Coordination of Protection to IEC 60947-4-1 Coordination Tables 1SBC 0097 00 R1001 edition Dec 2001 Home Fuse MCCB MMS Softstarters UL Comb MCB ABB is providing a large offer of coordination tables needed for any motor supply feeder for which protection against overload and short circuit are mandatory in industrial applications Choice Guidance For instance, a table given for 80kA is covering the intermediate short circuit leveel i.e 70, 60, kA at the same voltage However, you may find some cheaper solution for lower short circuit levels in the database : the SCPD upstream is calibrated to give the cheapest solution for the whole combination starter according to the highest shor circuit level General Remarks - to read before using the coordination tables Please read those remarks before you start using the coordination They will give you the general data and help you use the tables properly Following basic functions are achieved : overload protection, motor control, short circuit protection, isolation These functions are applied here for standard starters : direct-on-line (DOL), reverser, star-delta, softstarters Coordination Types Any table is in conformity with the standard IEC 60947-4-1 which defines two types of coodinations : - Type : there is not any risk for the operator and assets, damage to the starter is acceptable, its replacement for re-starting is generally necessary - Type : the single acceptable risk is a light welding of the contactor, that means the contacts shall be easily separated either by electrical control or using a tool After a short circuit, whatever its level, re-starting is allowed after a few verifications : all the protection device functions are still operational >> Coordination Tables - choose your type of protection - Fuses - MCCBs - MMS - MCBs - Softstarters - UL Combination Starters Short Circuit Protection Devices The starters given in the tables are protected starters or combination starters i.e the SCPD (Short Circuit Protection Device) and the starter are mounted in the same compartment or enclosure Various SPCDs are proposed : Moulded-Case Circuit Breaker (MCCB), Manual Motor Starter (MMS), Switch-Disconnector-Fuse or Switch-Fuse Circuit Breakers or fuses coordinated with starters cannot be determined directly : tests in Power Laboratories shall be carried out to qualify the coordination type at low fault and high fault currents ABB has got a large knowledge about short circuit protection in its qualified Laboratories in Europe (Low Voltage Agreement Group : LOVAG) Use of a SCPD not in compliance with the manufacturers' recommandations (type, settings) may invalidate the coordination Home Fuse MCCB MMS Softstarters UL Comb MCB General Remarks Motor Current Tables are based on 4-pole, 3-phase motor currents Indicative currents are given Magnetic Tripping Current Magnetic tripping current is everytime indicated and chosen to withstand the sub transient current at the starting phase Ambient Temperature Tables are given for 40°C ambient temperature For higher temperature a derating factor must be applied : Fuses : 0.8 to In when ambient temperature is 70°C MCCBs : 0.8 to In when ambient temperature is 60°C Thermal Overload Relay without derating up to 55°C, 0.9 In at 70°C Safety Perimeter It indicates the minimum distances of any metallic plates from the components in order to avoid any breakdown during short circuit Starting Normal starting means up to 5s (cold state) at full speed (class 10) and up to 2s (warm state) Long starting or heavy duty means starting time between to 30s (class 30) Thermal overload relays DU type and MMS are class 10A Thermal overload relays SU type are class 30 Reverser Table A "reverser" (two identical contactors) table is given by the corresponding "DOL" table Heavy duty star-delta starters Heavy duty star-delta starters are star-delta starters for which : - the motor speed reached at the end of the star period is less than 85% of the nominal one, mainly due to the incertainty of the load inertia - the connecting diagram to the motor is not in accordance with the one described in Main catalogue 1SBC0004 99 R1001 (p 8/10) - the dwelling time (transition between star and delta connection) is longer than 80ms Note : one only of the above conditions leads to "heavy duty" class Home Fuse MCCB MMS Softstarters UL Comb MCB FUSE Ue V Iq kA Coor type Starting type SCPD type SCPD curve Size kW 400 50 2 Normal Normal Normal Din Fuse Din Fuse Din Fuse 04/02/00 04/02/00 Normal Din Fuse HD Din Fuse HD Din Fuse SD Din Fuse SD Din Fuse FG4080NS2.1af FM4080NS2.1af FG4080NSIN2.1 FM4080NSIN2.1 FG4080HDIN2.1 FM4080HDIN2.1 FG4080HD2.1 FM4080HD2.1af FM4080SD1.1 FG4080SD1.1 FM4080SD2.1 FG4080SD2.1 29/08/01 29/08/01 04/02/00 04/02/00 04/02/00 04/02/00 04/02/00 12/11/01 27/09/00 27/09/00 05/04/00 05/04/00 100 Normal Din Fuse 415 440 80 80 2 Normal Normal BS Fuse Din Fuse 0.37 7.5 0.37 7.5 0.37 355 0.37 290 0.37 250 0.37 290 0.37 200 0.37 200 0.37 200 0.37 250 355 355 355 355 0.37 55 0.37 55 0.37 355 0.37 55 0.37 55 FG4050NS1,1a/b FG4050NS2.1a/b gG gG gG aM gG aM gG aM gG aM aM gG aM gG gG aM gM gG aM FG4000NS1.1 FM4000NS1.1 FGB4180NS2.1 FG4480NS2.1 FM4480NS2.1 04/02/00 04/02/00 04/02/00 04/02/00 04/02/00 500 80 Normal Din Fuse Normal Din Fuse HD Din Fuse HD Din Fuse SD Din Fuse SD Din Fuse 2 Normal Normal Normal Din Fuse Din Fuse Din Fuse Normal Din Fuse HD Din Fuse HD Din Fuse SD Din Fuse SD Din Fuse gG aM gG aM gG aM gG aM aM gG gG aM gG gG gG aM gG aM gG aM gG aM aM gG gG aM 0.37 315 0.37 315 0.37 355 0.37 355 0.37 200 0.37 200 0.37 200 0.37 200 400 355 355 400 0.37 11 0.37 11 1.1 500 1.1 500 0.37 355 0.37 355 0.37 200 0.37 200 0.37 200 0.37 315 560 400 400 400 FG5080NS2.1af FM5080NS2.1af FG5080NSIN2.1 FM5080NSIN2.1 FG5080HDIN2.1 FM5080HDIN2.1 FG5080HD2.1 FM5080HD2.1 FM5080SD1.1 FG5080SD1.1 FG5080SD2.1 FM5080SD2.1 FG6935NS1.1 FG6935NS2.1 FG6950NS2.1af FM6950NS2.1af FG6950NSIN2.1 FM6950NSIN2.1 FG6950HDIN2.1 FM6950HDIN2.1 FG6950HD2.1 FM6950HD2.1 FM6950SD1.1 FG6950SD1.1 FG6950SD2.1 FM6950SD2.1 29/08/01 29/08/01 04/02/00 04/02/00 04/02/00 04/02/00 04/02/00 04/02/00 27/09/00 27/09/00 05/04/00 05/04/00 04/02/00 04/02/00 29/08/01 29/08/01 04/02/00 04/02/00 04/02/00 04/02/00 04/02/00 04/02/00 27/09/00 27/09/00 05/04/00 05/04/00 80 690 35 50 Table Last Update Glossary SCPD HD NS SD Short Circuit Protection Device Heavy Duty Normal start Star Delta gG aM Fuselink for general protection Fuselink for motor starter protection IN INSUM Motor Protection Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB Latest changed 14/11/2001 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 50 kA - Normal start - up, type : Note : FG4050NS1.1a/b gG Fuse type gG Direct-on-line starters with Switch - fuse 400 V, 50 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 Ie [A] 1.2 1.5 2.6 3.5 6.6 8.5 11.5 15.2 Switch-fuse Type OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D Fuse type gG [A] 10 10 10 10 20 20 25 25 25 40 Contactor Size Type 00 00 00 00 00 00 00 00 00 00 B6 B6 B6 B6 B6 B6 B7 B7 B7 A16 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type E16DU2.7 E16DU2.7 E16DU2.7 E16DU2.7 E16DU6.3 E16DU6.3 E16DU18.9 E16DU18.9 E16DU18.9 E16DU18.9 Group Current Max setting range Current [A] 0.9 - 2.7 0.9 - 2.7 0.9 - 2.7 0.9 - 2.7 - 6.3 - 6.3 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 Imax [A] 2.7 2.7 2.7 2.7 2.7 6.3 9 12 16 FG4050NS1.1b Fuse type gG Direct-on-line starters with Switch - fuse 400 V, 50kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 Ie [A] 1.2 1.5 2.6 3.5 6.6 8.5 11.5 15.2 Switch-fuse Type OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D Fuse type gG [A] 10 10 10 10 20 20 25 35 40 40 Contactor Size Type 00 00 00 00 00 00 00 00 00 00 A9 A9 A9 A9 A9 A9 A9 A9 A12 A16 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type E16DU2.7 E16DU2.7 E16DU2.7 E16DU2.7 E16DU6.3 E16DU6.3 E16DU18.9 E16DU18.9 E16DU18.9 E16DU18.9 Group Current Max setting range Current [A] 0.9 - 2.7 0.9 - 2.7 0.9 - 2.7 0.9 - 2.7 2,0 - 6.3 2,0 - 6.3 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 Imax [A] 2.7 2.7 2.7 2.7 2.7 6.3 9 12 16 FG4050NS1.1a Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB Latest changed 10/07/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 50 kA - Normal start - up, type : Note : FG4050NS2.1a/b gG Fuse type gG Direct-on-line starters with Switch - fuse 400 V, 50 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 Ie [A] 1.2 1.5 2.6 3.5 6.6 8.5 11.5 15.2 Switch-fuse Type OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D Fuse type gG [A] 10 10 10 10 20 20 20 20 20 25 Contactor Size Type 00 00 00 00 00 00 00 00 00 00 B7 B7 B7 B7 B7 B7 B7 B7 B7 A16 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type E16DU2.7 E16DU2.7 E16DU2.7 E16DU2.7 E16DU6.3 E16DU6.3 E16DU18.9 E16DU18.9 E16DU18.9 E16DU18.9 Group Current Max setting range Current [A] 0.9 - 2.7 0.9 - 2.7 0.9 - 2.7 0.9 - 2.7 - 6.3 - 6.3 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 Imax [A] 2.7 2.7 2.7 2.7 6.3 6.3 9 12 16 FG4050NS2.1b Fuse type gG Direct-on-line starters with Switch - fuse 400 V, 50kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 Ie [A] 1.2 1.5 2.6 3.5 6.6 8.5 11.5 15.2 Switch-fuse Type OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D Fuse type gG [A] 10 10 10 10 20 20 20 20 20 25 Contactor Size Type 00 00 00 00 00 00 00 00 00 00 A9 A9 A9 A9 A9 A9 A9 A9 A12 A16 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type E16DU2,7 E16DU2,7 E16DU2,7 E16DU2,7 E16DU6,3 E16DU6,3 E16DU18,9 E16DU18,9 E16DU18,9 E16DU18,9 Group Current Max setting range Current [A] 0,9 - 2,7 0,9 - 2,7 0,9 - 2,7 0,9 - 2,7 - 6,3 - 6,3 5,7 - 18,9 5,7 - 18,9 5,7 - 18,9 5,7 - 18,9 Imax [A] 2.7 2.7 2.7 2.7 2.7 6.3 9 12 16 FG4050NS2.1a Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB Latest changed 10/07/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 80 kA - Normal start - up, type : Note : FG4080NS2.1af gG Fuse type gG Direct-on-line starters with Switch - fuse 400 V, 80 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.37 0.55 0.75 1.1 1.5 Ie [A] 1.2 1.5 2.6 3.5 2.2 5.5 7.5 6.6 8.5 11.5 15.5 19 22 25 30 32 37 44 50 60 63 72 85 105 135 165 200 240 290 350 420 520 545 610 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 250 290 315 355 Switch-fuse Type OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS63D OS63D OS125D OS125D OESA250D OESA250D OESA250D OESA250D OESA250D OESA400D OESA400D OESA400D OESA630D OESA630D OESA630D OESA800D OESA800D OESA800D Fuse type* gG [A] 6 10 10 10 16 16 25 32 32 40 50 63 63 80 100 100 125 125 160 160 200 200 250 315 400 400 500 630 630 800 800 800 Contactor Size Type OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA1H OFAA1H OFAA1H OFAA1H OFAA1H OFAA2H OFAA2H OFAA2H OFAA3H OFAA3H OFAA3H 3 A9 A9 A9 A9 A9 A9 A9 A9 A9 A12 A16 A26 A26 A26 A30 A30 A40 A50 A50 A63 A63 A75 A95 A110 A145 A185 A210 A260 AF400 AF400 AF460 AF580 AF580 AF750 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 30 30 10 10 10 10 10 10 10 10 10 10 Thermal Overload Relay Type Group Current Max setting range Current TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4 TA25DU5 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU19 TA25DU25 TA25DU25 TA25DU32 TA25DU32 TA42DU42 TA75DU52 TA75DU52 TA75DU63 TA75DU63 TA75DU80 TA110DU90 TA110DU110 TA200DU150 TA200DU175 TA450DU235 TA450DU310 E500DU(10) E500DU(10) E500DU(10) E800DU(10) E800DU(10) E800DU(10) [A] - 1.4 1.3 - 1.8 1.7 - 2.4 2.2 - 3.1 2.8 - 3.5 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 13 - 19 18 - 25 18 - 25 24 - 32 24 - 32 29 - 42 36 - 52 36 - 52 45 - 63 45 - 63 60 - 80 65 - 90 80 - 110 110 - 150 130 - 175 165 - 235 220 - 310 150 - 500 150 - 500 150 - 500 250 - 800 250 - 800 250 - 800 max [A] 1.4 1.8 2.4 3.1 6.5 8.5 12 16 19 22 25 30 32 40 44 50 60 63 75 90 110 135 175 210 240 290 400 430 580 580 610 FG4080NS2.1af * : tested with ABB fuses To use such fuses or fuses with similar characteristics Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 29/08/2001 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 80 kA - Normal start - up, type : Note : FM4080NS2.1af aM Fuse type aM Direct-on-line starters with Switch - fuse 400 V, 80 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.37 0.55 0.75 1.1 1.5 Ie [A] 1.2 1.5 2.6 3.5 2.2 5.5 7.5 11 6.6 8.5 11.5 15.5 22 25 30 32 37 40 44 50 60 63 72 75 85 95 105 135 145 165 200 240 280 305 350 400 430 460 520 15 18.5 22 30 37 45 55 75 90 110 132 160 200 250 290 Switch-fuse Type Fuse* type aM OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS63D OS63D OS63D OS63D OS63D OS63D OS125D OS125D OS125D OS125D OS125D OS160D OESA250D OESA250D OESA250D OESA400D OESA400D OESA400D OESA400D OESA630D OESA630D OESA630D OESA630D [A] 2 4 6 10 16 16 20 25 32 32 40 40 50 50 63 63 80 80 100 100 125 160 160 200 200 250 315 315 355 400 500 500 500 630 Contactor Size Type OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM00aM OFAM1aM OFAM1aM OFAM1aM OFAM2aM OFAM2aM OFAM2aM OFAM2aM OFAM3aM OFAM3aM OFAM3aM OFAM3aM A9 A9 A9 A9 A9 A9 A9 A9 A9 A12 A16 A26 A26 A30 A30 A40 A40 A50 A50 A63 A63 A75 A75 A95 A95 A110 A145 A145 A185 A210 A260 A300 A300 AF400 AF400 AF460 AF460 AF580 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 20 30 30 30 10 10 10 10 10 10 10 10 10 10 10 10 Thermal Overload Relay Type Group Current Max setting range Current TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4 TA25DU5 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 TA25DU25 TA25DU32 TA25DU32 TA42DU42 TA42DU42 TA75DU52 TA75DU52 TA75DU63 TA75DU63 TA75DU80 TA75DU80 TA110DU90 TA110DU110 TA110DU110 TA200DU150 TA200DU150 TA200DU175 TA450DU235 TA450DU310 TA450DU310 TA450DU310 E500DU(10) E500DU(10) E500DU(10) E500DU(10) E800DU(10) [A] - 1.4 1.3 - 1.8 1.7 - 2.4 2.2 - 3.1 2.8 - 3.5 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 18 - 25 24 - 32 24 - 32 29 - 42 29 - 42 36 - 52 36 - 52 45 - 63 45 - 63 60 - 80 60 - 80 65 - 90 80 - 110 80 - 110 110 - 150 110 - 150 130 - 175 165 - 235 220 - 310 220 - 310 220 - 310 150 - 500 150 - 500 150 - 500 150 - 500 250 - 800 Imax [A] 1.4 1.8 2.4 3.1 6.5 8.5 12 17 22 25 30 32 37 40 45 50 60 63 72 75 85 95 110 135 145 175 200 250 280 305 350 400 430 460 520 FM4080NS2.1af * : tested with ABB fuses To use such fuses or fuses with similar characteristics Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 29/08/2001 by Jean-Paul Guitton Home Fuse Coordination Table MCCB MMS Softstarters UL Comb MCB Direct-on-line starters protected by INSUM 400 V - 80 kA - Normal start - up, type : Note : FG4080NSIN2.1[INSUM 2] gG, INSUM2 Fuse type gG Direct-on-line starters with Switch - fuse + INSUM 400 V, 80 kA, Normal start - up, type Motor Rated Output Pe [kW] 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 11 15 18.5 Switch-fuse Rated Current Ie [A] 1.1 1.5 1.9 2.8 3.5 5.0 6.6 8.6 11.5 15.2 22 28.5 36 22 30 37 45 55 75 90 110 132 160 200 250 42 56 68 83 98 135 158 193 232 282 349 420 Type Fuse rating gG Contactor Fuse Type and Size Type Safety clearance Thermal Overload Relay Type INSUM MCU1/MCU2 t6 setting max for starter Max Current OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D [A] 10 10 16 16 20 25 OFAA 00 H OFAA 00 H OFAA 00 H OFAA 00 H OFAA 00 H OFAA 00 H OFAA 00 H OFAA 00 H A9 A9 A9 A9 A9 A9 A9 A9 [mm] 15 15 15 15 15 15 15 15 [s] 7 7 7 7 Imax [A] 1.3 1.8 3.4 3.4 6.5 6.5 7.5 OS32D 32 OFAA 00 H A12 15 13 OS32D 32 OFAA 00 H A16 15 15 OS32D 40 OFAA 00 H A26 20 16.5 OS32D 50 OFAA 00 H A26 20 19.5 OS32D OS32D 63 80 OFAA 00 H OFAA 00 H A26 A30 20 20 7 26 32 OS63D 100 OFAA 00 H A40 20 37 OS63D 100 OFAA 00 H A50 20 40 0S125D 125 OFAA 00 H A50 20 50 OS125D 125 OFAA 00 H A63 20 58 OESA250D 160 OFAA H A75 20 66 OESA250D OESA250D OESA250D OESA400D OESA400D OESA400D OESA400D OESA630D OESA630D 160 200 250 315 315 400 400 500 630 OFAA H OFAA H OFAA H OFAA H OFAA H OFAA H OFAA H OFAA H OFAA H A75 A95 A145 A145 A185 A260 A260 EH370 EH370 20 20 10 10 10 10 10 40 40 7 7 7 7 75 90 115 145 168 210 235 290 400 OESA630D 630 OFAA H EH550 40 440 OESA630D 630 OFAA H EH550 40 480 FG4080NSIN2.1 Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB Home Group Fuse MCCB MMS Softstarters UL Comb MCB Direct-on-line starters protected by INSUM 400 V - 80 kA - Normal start - up, type : Note : FM4080NSIN2.1[INSUM 2] aM , INSUM2 Fuse type aM Direct-on-line starters with Switch - fuse + INSUM 400 V, 80 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 11 Ie [A] 1.1 1.5 1.9 2.8 3.5 6.6 8.6 11.5 15.2 22 15 18.5 22 30 37 45 55 75 28.5 36 42 56 68 83 98 135 90 110 132 158 193 232 160 200 282 349 250 420 290 520 Switch-fuse Type OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS32D OS63D OS63D OS63D OS125D OS125D OS125D OS160D OESA250D OESA250D OESA250D OESA400D OESA400D OESA400D OESA630D OESA630D OESA630D OESA630D OESA630D Fuse rating aM [A] 2 4 10 10 16 16 20 25 32 40 50 63 80 100 125 160 160 200 200 250 315 355 400 500 500 500 630 630 Contactor Fuse Type and Size Type OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM 00 aM OFAM aM OFAM aM OFAM aM OFAM aM OFAM aM OFAM aM OFAM aM OFAM aM OFAM aM OFAM aM OFAM aM A9 A9 A9 A9 A9 A9 A9 A9 A12 A16 A26 A26 A30 A40 A50 A63 A75 A95 A145 A145 A145 A185 A210 A260 EH370 EH370 EH370 EH550 EH550 EH550 EH550 Safety clearance Thermal Overload Relay Type INSUM MCU1/MCU2 [mm] 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 10 10 10 10 10 10 40 40 40 40 40 40 40 Group t6 setting max for starter Max Current [s] 7 7 7 7 7 7 7 7 7 7 7 7 7 7 Imax [A] 1.7 1.7 3.2 3.2 4.9 7.2 7.2 12 16 22 26 30 37 50 65 75 96 125 135 145 162 200 245 275 315 400 415 450 500 520 FM4080NSIN2.1 Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 28/01/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 16 kA - Normal start - up, type : Note : MC4016NS1.1 S273 Direct-on-line starters with S 273-K circuit-breaker 400 V, 16 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 11 15 Ie [A] 0.22 0.34 0.44 0.60 0.83 1.12 1.45 1.9 2.6 3.5 4.8 6.5 8.5 11.5 15 22 28.5 Moulded Case CircuitBreaker Type Magnetic tripping current S 273-K1 S 273-K1 S 273-K1 S 273-K1.6 S 273-K1.6 S 273-K2 S 273-K3 S 273-K3 S 273-K4 S 273-K6 S 273-K8 S 283-K10 S 283-K13 S 283-K16 S 283-K20 S 283-K32 S 283-K40 [A] 12 12 12 19.2 19.2 24 36 36 48 72 96 140 182 224 280 448 560 Contactor Type A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 A16 A26 A26 A26 A40 A40 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type Group Current Max setting range Current TA25DU0.25 TA25DU0.40 TA25DU0.63 TA25DU0.63 TA25DU1.0 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4.0 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA42DU25 TA42DU32 [A] 0.16 - 0.25 0.25 - 0.4 0.4 - 0.63 0.4 - 0.63 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 2.8 - 4.5 - 6.5 - 8.5 7.5 - 11 10-14 13-19 18-25 24-32 Imax [A] 0.25 0.4 0.63 1 1.35 1.75 2.35 2.75 3.75 6.25 10.5 13.5 18.5 24 30 MC4016NS1.1 Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 01/02/2000 by Jean-Michel Eymery Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-On-Line Starters 400 V - 16 kA - Normal start - up, type : Note : MC4016NS2.1 S273 Direct-on-line starters with S 273/S283-K circuit-breaker 400 V, 16 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 Ie [A] 0.22 0.34 0.44 0.60 0.83 1.12 1.45 1.9 2.6 3.5 2.2 5.5 7.5 11 15 4.8 6.5 8.5 11.5 15 22 28.5 Miniature Circuit-Breaker Type Magnetic tripping current S 273-K1 S 273-K1 S 273-K1 S 273-K1.6 S 273-K1.6 S 273-K2 S 273-K3 S 273-K3 S 273-K4 S 273-K6 S 273-K8 S 283-K10 S 283-K13 S 283-K16 S 283-K20 S 283-K32 S 283-K40 [A] 12 12 12 19.2 19.2 24 36 36 48 72 96 140 182 224 280 448 560 Contactor Type A9 A9 A9 A9 A9 A9 A9 A12 A16 A26 A26 A26 A30 A30 A30 A40 A40 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type Group Current Max setting range Current TA25DU0.25 TA25DU0.40 TA25DU0.63 TA25DU0.63 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 [A] 0.16 - 0.25 0.25 - 0.4 0.4 - 0.63 0.4 - 0.63 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 Imax [A] 0.25 0.4 0.63 0,63 1.35 1.75 2.35 2.95 TA25DU4 2.8 - 3.75 TA25DU5 3,5 - 4.75 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA42DU25 TA42DU32 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 24 - 32 6.25 10.5 13.5 18.5 24.5 30 MC4016NS2.1 Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB Latest changed 18/02/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 35 kA - Normal start - up, type : Note : MC4035NS1.1 S273 Direct-on-line starters with S 273-K circuit-breaker 400 V, 35 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7,5 11 Ie [A] 0.22 0.34 0.44 0.60 0.83 1.12 1.45 1.9 2.6 3.5 4.8 6.5 8.5 11.5 15 22 Moulded Case CircuitBreaker Type Magnetic tripping current S 273-K1 S 273-K1 S 273-K1 S 273-K1.6 S 273-K1.6 S 273-K2 S 273-K3 S 273-K3 S 273-K4 S 273-K6 S 273-K8 S 283-K10 S 283-K13 S 283-K16 S 283-K20 S 283-K32 [A] 12 12 12 19.2 19.2 24 36 36 48 72 96 140 182 224 280 448 Contactor Type A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 A16 A26 A26 A26 A40 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type Group Current Max setting range Current TA25DU0.25 TA25DU0.4 TA25DU0.63 TA25DU0.63 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA42DU25 [A] 0.16 - 0.25 0.25 - 0.4 0.4 - 0.63 0.4 - 0.63 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 2.8 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 Imax [A] 0.25 0.4 0.63 1 1.35 1.75 2.35 2.75 3.75 6.25 10.5 13.5 18.5 24 MC4035NS1.1 Created 26/11/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 01/02/2000 by Jean-Michel Eymery Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-On-Line Starters 400 V - 35 kA - Normal start - up, type : Note : MC4035NS2.1 S273 Direct-on-line starters with S 273/S283-K circuit-breaker 400 V, 35 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 Ie [A] 0.22 0.34 0.44 0.60 0.83 1.12 1.45 1.9 2.6 3.5 2.2 5.5 7,5 11 4.8 6.5 8.5 11.5 15 22 Miniature Circuit-Breaker Type Magnetic tripping current S 273-K1 S 273-K1 S 273-K1 S 273-K1.6 S 273-K1.6 S 273-K2 S 273-K3 S 273-K3 S 273-K4 S 273-K6 S 273-K8 S 283-K10 S 283-K13 S 283-K16 S 283-K20 S 283-K32 [A] 12 12 12 19.2 19.2 24 36 36 48 72 96 140 182 224 280 448 Contactor Type A9 A9 A9 A9 A9 A9 A9 A16 A26 A26 A26 A26 A30 A30 A30 A40 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type Group Current Max setting range Current TA25DU0.25 TA25DU0.4 TA25DU0.63 TA25DU0.63 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 [A] 0.16 - 0.25 0.25 - 0.4 0.4 - 0.63 0.4 - 0.63 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 Imax [A] 0.25 0.4 0.63 0,63 1.35 1.75 2.35 2.95 TA25DU4 2.8 - 3.75 TA25DU5 3,5 - 4.75 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA42DU25 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 6.25 10.5 13.5 18.5 24 MC4035NS2.1 Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB Latest changed 18/02/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters, heavy duty class 20 400 V - 35 kA - Long starting (heavy duty) start - up, type : Note : MC4035HD2.1 MO325 Direct-on-line starters with MO 325 circuit-breaker, class 20 heavy-duty 400 V, 35 kA, long starting (heavy duty), type2 Motor Rated Output Rated Current Pe [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7,5 Ie [A] 0.22 0.34 0.44 0.72 0.83 1.12 1.45 1.9 2.6 3.5 4.8 6.5 8.5 11.5 15 18.3 Moulded Case CircuitBreaker Type Magnetic tripping current MO325-0.25 MO325-0.4 MO325-0.63 MO325-1 MO325-1 MO325-1.6 MO325-1.6 MO325-2.5 MO325-4 MO325-4 MO325-6.3 MO325-9 MO325-16 MO325-20 MO325-25 S503X-AG0074-32 [A] 2.44 3.9 6.14 11.5 11.5 16 16 27.5 40 40 67.7 112.5 200 250 312.5 352 Contactor Type A9 A9 A9 A9 A9 A9 A9 A9 A9 A12 A12 A26 A26 A26 A26 A30 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 10 Overload relay Type E16DU0.32 (10) E16DU1.0 (10) E16DU1.0 (10) E16DU1.0 (10) E16DU1.0 (10) E16DU2.7 (20) E16DU2.7 (20) E16DU2.7 (20) E16DU6.3 (20) E16DU6.3 (20) E16DU6.3 (20) E16DU18.9 (20) E16DU18.9 (20) E16DU18.9 (20) E16DU18.9 (20) E16DU18.9 (20) Group starter Current Separate Max setting range mounting Current [A] 0.1 - 0.32 0.3 - 0.3 - 0.3 - 0.3 - 0.9 - 2.7 0.9 - 2.7 0.9 - 2.7 - 6.3 - 6.3 - 6.3 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 5.7 - 18.9 AB16 AB16 AB16 AB16 AB16 Imax [A] 0.25 0.4 0.63 0.95 0.95 1.45 1.45 2.2 3.5 3.5 5.4 7.3 10.5 13 16 18.9 MC4035HD2.1 Created 19/08/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 01/02/2000 by Jean-Michel Eymery Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Tmax start (s) 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 Direct-on-line starters 400 V - 50 kA - Normal start - up, type : Note : MC4050NS1.1KM S503KM Miniature Circuit Breaker S503-KM 400 V, 50 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 1.85 2.2 5.5 7.5 11 15 18.5 22 30 Ie [A] 0.44 0.72 0.83 1.2 1.5 2.6 3.5 4.4 6.6 8.5 11.5 15.5 22 30 37 44 60 Manual Motor Starter Contactor Type Magnetic tripping current [A] Type S503-KM 1.6 S503-KM 1.6 S503-KM 1.6 S503-KM 1.6 S503-KM 2.5 S503-KM 2.5 S503-KM 4.0 S503-KM 6.0 S503-KM 6.0 S503-KM 6.0 S503-KM 9.0 S503-KM 20 S503-KM 20 S503-KM 20 S503-KM 32 S503-KM 32 S503-KM 52 S503-KM 63 S503-KM 75 16 16 16 16 25 25 45 55 55 55 100 200 200 200 400 400 580 800 840 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A12-30-10 A16-30-10 A26-30-10 A30-30-10 A40-30-00 A50-30-00 A63-30-00 Safety clearance [mm] 20 20 20 20 20 20 20 20 20 20 20 35 35 35 35 35 35 35 35 Thermal Overload Relay Type TA25DU0.63 TA25DU1 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4 TA25DU5 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 TA25DU32 TA42DU42 TA75DU52 TA75DU63 Group Current Max setting range Current [A] 0.4 - 0.63 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.2 - 3.1 2.8 - 3.5 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 24 - 32 29 - 42 36 - 52 45 - 63 Imax [A] 0.63 1 1.4 1.8 2.4 3.1 8.5 12 16 25 32 40 50 63 MC4050NS1.1KM Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 18/02/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on line starters 400 V - 50 kA - Normal start - up, type : Note : MC4050NS2.1KM S503KM Miniature Circuit Breaker S503-KM 400 V, 50 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 1.85 2.2 5.5 7.5 11 15 18.5 22 30 Ie [A] 0.44 0.72 0.83 1.2 1.5 2.6 3.5 4.4 6.6 8.5 11.5 15.5 22 30 37 44 60 Manual Motor Starter Contactor Type Magnetic tripping current [A] Type S503-KM1.6 S503-KM1.6 S503-KM1.6 S503-KM1.6 S503-KM2.5 S503-KM2.5 S503-KM4 S503-KM6 S503-KM6 S503-KM6 S503-KM9 S503-KM20 S503-KM20 S503-KM20 S503-KM32 S503-KM32 S503-KM52 S503-KM63 S503-KM75 16 16 16 16 25 25 45 55 55 55 100 200 200 200 400 400 580 800 840 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A12-30-10 A12-30-10 A16-30-10 A16-30-10 A16-30-10 A26-30-10 A26-30-10 A26-30-10 A26-30-10 A30-30-10 A40-30-00 A50-30-00 A63-30-00 Safety clearance [mm] 20 20 20 20 20 20 20 20 20 20 20 35 35 35 35 35 35 35 35 Thermal Overload Relay Type TA25DU0.63 TA25DU1 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4 TA25DU5 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 TA25DU32 TA42DU42 TA75DU52 TA75DU63 Group Current Max setting range Current [A] 0.4 - 0.63 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.2 - 3.1 2.8 - 3.5 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 24 - 32 29 - 42 36 - 52 45 - 63 Imax [A] 0.5 0.8 1.4 1.4 2.2 3.1 6.5 8.5 11 14 19 25 32 42 52 63 MC4050NS2.1KM Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 18/02/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 100 kA - Normal start - up, type : Note : MC4000NS1.1 MO325 Direct-on-line starters with MO 325 circuit-breaker 400 V, 100 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 11 Ie [A] 0.22 0.34 0.44 0.72 0.83 1.12 1.45 1.9 2.6 3.5 4.8 6.5 8.5 11.5 15 22 Moulded Case CircuitBreaker Type Magnetic tripping current MO325-0.25 MO325-0.4 MO325-0.63 MO325-1 MO325-1 MO325-1.6 MO325-1.6 MO325-2.5 MO325-2.5 MO325-4.0 MO325-6.3 MO325-9.0 MO325-12.5 MO325-16 MO325-20 MO325-25 [A] 2.44 3.9 6.14 11.5 11.5 16 16 27.5 27.5 40 67.7 112.5 156 200 250 312.5 Contactor Type A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 A12 A16 A26 A26 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type Group Current Max setting range Current TA25DU0.25 TA25DU0.4 TA25DU0.63 TA25DU1 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4.0 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 [A] 0.16 - 0.25 0.25 - 0.4 0.40 - 0.63 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 2.8 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 Imax [A] 0.25 0.4 0.63 1 1.35 1.75 2.35 2.75 3.75 6.25 10.5 13.5 18.5 24 MC4000NS1.1 Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB Latest changed 01/02/2000 by Jean-Michel Eymery Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 400 V - 100 kA - Normal start - up, type : Note : MC4000NS2.1 MO325 Direct-on-line starters with MO 325 circuit-breaker 400 V, 100 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 11 Ie [A] 0.22 0.34 0.44 0.72 0.83 1.12 1.45 1.9 2.6 3.5 4.8 6.5 8.5 11.5 15 22 Moulded Case CircuitBreaker Type Magnetic tripping current MO325-0.25 MO325-0.4 MO325-0.63 MO325-1.0 MO325-1.0 MO325-1.6 MO325-1.6 MO325-2.5 MO325-2.5 MO325-4.0 MO325-6.3 MO325-9.0 MO325-12.5 MO325-16 MO325-20 MO325-25 [A] 2.44 3.9 6.14 11.5 11.5 16 16 27.5 27.5 40 67.7 112.5 156 200 250 312.5 Contactor Type A9 A9 A9 A9 A9 A9 A9 A9 A9 A12 A12 A26 A26 A26 A26 A26 Safety clearance [mm] 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 Thermal Overload Relay Type Group Current Max setting range Current TA25DU0.25 TA25DU0.4 TA25DU0.63 TA25DU1.0 TA25DU1.0 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 [A] 0.16 - 0.25 0.25 - 0.4 0.40 - 0.63 0.63 - 0.63 - 1.0 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 2.8 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 Imax [A 0.25 0.4 0.63 1 1.35 1.75 2.35 2.75 3.75 6.25 10.5 13.5 18.5 24 MC4000NS2.1 Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB Latest changed 01/02/2000 by Jean-Michel Eymery Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB 500 V - 25 kA - Normal start - up, type : Note : MC5025NS1.1 S503KM Miniature Circuit Breaker S503-KM 500 V, 25 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 11 15 18.5 22 30 37 Ie [A] 0.35 0.58 0.68 0.9 1.2 1.5 2.1 2.7 3.8 5.1 6.5 8.9 11.9 17 22.5 28.5 33 44 54 Manual Motor Starter Contactor Type Current setting Magnetic release Type S503-KM 1.6 S503-KM 1.6 S503-KM 1.6 S503-KM 1.6 S503-KM 1.6 S503-KM 2.5 S503-KM 2.5 S503-KM S503-KM S503-KM S503-KM S503-KM 20 S503-KM 20 S503-KM 20 S503-KM 32 S503KM 32 S503-KM 52 S503-KM 63 S503-KM 75 16 16 16 16 16 25 25 45 55 100 100 200 200 200 400 400 580 800 840 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A12-30-10 A16-30-10 A26-30-10 A30-30-10 A40-30-10 A50-30-00 A63-30-00 A95-30-00 Thermal Overload Relay Safety clearance [mm] 20 20 20 20 20 20 20 20 20 35 35 35 35 35 35 35 35 35 35 Type Group Current Max setting range Current TA 25DU0.4 TA 25DU0.93 TA 25DU1 TA 25DU1 TA 25DU1.4 TA 25DU1.8 TA 25DU2.4 TA 25DU3.1 TA 25DU4 TA 25DU6.5 TA 25DU8.5 TA 25DU11 TA 25DU14 TA 25DU19 TA 25DU25 TA 25DU32 TA 75DU42 TA 75DU52 TA 80DU63 [A] 0.25 - 0.4 0.4 - 0.63 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.2 - 3.1 2.8 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 24 - 32 29 - 42 36 - 52 45 - 63 Imax [A] 0.4 0.63 1 1.35 1.75 2.3 2.95 6.25 8.1 10.5 13.5 18.5 24.5 30.5 39 48.5 63 MC5025NS1.1 Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 01/02/2000 by Jean-Michel Eymery Home Fuse Coordination Table MCCB MMS Softstarters UL Comb MCB 500 V - 25 kA - Normal start - up, type : Note : MC5025NS2.1 S503KM Miniature Circuit Breaker S503-KM 500 V, 25 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 5.5 7.5 11 15 18.5 22 30 37 Ie [A] 0.35 0.58 0.68 0.9 1.2 1.5 2.1 2.7 3.8 5.1 6.5 8.9 11.9 17 22.5 28.5 33 44 54 Manual Motor Starter Contactor Type Current setting Magnetic release Type S503-KM1.6 S503-KM1.6 S503-KM1.6 S503-KM1.6 S503-KM1.6 S503-KM2.5 S503-KM2.5 S503-KM4 S503-KM6 S503-KM9 S503-KM9 S503-KM20 S503-KM20 S503-KM20 S503-KM32 S503KM32 S503-KM52 S503-KM63 S503-KM75 16 16 16 16 16 25 25 45 55 100 100 200 200 200 400 400 580 800 840 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A12-30-10 A12-30-10 A16-30-10 A16-30-10 A16-30-10 A16-30-10 A26-30-10 A30-30-10 A40-30-10 A50-30-00 A63-30-00 A95-30-00 Thermal Overload Relay Safety clearance [mm] 20 20 20 20 20 20 20 20 20 35 35 35 35 35 35 35 35 35 35 Type TA25DU0.4 TA25DU0.93 TA25DU1 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 TA25DU32 TA75DU42 TA75DU52 TA80DU63 Group Current Max setting range Current [A] 0.25 - 0.4 0.4 - 0.63 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.2 - 3.1 2.8 - 4.5 - 6.5 - 8.5 7.5 - 11 10 - 14 13 - 19 18 - 25 24 - 32 29 - 42 36 - 52 45 - 63 Imax [A] 0.4 0.63 1 1.35 1.75 2.3 2.95 6.25 8.1 10.5 13.5 18.5 24.5 30.5 39 48.5 63 MC5025NS2.1 Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 01/02/2000 by Jean-Michel Eymery Home Fuse Coordination Table MCCB MMS Softstarters UL Comb MCB Direct-on-line starters 500 V - 100 kA - Normal start - up, type : Note : MC5000NS1.1 MO325 MO 325 circuit-breaker with Prolim current limiter 500 V, 100 kA, Normal start - up, type1 Motor Circuit-Breaker and Current Limitor Rated Output Rated Current Pe [kW] 0.25 0.37 0.55 0.75 1.1 1.5 Ie [A] 0.66 0.88 1.2 1.5 2.1 2.8 2.2 2.5 5.5 7.5 11 15 3.8 4.3 5.2 6.9 9.1 12.2 17.5 22.8 Contactor Type Safety clearance Thermal Overload Relay Group Type Limiter type PROLIM Magnetic tripping current Type Current Max setting range Current MO325-1 MO325-1 MO325-1.6 MO325-1.6 MO325-2.5 - [A] 11.5 11.5 16 16 27.5 A9 A9 A9 A9 A9 [mm] 15 15 15 15 15 TA25DU1 TA25DU1 TA25DU1.4 TA25DU1.8 TA25DU2.4 [A] 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 MO325-4 - 40 A9 15 TA25DU3.1 2.2 - 3.1 Imax [A] 1 1.35 1.75 2.3 2.95 MO325-4 - 40 A9 15 TA25DU4 2.8 - 3.75 MO325-4 MO325-6.3 MO325-6.3 MO325-9 MO325-12.5 - 40 67.7 67.7 112.5 156 A9 A9 A12 A12 A16 15 15 15 15 15 TA25DU5 TA25DU5 TA25DU6.5 TA25DU8.5 TA25DU11 3.5 - 3.5 - 4.5 - 6.5 - 8.5 7.5 - 11 4.2 4.75 6.25 10.5 MO325-12.5 - 156 A26 15 TA25DU14 10 - 14 12.5 MO325-16 PLM 36-B* 200 A26 15 TA25DU14 10 - 14 13.5 MO325-20 MO325-25 PLM 36-B PLM 36-B 250 312.5 A26 A26 15 15 TA25DU19 TA25DU25 13 - 19 18 - 25 18.5 23 * : PLM 36-B only needed for Iq > 100 kA MC5000NS1.1 Created 30/04/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 03/02/2000 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 500 V - 100 kA - Normal start - up, type : Note : MC5000NS2.1 MO325 MO 325 circuit-breaker with Prolim current limiter 500V, 100 kA, Normal start - up, type Motor Circuit-Breaker and Current Limitor Rated Output Rated Current Pe [kW] 0.25 0.37 0.55 0.75 1.1 1.5 Ie [A] 0.66 0.88 1.2 1.5 2.1 2.8 2.2 2.5 5.5 7.5 11 15 3.8 4.3 5.2 6.9 9.1 12.2 17.5 22.8 Contactor Type Safety clearance Thermal Overload Relay Group Type Limiter type PROLIM Magnetic tripping current Type Current Max setting range Current MO325-1 MO325-1 MO325-1.6 MO325-1.6 MO325-2.5 - [A] 11.5 11.5 16 16 27.5 A9 A9 A9 A9 A12 [mm] 15 15 15 15 15 TA 25DU1 TA 25DU1 TA 25DU1.4 TA 25DU1.8 TA 25DU2.4 [A] 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 MO325-4 - 40 A12 15 TA 25DU3.1 2.2 - 3.1 Imax [A] 1 1.35 1.75 2.3 2.95 MO325-4 - 40 A16 15 TA 25DU4 2.8 - 3.75 MO325-4 MO325-6.3 MO325-6.3 MO325-9 MO325-12.5 - 40 67.7 67.7 112.5 156 A26 A26 A26 A26 A26 15 15 15 15 15 TA 25DU5 TA 25DU5 TA 25DU6.5 TA 25DU8.5 TA 25DU11 3.5 - 3.5 - 4.5 - 6.5 - 8.5 7.5 - 11 4.2 4.75 6.25 10.5 MO325-12.5 - 156 A26 15 TA 25DU14 10 - 14 12.5 MO325-16 PLM 36-B* 200 A26 15 TA 25DU14 10 - 14 13.5 MO325-20 MO325-25 PLM 36-B PLM 36-B 250 312.5 A26 A26 15 15 TA 25DU19 TA 25DU25 13 - 19 18 - 25 18.5 23 * : PLM 36-B only needed for Iq > 100 kA MC5000NS2.1 Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB Latest changed 25/02/2000 by Jean-Michel Eymery Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB Direct-on-line starters 690 V - 100 kA - Normal start - up, type : Note : MC6900NS1.1 MO325 MO 325 circuit-breaker with Prolim current limiter 690 V, 100 kA, Normal start - up, type Motor Rated Output Rated Current Pe [kW] 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 1.85 2.2 Ie [A] 0.26 0.42 0.48 0.65 0.84 1.1 1.5 1.99 2.54 2.77 3.74 5.5 7.5 11 4.97 6.41 8.54 12.4 Circuit Breaker and Current Limiter Contactor Type Safety clearance Thermal Overload Relay Group Type Limiter type PROLIM Magnetic tripping current Type Current Max setting range Current MO325-0.40 MO325-0.63 MO325-0.63 MO325-1 MO325-1 MO325-1.6 MO325-1.6 MO325-2.5 MO325-2.5 MO325-4 - [A] 3.9 6.14 6.14 11.5 11.5 18.4 18.4 28.75 28.75 50 A9 A9 A9 A9 A9 A9 A9 A9 A9 A9 [mm] 15 15 15 15 15 15 15 15 15 15 TA 25DU0.40 TA 25DU0.63 TA 25DU0.63 TA 25DU1 TA 25DU1 TA 25DU1.4 TA25DU1.8 TA 25DU2.4 TA 25DU3.1 TA 25DU3.1 [A] 0.25 - 0.40 0.4 - 0.63 0.4 - 0.63 0.63 - 0.63 - 1.0 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 2.3 - 3.1 Imax [A] 0.40 0.63 0.63 1 1.35 1.75 2.35 2.6 MO325-4 - 50 A9 15 TA 25DU4 2.8 - 4.0 3.75 MO325-4 - 50 A9 15 TA 25DU5 3.5 - 5.0 4.5 MO325-6.3 MO325-6.3 PLM 20-C 78.75 78.75 A9 A9 15 15 TA 25DU6.5 TA 25DU8.5 4.5 - 6.5 - 8.5 6.25 6.7 MO325-9 PLM 20-C 135 A12 15 TA 25DU11 7.5 - 11 MO325-12.5 PLM 20-C 187.5 A16 15 TA25DU11 7.5 - 11 10 MO325-12.5 PLM 20-C 187.5 A26 15 TA 25DU14 10 - 14 13.5 MC6900NS1.1 Created 30/04/99 by Jean-Paul Guitton/FRCTL/ABB Latest changed 27/09/2000 by Jean-Paul Guitton Home Fuse Coordination Table MCCB MMS Softstarters UL Comb MCB Direct-on-line starters 690 V - 100 kA - Normal start - up, type : Note : MC6900NS2.1 MO325 MO 325 circuit-breaker with Prolim current limiter 690 V, 100 kA, Normal start - up, type Motor Circuit Breaker and Current Limiter Rated Output Rated Current Pe [kW] 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 1.85 2.2 Ie [A] 0.26 0.42 0.48 0.65 0.84 1.1 1.5 1.99 2.54 2.77 3.74 5.5 7.5 11 4.97 6.41 8.54 12.4 Contactor Type Safety clearance Thermal Overload Relay Group Type Limiter type PROLIM Magnetic tripping current Type Current Max setting range Current MO325-0.40 MO325-0.63 MO325-0.63 MO325-1 MO325-1 MO325-1.6 MO325-1.6 MO325-2.5 MO325-2.5 MO325-4 - [A] 3.9 6.14 6.14 11.5 11.5 18.75 18.75 28.75 28.75 50 A9 A9 A9 A9 A9 A9 A9 A9 A12 A12 [mm] 15 15 15 15 15 15 15 15 15 15 TA 25DU0.40 TA 25DU0.63 TA 25DU0.63 TA 25DU1 TA 25DU1 TA 25DU1.4 TA25DU1.8 TA 25DU2.4 TA 25DU3.1 TA 25DU3.1 [A] 0.25 - 0.40 0.4 - 0.63 0.4 - 0.63 0.63 - 0.63 - 1 - 1.4 1.3 - 1.8 1.7 - 2.4 2.3 - 3.1 2.3 - 3.1 Imax [A] 0.40 0.63 0.63 1 1.35 1.75 2.35 2.6 MO325-4 - 50 A12 15 TA 25DU4 2.8 - 3.75 MO325-4 - 50 A26 15 TA 25DU5 3.5 - 4.75 MO325-6.3 MO325-6.3 PLM 20-C 78.75 78.75 A26 A26 15 15 TA 25DU6.5 TA 25DU8.5 4.5 - 6.5 - 8.5 6.25 8.0 MO325-9 PLM 20-C 135 A26 15 TA 25DU11 7.5 - 11 MO325-12.5 PLM 20-C 187.5 A26 15 TA25DU11 7.5 - 11 10.5 MO325-12.5 PLM 20-C 187.5 A26 15 TA 25DU14 10 - 14 13.5 MC6900NS2.1 Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB Latest changed 06/07/2001 by Jean-Paul Guitton Home Fuse MCCB Coordination Table MMS Softstarters UL Comb MCB ... Type OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA1H OFAA1H OFAA1H OFAA1H OFAA1H OFAA2H OFAA2H OFAA2H... Contactor Size Type OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H... Contactor Size Type OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA00H OFAA1H OFAA1H OFAA1H