is also necessary to reset the command selection after returning from the "slave slave" operation mode to other operating modes 6.14 Time setting interface Year Month Day Time Prohibit operation Confirm 6.15 Network Parameters Interface Prohibit operation In the TCP / IP settings, the IP address is the IP address of the controller If you need to access the unit by IP address, set the corresponding address 7 Operating and maintenance 7.1 The user to install the correct wiring and the corresponding parameter settings can be put into use after the controller 7.2 controller in use, should always be kept clean, there should be no conductive dust covering the body and the terminal Documents and spare parts Product Certificate: One Manual: One 1-24 plug: a group (factory installed in the X1 socket) 1-5 Plug: a group (factory installed in the X2 socket) 1-3 Plug: a group (factory installed in the X3 socket) Mounting bracket: two User notes 9.1 When ordering, it is necessary to provide the type of tap changer, voltage regulation series, middle position, required input / output interface 9.2 Users under the custody and use of the rules, from the installation of the use of 12 months, and shipped from the manufacturer to the user within 18 months deadline, the product due to the quality of the cause of damage or does not work properly, the manufacture The factory can be replaced or repaired for users without compensation 10 Appendix: MODBUS protocol YK-6 controller using MODBUS RTU protocol YK-6 controller communication physical layer using optical or RS485, baud rate 4800, the data format for the start bit, data bits, no parity, a stop bit The YK-6 controller opens 03, 05, and 06 function codes to make it easier for the user to read information about the controller, and to perform operations of raising, lowering, and stopping the controller, and modifying the communication address of the machine Read data (function code 03H) An example of the following table is an example of reading the current tap position (register 03) from the No 01 slave The data frame received by the slave (YK-6 controller) Slave Function Start Start Read data Read data CRC16 CRC16 address code address address number high number low low high high Low 01H 03H 00H 03H 00H 01H 74 0AH The data frame returned by slave (YK-6 controller) (the current tap position is 06) Slave Function Data length Data segment CRC16 low CRC16 address code (2 bytes) high 01H 03H 02H 00H, 06 H 38H 46H YK-6 controller data call address table: Address Parameter Data Type Property 0001H Max tap position Uint16 R 0002H Min tap position Uint16 R 0003H 0004H 0005H Current tap position Uint16 High position number Uint16 of operations Low position number Uint16 of operations R Remark If high position are 10, 11, 12, corresponding to a, b, c, the low position for the step(e.g: 22a, data is 0x0a16) R R 0006H Temperature value Uint16 R 0007H Humidity value Uint16 R 0008H State quantity Uint16 R 0009H Linkage position Uint16 R 000AH Linkage position Uint16 R 000BH Linkage position Uint16 R 000CH Linkage position Uint16 R 000DH Linkage position Uint16 R 000EH Linkage position Uint16 R Format with register Status Description SN Bit address Description Bit1~bit2 Operating modes: 00-Stop, 01-Local, 10-Remote Bit3 Operating status: 0-Switch to position, 1-switching Bit4 Locked state: 0-Unlock, 1-Lock Bit5 Fault status: 0-Ready, 1-Air switch open Bit6 Fault Status: 0-Ready, 1-Power Failure Bit7 Fault Status: 0-Ready, 1-Self-test fault Bit8 Minimum limit: 0-Normal, 1-Minimum limit Bit9 Maximum limit: 0-Normal, 1-Maximum limit Bit14 Action direction: 0-No action, 1-N→1 10 Bit15 Action direction: 0-No action, 1-1→N Remote control format (function code 05H) Remote control upper Slave function address code Remote Remote Remote Remote CRC16 CRC16 control control command command low high address high address low high low 01H 05H 00H 01H FFH 00H DDH FAH Remote control lower Slave function Remote Remote Remote Remote CRC16 CRC16 address code control control command command low high address high address low high low 01H 05H 00H 02H FFH 00H 6cH 0aH Remote control stop Slave function Remote Remote Remote Remote CRC16 CRC16 address code control control command command low high address high address low high low 01H 05H 00H 03H FFH 00H 3DH CAH Remote address description Address Parameter 0001H Remote control upper 0002H Remote control lower 0003H Remote control stop Data Type Uint16 Uint16 Uint16 Property S S S Remarks