— RELION® 615 SERIES Motor Protection and Control REM615 Product Guide Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N Contents Description 17 Inputs and outputs 16 Standard configuration 18 Station communication 17 Protection functions 19 Technical data 22 Application 20 Local HMI 47 Supported ABB solutions 11 21 Mounting methods 48 Control 13 22 Relay case and plug-in unit 48 Measurement 14 23 Selection and ordering data .48 Disturbance recorder 14 24 Accessories and ordering data 49 Event log 14 25 Tools 50 10 Recorded data 14 26 Cyber security 51 11 Condition monitoring 15 27 Terminal diagrams .52 12 Trip-circuit supervision .15 28 Certificates 55 13 Self-supervision 15 29 References 55 14 Fuse failure supervision 16 30 Functions, codes and symbols 56 15 Current circuit supervision 16 31 Document revision history 59 16 Access control 16 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB ABB assumes no responsibility for any errors that may appear in this document © Copyright 2018 ABB All rights reserved Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders ABB Motor Protection and Control REM615 Product version: 5.0 FP1 Description REM615 is a dedicated motor protection and control relay designed for the protection, control, measurement and supervision of asynchronous motors in manufacturing and process industry REM615 is a member of ABB’s Relion ® product family and part of its 615 protection and control product series The 615 series relays are characterized by their compactness and withdrawable-unit design Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between substation automation devices Once the standard configuration relay has been given the application-specific settings, it can directly be put into service The 615 series relays support a range of communication protocols including IEC 61850 with Edition support, process bus according to IEC 61850-9-2 LE, IEC 60870-5-103, Modbus ® and DNP3 Profibus DPV1 communication protocol is supported by using the protocol converter SPA-ZC 302 ABB 1MRS756890 N Issued: 2018-12-20 Revision: N Standard configuration REM615 is available with four alternative standard configurations The standard signal configuration can be altered by means of the graphical signal matrix or the graphical application functionality of the Protection and Control IED Manager PCM600 Further, the application configuration functionality of the relay supports the creation of multi-layer logic functions using various logical elements including timers and flip-flops By combining protection functions with logic function blocks, the relay configuration can be adapted to userspecific application requirements The relay is delivered from the factory with default connections described in the functional diagrams for binary inputs, binary outputs, function-to-function connections and alarm LEDs Some of the supported functions in REM615 must be added with the Application Configuration tool to be available in the Signal Matrix tool and in the relay The positive measuring direction of directional protection functions is towards the outgoing feeder Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N REM615 MOTOR PROTECTION AND CONTROL RELAY PROTECTION 2× STANDARD CONFIGURATION LOCAL HMI Master Trip Lockout relay 94/86 3× ALSO AVAILABLE Master Trip Lockout relay 94/86 Configuration System HMI Time Authorization I - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR A ESC Clear A O R L U12 0 kV P 0.00 kW Q 0.00 kVAr 3I 3I< 37 2× IL2 A I2>M 46M I2>> 46R I ESC Clear O 3× Is2t n< 49, 66, 48, 51LR 3Ith>M 49M ARC 50L/50NL 3I>>> 50P/51P 3I>/Io>BF 51BF/51NBF Ist> 51LR 3× 3I> 51P-1 3I>> 51P-2 Io R L CONDITION MONITORING AND SUPERVISION CBCM CBCM 2× A MCS 3I MCS 3I COMMUNICATION Protocols: IEC 61850-8-1 Modbus® IEC 60870-5-103 DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP OPTS OPTM TCS TCM Io CONTROL AND INDICATION 1) Io Io> 51N-1 Io>> 51N-2 Object Ctrl 2) Ind MEASUREMENT CB - DC ES 1) 2) 3) - I, Io - Limit value supervision - Load profile record - RTD/mA measurement (optional) - Symmetrical components 3) Check availability of binary inputs/outputs from technical documentation Control and indication function for primary object Status indication function for primary object Analog interface types 1) Current transformer Voltage transformer - 1) Conventional transformer inputs ESTART ESTART REMARKS 18× MAP MAP 6xRTD 2xmA Optional function Calculated value 3× No of instances Io/Uo OR Alternative function to be defined when ordering GUID-4A93E0BB-46C2-4A06-BC4F-50C42B51366F V2 EN Figure Functionality overview for standard configuration A ABB UL1UL2UL3 Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N REM615 MOTOR PROTECTION AND CONTROL RELAY PROTECTION 2× STANDARD CONFIGURATION LOCAL HMI Master Trip Lockout relay 94/86 3× ALSO AVAILABLE Master Trip Lockout relay 94/86 Configuration System HMI Time Authorization I - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR A ESC Clear A O R L U12 0 kV P 0.00 kW Q 0.00 kVAr 3I 2× 3I< 37 IL2 A I2>M 46M I2>> 46R I ESC Clear O 3× Is2t n< 49, 66, 48, 51LR 3Ith>M 49M ARC 50L/50NL 3I>>> 50P/51P 3I>/Io>BF 51BF/51NBF Ist> 51LR 3I> 51P-1 R L FUSEF 60 OPTS OPTM 3I>> 51P-2 CBCM CBCM 2× MCS 3I MCS 3I TCS TCM Io Io>> 51N-2 CONTROL AND INDICATION 1) Io Object Io>→ 67N-1 Uo 2× f>/f 47O- Ctrl 2) CB 1) 3U< 27 Protocols: IEC 61850-8-1/-9-2LE Modbus® IEC 60870-5-103 DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP Io 3I Io UL1UL2UL3 COMMUNICATION CONDITION MONITORING AND SUPERVISION 3× B Analog interface types Check availability of binary inputs/outputs from technical documentation Control and indication function for primary object Status indication function for primary object 1) Current transformer Voltage transformer 1) Conventional transformer inputs ESTART ESTART REMARKS 18× MAP MAP 6xRTD 2xmA Optional function Calculated value 3× No of instances Io/Uo OR Alternative function to be defined when ordering GUID-521A1FAA-FF73-4988-BA61-33AA451F33E0 V2 EN Figure ABB Functionality overview for standard configuration B UL1UL2UL3 Uo Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N REM615 MOTOR PROTECTION AND CONTROL RELAY PROTECTION 2× STANDARD CONFIGURATION LOCAL HMI Master Trip Lockout relay 94/86 3× ALSO AVAILABLE Master Trip Lockout relay 94/86 Configuration System HMI Time Authorization I - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR A ESC Clear A O 2× 3I< 37 IL2 A I2>M 46M I2>> 46R I ESC Clear O 3× R L U12 0 kV P 0.00 kW Q 0.00 kVAr 3I Is2t n< 49, 66, 48, 51LR 3Ith>M 49M ARC 50L/50NL 3I>>> 50P/51P 3I>/Io>BF 51BF/51NBF Ist> 51LR 3I> 51P-1 R L 3I FUSEF 60 OPTS OPTM 3I>> 51P-2 CBCM CBCM 2× MCS 3I MCS 3I TCS TCM Io Io>> 51N-2 CONTROL AND INDICATION 1) Io Object Io>→ 67N-1 U1< 47U+ 2× f>/f 47O- Ind MEASUREMENT - DC ES 3) - I, U, Io, Uo, P, Q, E, pf, f - Limit value supervision - Load profile record - Symmetrical components 3) 2) 3U< 27 Ctrl 2) CB 1) UL1UL2UL3 Protocols: IEC 61850-8-1/-9-2LE Modbus® IEC 60870-5-103 DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP Io Io Uo COMMUNICATION CONDITION MONITORING AND SUPERVISION 3× C Check availability of binary inputs/outputs from technical documentation Control and indication function for primary object Status indication function for primary object Analog interface types 1) Current transformer Voltage transformer 2) Conventional transformer inputs 2) One of the five inputs is reserved for future applications 1) ESTART ESTART REMARKS 18× MAP MAP Optional function Calculated value 3× No of instances Io/Uo OR Alternative function to be defined when ordering GUID-C6EEADA8-8AB0-4BE0-8D58-97351C7B0D07 V2 EN Figure Functionality overview for standard configuration C ABB UL1UL2UL3 Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N REM615 MOTOR PROTECTION AND CONTROL RELAY PROTECTION 2× LOCAL HMI Master Trip Lockout relay 94/86 3× ALSO AVAILABLE Master Trip Lockout relay 94/86 Configuration System HMI Time Authorization I - Disturbance and fault recorders - Event log and recorded data - High-Speed Output module (optional) - Local/Remote push button on LHMI - Self-supervision - Time synchronization: IEEE 1588 v2, SNTP, IRIG-B - User management - Web HMI AND OR A ESC Clear A O 2× 3I< 37 IL2 A I2>M 46M I2>> 46R I ESC Clear O 3× R L U12 0 kV P 0.00 kW Q 0.00 kVAr 3I Is2t n< 49, 66, 48, 51LR 3Ith>M 49M ARC 50L/50NL 3I>>> 50P/51P 3I>/Io>BF 51BF/51NBF Ist> 51LR 3I> 51P-1 R L 3I Protocols: IEC 61850-8-1/-9-2LE Modbus® IEC 60870-5-103 DNP3 Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass fiber (ST), RS-485, RS-232 Redundant protocols: HSR PRP RSTP Io FUSEF 60 OPTS OPTM 3I>> 51P-2 CBCM CBCM 2× MCS 3I MCS 3I TCS TCM Io Io Io>> 51N-2 CONTROL AND INDICATION 1) Io Object Io>→ 67N-1 Uo U1< 47U+ f>/f 47O- Ind MEASUREMENT - DC ES 3) - I, U, Io, P, Q, E, pf, f - Limit value supervision - Load profile record - Symmetrical components 3) 2) 2× Ctrl 2) CB 1) 3U< 27 COMMUNICATION CONDITION MONITORING AND SUPERVISION 3× D STANDARD CONFIGURATION Check availability of binary inputs/outputs from technical documentation Control and indication function for primary object Status indication function for primary object Analog interface types 1) Current sensor Voltage sensor Voltage transformer 1) ESTART ESTART Combi sensor inputs with conventional Io input REMARKS 18× MAP MAP Optional function Calculated value 3× No of instances Io/Uo OR Alternative function to be defined when ordering GUID-13051FBE-3F18-43EF-9309-7DE749EDA262 V2 EN Figure Functionality overview for standard configuration D Table Standard configuration Description Std.conf Basic motor protection (RTD option) A Motor protection with voltage and frequency based protection and measurements (RTD option) B Motor protection with voltage and frequency based protection and measurements C Motor protection with voltage and frequency based protection and measurements (sensor inputs) D ABB Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N Table Supported functions Function IEC 61850 A B C D Three-phase non-directional overcurrent protection, low stage PHLPTOC 1 1 Three-phase non-directional overcurrent protection, high stage PHHPTOC 1 1 Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 1 1 Non-directional earth-fault protection, low stage EFLPTOC Non-directional earth-fault protection, high stage EFHPTOC 1 1 Directional earth-fault protection, low stage DEFLPDEF 11) 11) Three-phase undervoltage protection PHPTUV 1 Positive-sequence undervoltage protection PSPTUV 1 Negative-sequence overvoltage protection NSPTOV 1 Frequency protection FRPFRQ 2 Negative-sequence overcurrent protection for machines MNSPTOC 2 2 Loss of load supervision LOFLPTUC 1 1 Motor load jam protection JAMPTOC 1 1 Motor start-up supervision STTPMSU 1 1 Phase reversal protection PREVPTOC 1 1 Thermal overload protection for motors MPTTR 1 1 Circuit breaker failure protection CCBRBRF 1 1 Master trip TRPPTRC (3) 2) (3) 2) (3) 2) (3) 2) Arc protection ARCSARC (3) (3) (3) (3) Multipurpose protection MAPGAPC 18 18 18 18 Circuit-breaker control CBXCBR 1 1 Disconnector control DCXSWI 2 2 Earthing switch control ESXSWI 1 1 Disconnector position indication DCSXSWI 3 3 Earthing switch indication ESSXSWI 2 2 Emergency start-up ESMGAPC 1 1 Circuit-breaker condition monitoring SSCBR 1 1 Trip circuit supervision TCSSCBR 2 2 Current circuit supervision CCSPVC 1 1 Fuse failure supervision SEQSPVC 1 Runtime counter for machines and devices MDSOPT 1 1 Disturbance recorder RDRE 1 1 Load profile record LDPRLRC 1 1 Fault record FLTRFRC 1 1 Three-phase current measurement CMMXU 1 1 Sequence current measurement CSMSQI 1 1 Residual current measurement RESCMMXU 1 1 Three-phase voltage measurement VMMXU 1 Residual voltage measurement RESVMMXU Sequence voltage measurement VSMSQI 1 Three-phase power and energy measurement PEMMXU 1 RTD/mA measurement XRGGIO130 Protection Control Condition monitoring and supervision Measurement (1) (1) Frequency measurement FMMXU1 1 IEC 61850-9-2 LE sampled value sending 3)4) SMVSENDER (1) (1) (1) IEC 61850-9-2 LE sampled value receiving (voltage sharing) 3)4) SMVRCV (1) (1) (1) Other Minimum pulse timer (2 pcs) TPGAPC 4 4 Minimum pulse timer (2 pcs, second resolution) TPSGAPC 1 1 Minimum pulse timer (2 pcs, minute resolution) TPMGAPC 1 1 ABB Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N Table Supported functions, continued Function IEC 61850 A B C D Pulse timer (8 pcs) PTGAPC 2 2 Time delay off (8 pcs) TOFGAPC 4 4 Time delay on (8 pcs) TONGAPC 4 4 Set-reset (8 pcs) SRGAPC 4 4 Move (8 pcs) MVGAPC 2 2 Generic control point (16 pcs) SPCGAPC 2 2 Analog value scaling (4 pcs) SCA4GAPC 4 4 Integer value move (4 pcs) MVI4GAPC 1 1 1, 2, = Number of included instances The instances of a protection function represent the number of identical protection function blocks available in the standard configuration () = optional 1) 2) 3) 4) "Uo calculated" is always used Master trip is included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used If additionally the ARC option is selected, ARCSARC is connected in the configuration to the corresponding master trip input Available only with IEC 61850-9-2 Available only with COM0031-0037 Protection functions The relay offers all the functionality needed to manage motor start-ups and normal operation, also including protection and fault clearance in abnormal situations The main features of the relay include thermal overload protection, motor start-up supervision, locked rotor protection and protection against too frequent motor start-ups The relay also incorporates nondirectional earth-fault protection, negative phase-sequence current unbalance protection and backup overcurrent protection Furthermore, the relay offers motor running stall protection, loss-of-load supervision and phase reversal protection Standard configurations B, C and D additionally offer directional earth-fault protection, three-phase undervoltage protection, negative-sequence overvoltage and positive-sequence undervoltage protection Further, the B, C and D configurations offer frequency protection including overfrequency, underfrequency and rate-of-change frequency protection modes The RTD/mA module offered as an option for standard configurations A and B enables the use of the optional multipurpose protection function for tripping and alarm purposes using RTD/mA measuring data or analog values via GOOSE messages In certain motor drives of special importance there must be a possibility to override the motor thermal overload protection to perform an emergency start of a hot motor To enable an emergency hot start, REM615 offers a forced start execution feature Enhanced with optional hardware and software, the relay also features three light detection channels for arc fault protection of the circuit breaker, busbar and cable compartment of metalenclosed indoor switchgear ABB The arc-fault protection sensor interface is available on the optional communication module Fast tripping increases staff safety and security and limits material damage in an arc fault situation A binary input and output module can be selected as an option - having three high speed binary outputs (HSO) it further decreases the total operate time with typically ms compared to the normal power outputs Application REM615 constitutes main protection for asynchronous motors and the associated drives Typically, the motor relay is used with circuit breaker or contactor controlled HV motors, and contactor controlled medium sized and large LV motors in a variety of drives, such as pumps and conveyors, crushers and choppers, mixers and agitators, fans and aerators The motor relay is thoroughly adapted for earth-fault protection Using cable current transformers sensitive and reliable earthfault protection can be achieved Phase current transformers in Holmgreen (summation) connection can also be used for earthfault protection In that case possible unwanted operations of the earth-fault protection at motor start-up due to CT saturation can be prevented using the relay's internal interlocking features or a suitable stabilizing resistor in the common neutral return The optional RTD/mA module offered for standard configurations A and B facilitates the measurement of up to eight analog signals via the six RTD inputs or the two mA inputs using transducers The RTD and mA inputs can be used for temperature monitoring of motor bearings and stator windings, thus expanding the functionality of the thermal overload protection and preventing premature aging of the motor Furthermore, the RTD/mA inputs can be used for measuring the ambient cooling air temperature The analog temperature values can, if required, be sent to other devices using analog horizontal GOOSE messaging Temperature values can also be Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N received from other devices over the station bus, thus increasing the extent of relevant information The standard configuration D includes one conventional residual current (Io) input and three combi-sensor inputs for phase currents and phase voltages The connection of the three combi-sensors is made with RJ-45 type of connectors Sensors offer certain benefits compared to conventional current and voltage instrument transformers, for example, current sensors not saturate at high currents, they consume less energy and they weigh less In voltage sensors the risk of ferro-resonance is eliminated The sensor inputs also enable the use of the relay in compact medium voltage switchgears, such as ABB’s UniGear Digital, SafeRing and SafePlus, with limited space for conventional measuring transformers, thus requiring the use of sensor technology Further, the adapters also enable the use of sensors with Twin-BNC connectors REF615 Std conf Io 3I C/D ANSI IEC 46 I2> 50L/50NL ARC 50P/51P 3I>>> 50N/51N-1/51N-2 Io>>>/Io>>/Io> 51BF/51NBF 3I>/Io>BF 68 3I2f> 3I 3I 3U Io Uo Io RTD RTD REM615 REU615 REM615 Std conf Std conf B A Std conf A ANSI IEC U2>/3U> 37 3I< U1> 50L/50NL ARC 49,66,48,51LR Is2t n< U1 49M 3Ith>M 49,66,48,51LR Is2t n< 81 f,df/dt 50L/50NL ARC 49M 3Ith>M 81LSH UFLS/R 51N-1/51N-2 Io>>/Io> 50L/50NL ARC 50P/51P 3I>>> 51N-2/67N-1 Io>>/Io> -> 51LR Ist> 50P/51P 3I>>> 51P/51N 3I/Io 51LR Ist> 51P/51N 3I/Io ANSI IEC ANSI 37 3I< 47O-/59 46R I2>> 47U+/27 47O-/59 U2>/3U> 47U+/27 IEC 1) 1) 1) Light detection only GUID-52860380-D410-4969-A44E-7C7311221D0F V5 EN Figure Motor protection and control of contactor and circuit breaker controlled motors using standard configurations A and B Figure illustrates an example of motor protection and control of contactor and circuit breaker controlled motors using standard configurations A and B To prevent possible power system instability due to busbar voltage collapse, the 10 simultaneous starting of several motors can be inhibited with the "restart inhibit" input of REM615 The optional RTD/mA inputs are utilized for motor winding and bearing temperature supervision ABB Motor Protection and Control REM615 Product version: 5.0 FP1 25 Tools The protection relay is delivered as a preconfigured unit The default parameter setting values can be changed from the frontpanel user interface (local HMI), the Web browser-based user interface (Web HMI) or Protection and Control IED Manager PCM600 in combination with the relay-specific connectivity package PCM600 offers extensive relay configuration functions For example, depending on the protection relay, the relay signals, application, graphical display and single-line diagram, and IEC 61850 communication, including horizontal GOOSE communication, can be modified with PCM600 When the Web HMI is used, the protection relay can be accessed either locally or remotely using a Web browser 1MRS756890 N (Internet Explorer) For security reasons, the Web HMI is disabled by default but it can be enabled via the local HMI The Web HMI functionality can be limited to read-only access The relay connectivity package is a collection of software and specific relay information, which enables system products and tools to connect and interact with the protection relay The connectivity packages reduce the risk of errors in system integration, minimizing device configuration and setup times Further, the connectivity packages for protection relays of this product series include a flexible update tool for adding one additional local HMI language to the protection relay The update tool is activated using PCM600, and it enables multiple updates of the additional HMI language, thus offering flexible means for possible future language updates Table 85 Tools Description Version PCM600 2.6 (Rollup 20150626) or later Web browser IE 8.0, IE 9.0, IE 10.0 or IE 11.0 REM615 Connectivity Package 5.1 or later 50 ABB Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N Table 86 Supported functions Function Web HMI PCM600 Relay parameter setting ● ● Saving of relay parameter settings in the relay ● ● Signal monitoring ● ● Disturbance recorder handling ● ● Alarm LED viewing ● ● Access control management ● ● Relay signal configuration (Signal Matrix) - ● Modbus® communication configuration (communication management) - ● DNP3 communication configuration (communication management) - ● IEC 60870-5-103 communication configuration (communication management) - ● Saving of relay parameter settings in the tool - ● Disturbance record analysis - ● XRIO parameter export/import ● ● Graphical display configuration - ● Application configuration - ● IEC 61850 communication configuration, GOOSE (communication configuration) - ● Phasor diagram viewing ● - Event viewing ● ● Saving of event data on the user's PC ● ● Online monitoring - ● ● = Supported 26 Cyber security The relay supports role based user authentication and authorization It can store 2048 audit trail events to a nonvolatile memory The non-volatile memory is based on a memory type which does not need battery backup or regular component exchange to maintain the memory storage FTP ABB and Web HMI use TLS encryption with a minimum of 128 bit key length protecting the data in transit In this case the used communication protocols are FTPS and HTTPS All rear communication ports and optional protocol services can be deactivated according to the required system setup 51 Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N 27 Terminal diagrams GUID-B2057B3C-DDFD-4A85-98AF-9E14D947439D V1 EN Figure 17 52 Terminal diagram of standard configuration A ABB Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N GUID-FB8CC4CD-F5ED-4FE5-837D-B39CB06ED67C V1 EN Figure 18 ABB Terminal diagram of standard configuration B 53 Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N GUID-1589F909-AB4D-44A7-9445-057B7385AFD7 V2 EN Figure 19 54 Terminal diagram of standard configuration C ABB Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N REM615 X100 X130 0,2/1A N + U aux Io - IRF X131 IL1 U1 PO2 IL2 10 U2 SO1 X133 PO1 X132 11 12 13 IL3 SO2 U3 PO3 TCS1 14 16 17 15 19 18 20 22 PO4 TCS2 10 11 12 13 24 X110 X110 21 23 14 BI SO1 16 15 17 BI SO2 BI 19 18 20 BI SO3 22 21 23 BI SO4 24 BI BI BI X13 Light sensor input X14 Light sensor input X15 Light sensor input 1) 1) 1) 1) Optional 2) The IED features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached GUID-6C78FB07-4F88-4810-B265-F78B98C9F584 V1 EN Figure 20 Terminal diagram of standard configuration D 28 Certificates DNV GL has issued an IEC 61850 Edition Certificate Level A1 for Relion® 615 series Certificate number: 7410570I-OPE/INC 15-1136 DNV GL has issued an IEC 61850 Edition Certificate Level A1 Relion ® for 615 series Certificate number: 74105701-OPE/INC 15-1145 29 References The www.abb.com/substationautomation portal provides information on the entire range of distribution automation products and services The latest relevant information on the REM615 protection and control relay is found on the product page Scroll down the page to find and download the related documentation Additional certificates can be found on the product page ABB 55 Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N 30 Functions, codes and symbols Table 87 Functions included in the relay Function IEC 61850 IEC 60617 IEC-ANSI Three-phase non-directional overcurrent protection, low stage PHLPTOC1 3I> (1) 51P-1 (1) Three-phase non-directional overcurrent protection, high stage PHHPTOC1 3I>> (1) 51P-2 (1) Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC1 3I>>> (1) 50P/51P (1) Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1) Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1) Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1) Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1) Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U+ (1) Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1) Frequency protection FRPFRQ1 f>/f/fM (1) 46M (1) MNSPTOC2 I2>M (2) 46M (2) Loss of load supervision LOFLPTUC1 3I< (1) 37 (1) Motor load jam protection JAMPTOC1 Ist> (1) 51LR (1) Motor start-up supervision STTPMSU1 Is2t n< (1) 49,66,48,51LR (1) Phase reversal protection PREVPTOC1 I2>> (1) 46R (1) Thermal overload protection for motors MPTTR1 3Ith>M (1) 49M (1) Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1) Master trip TRPPTRC1 Master Trip (1) 94/86 (1) TRPPTRC2 Master Trip (2) 94/86 (2) TRPPTRC3 Master Trip (3) 94/86 (3) TRPPTRC4 Master Trip (4) 94/86 (4) TRPPTRC5 Master Trip (5) 94/86 (5) ARCSARC1 ARC (1) 50L/50NL (1) ARCSARC2 ARC (2) 50L/50NL (2) ARCSARC3 ARC (3) 50L/50NL (3) Protection Arc protection 56 ABB Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N Table 87 Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Multipurpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3) MAPGAPC4 MAP (4) MAP (4) MAPGAPC5 MAP (5) MAP (5) MAPGAPC6 MAP (6) MAP (6) MAPGAPC7 MAP (7) MAP (7) MAPGAPC8 MAP (8) MAP (8) MAPGAPC9 MAP (9) MAP (9) MAPGAPC10 MAP (10) MAP (10) MAPGAPC11 MAP (11) MAP (11) MAPGAPC12 MAP (12) MAP (12) MAPGAPC13 MAP (13) MAP (13) MAPGAPC14 MAP (14) MAP (14) MAPGAPC15 MAP (15) MAP (15) MAPGAPC16 MAP (16) MAP (16) MAPGAPC17 MAP (17) MAP (17) MAPGAPC18 MAP (18) MAP (18) Circuit-breaker control CBXCBR1 I O CB (1) I O CB (1) Disconnector control DCXSWI1 I O DCC (1) I O DCC (1) DCXSWI2 I O DCC (2) I O DCC (2) Earthing switch control ESXSWI1 I O ESC (1) I O ESC (1) Disconnector position indication DCSXSWI1 I O DC (1) I O DC (1) DCSXSWI2 I O DC (2) I O DC (2) DCSXSWI3 I O DC (3) I O DC (3) ESSXSWI1 I O ES (1) I O ES (1) ESSXSWI2 I O ES (2) I O ES (2) ESMGAPC1 ESTART (1) ESTART (1) Circuit-breaker condition monitoring SSCBR1 CBCM (1) CBCM (1) Trip circuit supervision TCSSCBR1 TCS (1) TCM (1) TCSSCBR2 TCS (2) TCM (2) Current circuit supervision CCSPVC1 MCS 3I (1) MCS 3I (1) Fuse failure supervision SEQSPVC1 FUSEF (1) 60 (1) Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM (1) RDRE1 DR (1) DFR (1) Control Earthing switch indication Emergency start-up Condition monitoring and supervision Measurement Disturbance recorder ABB 57 Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N Table 87 Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Load profile record LDPRLRC1 LOADPROF (1) LOADPROF (1) Fault record FLTRFRC1 FAULTREC (1) FAULTREC (1) Three-phase current measurement CMMXU1 3I (1) 3I (1) Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1) Residual current measurement RESCMMXU1 Io (1) In (1) Three-phase voltage measurement VMMXU1 3U (1) 3V (1) Residual voltage measurement RESVMMXU1 Uo (1) Vn (1) Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1) Three-phase power and energy measurement PEMMXU1 P, E (1) P, E (1) RTD/mA measurement XRGGIO130 X130 (RTD) (1) X130 (RTD) (1) Frequency measurement FMMXU1 f (1) f (1) IEC 61850-9-2 LE sampled value sending SMVSENDER SMVSENDER SMVSENDER IEC 61850-9-2 LE sampled value receiving (voltage sharing) SMVRCV SMVRCV SMVRCV TPGAPC1 TP (1) TP (1) TPGAPC2 TP (2) TP (2) TPGAPC3 TP (3) TP (3) TPGAPC4 TP (4) TP (4) Minimum pulse timer (2 pcs, second resolution) TPSGAPC1 TPS (1) TPS (1) Minimum pulse timer (2 pcs, minute resolution) TPMGAPC1 TPM (1) TPM (1) Pulse timer (8 pcs) PTGAPC1 PT (1) PT (1) PTGAPC2 PT (2) PT (2) TOFGAPC1 TOF (1) TOF (1) TOFGAPC2 TOF (2) TOF (2) TOFGAPC3 TOF (3) TOF (3) TOFGAPC4 TOF (4) TOF (4) TONGAPC1 TON (1) TON (1) TONGAPC2 TON (2) TON (2) TONGAPC3 TON (3) TON (3) TONGAPC4 TON (4) TON (4) SRGAPC1 SR (1) SR (1) SRGAPC2 SR (2) SR (2) SRGAPC3 SR (3) SR (3) SRGAPC4 SR (4) SR (4) MVGAPC1 MV (1) MV (1) MVGAPC2 MV (2) MV (2) Other Minimum pulse timer (2 pcs) Time delay off (8 pcs) Time delay on (8 pcs) Set-reset (8 pcs) Move (8 pcs) 58 ABB Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N Table 87 Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Generic control point (16 pcs) SPCGAPC1 SPC (1) SPC (1) SPCGAPC2 SPC (2) SPC (2) SCA4GAPC1 SCA4 (1) SCA4 (1) SCA4GAPC2 SCA4 (2) SCA4 (2) SCA4GAPC3 SCA4 (3) SCA4 (3) SCA4GAPC4 SCA4 (4) SCA4 (4) MVI4GAPC1 MVI4 (1) MVI4 (1) Analog value scaling Integer value move 31 Document revision history Document revision/date Product version History A/2009-07-03 2.0 First release B/2009-10-01 2.0 Content updated C/2010-06-11 3.0 Content updated to correspond to the product version D/2010-06-29 3.0 Terminology updated E/2010-09-07 3.0 Content updated F/2012-05-11 4.0 Content updated to correspond to the product version G/2013-02-21 4.0 FP1 Content updated to correspond to the product version H/2014-01-24 5.0 Content updated to correspond to the product version K/2014-09-04 5.0 Content updated L/2015-10-30 5.0 FP1 Content updated to correspond to the product version M/2016-05-20 5.0 FP1 Content updated N/2018-12-20 5.0 FP1 Content updated ABB 59 60 — ABB Distribution Solutions Distribution Automation P.O Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 ABB Distribution Automation Maneja Works Vadodara-390013, India Phone +91 265 2604386 Fax +91 265 2638922 © Copyright 2018 ABB All rights reserved 1MRS756890 N www.abb.com/mediumvoltage www.abb.com/relion www.abb.com/substationautomation ... overview for standard configuration A ABB UL1UL2UL3 Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N REM615 MOTOR PROTECTION AND CONTROL RELAY PROTECTION 2× STANDARD CONFIGURATION... Figure Motor protection and control of contactor and circuit breaker controlled motors using standard configuration D Example of motor protection and control of contactor and circuit breaker controlled... Figure ABB Functionality overview for standard configuration B UL1UL2UL3 Uo Motor Protection and Control REM615 Product version: 5.0 FP1 1MRS756890 N REM615 MOTOR PROTECTION AND CONTROL RELAY PROTECTION