This section is concerned with the design and operation of pressure relieving systems for gas processing plants. The princi pal elements of pressure relief systems are the individual pres sure relief devices, the flare piping system, the flare separator drum, and the flare — including igniters, tips, sealing devices, purge and steam injection for smokeless burning. Application of relief devices must comply with appropriate ASME Vessel Codes. Design of relief systems must also comply with applica ble state and federal codes and laws as well as the requirements
Trang 1This section is concerned with the design and operation of
pressure relieving systems for gas processing plants The
princi-pal elements of pressure relief systems are the individual
pres-sure relief devices, the flare piping system, the flare separator
drum, and the flare — including igniters, tips, sealing devices,
purge and steam injection for smokeless burning Application
of relief devices must comply with appropriate ASME Vessel
Codes Design of relief systems must also comply with
applica-ble state and federal codes and laws as well as the requirements
of the insurance underwriter covering the plant or installation State and federal regulations not only cover safety but also environmental considerations such as air and water pollution and noise abatement This section presents a convenient sum-mary of relief system information obtained from API and other sources, abridged and modified for this data book Final design work should be consistent with the full scope of API, ASME, and other code and specification requirements
SECTION 5
Relief Systems
a = sonic velocity, m/s
A = required discharge area of the valve, cm2 Use
valve with the next larger standard orifice size/area
AB = bellows area, cm2
A´ = discharge area of the valve, cm2, for valve with
next standard size larger than required discharge
area
AD = disk area, cm2
AN = nozzle seat area, cm2
AP = piston area, cm2
Aw = total wetted surface area of vessel, m2
A3 = vessel area exposed to fire, m2
B = liquid expansion coefficient, 1/°C, at relieving
temperature [or (Vol/Vol)/°C]
C = drag coefficient
Cp = specific heat at constant pressure, kJ/(kg • K)
Cv = specific heat at constant volume, kJ/(kg • K)
C1 = coefficient determined by the ratio of specific
heats of the gas or vapor at standard conditions
d = flare tip diameter, mm
D = particle diameter, m
f = correction factor based on the ratio of specific heats
F = environment factor (see Fig 5-16)
F´ = relief valve factor, dimensionless
F* = fraction of heat radiated
F2 = coefficient for subcritical flow (Fig 5-12)
Fs = spring force, Newtons
g = acceleration due to gravity, 9.81 m/s2
G = relative density of gas referred to air = 1.00 at
15°C and 101.325 kPa (abs); or, if liquid, the relative
density of liquid at flowing temperature referred to
hG2 = enthalpy of vapor at downstream pressure, kJ/kg
H = height of vapor space of vessel, m
Hl = latent heat of the liquid exposed to fire, kJ/kg
HS = flare stack height, m
FIG 5-1 Nomenclature
I = radiation intensity at point X, W/m2
k = specific heat ratio, Cp/Cv (see Section 13)
Kb = capacity correction factor due to back pressure
Kc = combination correction for rupture disk = 0.9 = 1.0 no rupture disk installed
Kd = coefficient of discharge
Kn = correction factor for Napier steam equation
Ksh = correction factor due to the amount of superheat
in the stream
Kv = capacity correction factor due to viscosity for liquid
phase pressure relief
Kw = capacity correction factor due to back pressure for
balanced bellows pressure relief valves in liquid service (Fig 5-14)
L = drum length, m L/D = length to diameter ratio of pipe
Lf = length of flame, m
M = Mach number at pipe outlet
MW = molecular mass of gas or vapor MABP = maximum allowable back pressure, kPa (ga) NHV = net heating value of flare gas, kJ/kg
P = set pressure, kPa (ga)
PCF = critical-flow pressure, kPa (abs)
Pn = normal operating gas pressure, kPa (abs)
P1 = upstream relieving pressure, kPa (abs) This is
the set pressure plus the allowable overpressure plus the atmospheric pressure
P1g = upstream relieving pressure, kPa (ga) This is the
set pressure plus the allowable overpressure
P2 = downstream pressure at the valve outlet, kPa (abs)
Pb = back pressure, kPa (ga)
Trang 2A facility’s documentation allows the user to determine that
the facility was designed in accordance with relevant codes and
standards The relief system design documentation is one facet
of the overall facility documentation, which helps demonstrate
that the process can be operated in a safe manner Any
equip-ment modifications, operations, or changes made to process
pa-rameters, or operating procedures, can have a direct impact on
the relief system, and should therefore be documented as part
of a facility management of change (MOC) process
The relief system documentation should demonstrate that
all pressure-containing equipment has been identified and that
the overpressure protection has been analyzed
Documenta-tion based on the individual protected systems can facilitate
ensuring that all systems requiring pressure protection have
been identified The documentation should show that potential
causes of overpressure have been identified, rationale has been
provided as to whether a scenario is or is not credible, and
cred-ible causes of overpressure have been evaluated The design
basis of the disposal system, including all assumptions made
in the determination of controlling load(s), and calculated back
pressure at each relief device should be documented A detailed
list of documentation requirements is presented in ISO 23251
(API Std 521)
HAZARD REVIEWS
Appropriate hazard reviews, as a part of a Process Safety
Management Program, are required by U.S OSHA-29 CFR
Part 1910 in the United States, and by similar regulations in
most other localities in the world These reviews are conducted
during the design phase, prior to operation, and periodically
during operation The relief device sizing, and relief and
dispos-al system design, are criticdispos-al components of this review Typicdispos-al
steps in this process are:
• Preliminary hazard review using process flow diagrams and a preliminary layout, to identify hazards in the pro-cess, with the proposed facility location, and layout, and with storage and handling of feed materials or intermedi-ate and final products
• Early engineering hazard review with more advanced work products
• Detailed hazards review using one of several possible techniques sanctioned by local authorities (e.g., HAZOP, Hazard and Operability Analysis, What-if, Quantitative Risk Evaluation), utilizing process and instrumentation diagrams, plot plan, and other detailed design deliver-ables
• Safety Integrity Level (SIL) Review
• Engineering management of change (MOC) process
• Facility management of change (MOC) process
• Pre-start-up detailed hazard review
• Periodic detailed hazard review
CAUSES OF OVERPRESSURE
Pressure relief valves or other relieving devices are used to protect piping and equipment against excessive over-pressure Proper selection, use, location, and maintenance of relief de-vices are essential to protect personnel and equipment as well
as to comply with codes and laws
Determination of the maximum relief requirements may be difficult Loads for complex systems are determined by conser-vative assumptions and detailed analysis By general assump-
tion, two unrelated emergency conditions caused by unrelated
equipment failures or operator error will not occur
Ro = universal gas constant = 8314 kg J
• mol K
Re = Reynolds number (dimensionless)
S = specific heat, kJ/(kg • °C)
t = temperature, °C
T = absolute temperature of the inlet vapor, K
Tn = normal operating gas temperature, K
T1 = gas temperature, K, at the upstream pressure
Tw = vessel wall temperature, K
Ud = maximum allowable vapor velocity for vertical
Wf = flare gas flow rate, kg/h
Wr = vapor rate to be relieved by the relief valve, kg/h
xi = weight fraction of component i in total stream
X = distance from the base of the stack to another
point at the same elevation, m
Xc = dimensional reference for sizing a flare stack
θ = angle of flare flame from vertical, degrees
µ = viscosity at flowing temperature, mPa • s (centipoise)
μS = viscosity at flowing temperature, Saybolt Universal
Seconds (SSU)
FIG 5-1 (Cont’d) Nomenclature
Trang 3neously (no double jeopardy) The relationship and sequence of
events must be considered ISO 23251 (API Std 521) provides
fur-ther guidance on these issues
The development of relief loads requires the engineer to be
familiar with overall process design, including the type of pump
drives used, cooling water source, spares provided, plant layout,
instrumentation, and emergency shutdown philosophy The
de-sign of the proper relieving device must take into consideration,
as a minimum, all of the following upset conditions for the
indi-vidual equipment item if such upset can occur Each upset
condi-tion must be carefully evaluated to determine the “worst case”
condition which will dictate the relieving device capacity
The following provides guidance for some common
overpres-sure scenarios It must be recognized that it does not and cannot
address all potential overpressure scenarios that may be relevant
for a specific piece of process equipment The designer should
employ the Hazard Reviews discussed above to ensure that all
credible overpressure scenarios have been incorporated into a
facility’s design
SUMMARY OF COMMON
RELIEF SCENARIOS
Blocked Discharge
The outlet of almost any vessel, pump, compressor, fired
heat-er, or other equipment item can be blocked by mechanical failure
or human error The relief load for many cases is the maximum
flow into the system, at relief conditions, but must be carefully
analyzed for each contingency
Fire Exposure
Fire is one of the least predictable events which may occur in
a gas processing facility, but is a condition that may create the
greatest relieving requirements If fire can occur on a plant-wide
basis, this condition may dictate the sizing of the entire relief
sys-tem; however, since equipment may be dispersed geographically,
the effect of fire exposure on the relief system may be limited to
a specific plot area Various empirical equations have been
devel-oped to determine relief loads from vessels exposed to fire
For-mula selection varies with the system and fluid considered Fire
conditions may overpressure vapor-filled, liquid-filled, or
mixed-phase systems See the discussion on Sizing of Relief Devices, for
details, and relief load calculation methods
Tube Rupture
The tubes of shell and tube heat exchangers are subject to
fail-ure from a number of causes; including corrosion, thermal shock,
and vibration In the event of such a failure, it is possibile that the
high-pressure stream can overpressure the equipment and
pip-ing connected to the low pressure side of the exchanger A tube
rupture can also cause short duration hydraulic pressure shock,
due to the rapid acceleration of the fluid on the low pressure side
at the time of rupture
An internal failure can vary from a leaking tube or tube sheet
to a complete tube rupture where a sharp break occurs in one tube
The loss of containment of the low-pressure side to atmosphere is
unlikely to result from a tube rupture, if the resulting pressure on
the low-pressure side, including upstream and downstream
sys-tems, does not exceed the corrected hydrostatic test pressure
Appropriate design options to be considered for protecting the
low pressure side equipment and piping from potential tube
ture are: 1) Install a relief device (pressure relief valve or
rup-ture disk) on, or close to, the low pressure side of the heat exchanger, 2) ensure there is an adequate open relief path,
so that the low pressure side will not be over-pressured by a tube rupture, or 3) design the low pressure side of the heat exchanger, and the piping and equipment in the associated systems, such that the corrected hydro-static test pressure of the low pressure system exceeds the high pressure side design pressure (in some cases maximum upstream side operating pressure may be used instead of design pressure) The best option for each application is a function of the operating and design pressure for each side, fluid phase on each side, fluid type and service corrosion history, and the heat exchanger design Systems with gas, two phases, or a liquid which will flash across the tube rupture, on the high pressure side, and
a liquid on the low pressure side, should be thoroughly viewed, since a relief valve may be less effective in preventing surges in these circumstances See ISO 23251 (API Std 521) for the definition of corrected hydro-static test pressure and detailed guidance on this subject
re-Relief protection for tube rupture is not required for ble pipe heat exchangers, if the internal parts are constructed
dou-of schedule pipe
Control Failure
The failure positions of instruments and control valves must be carefully evaluated In practice, the control valve may not fail in the desired position A valve may stick in the wrong position, or a control loop may fail Relief protection for these factors must be provided Relief valve sizing require-ments for these conditions should be based on flow coeffi-cients (manufacturer data) and pressure differentials for the specific control valves and the facility involved Credit can be taken for some downstream flow paths, if ensured to be open throughout the relief event No favorable control valve action may be assumed In addition, the relief load determination should take into account that the liquid level in the upstream vessel may be lost, causing gas blow-by through the open con-trol valve
ISO 23251 (API Std 521) describes several relief scenarios that consider the position of a control valve and its bypass valve If during operation, the bypass valve may be opened to provide additional flow, then the total maximum flow (control valve wide open, plus bypass valve at some position, depend-ing on the service and facility practices, must be considered when determining the relief load If the bypass is opened only during maintenance, when the control valve is blocked in af-ter switchover, then a design based on the maximum flow through either the control valve, or the bypass valve, which-ever is greater, may be considered In this case the system must be evaluated during the facility hazard review to en-sure that the proper administrative controls are in place to prevent a situation in which both the control valve and the bypass are open simultaneously
Thermal Expansion
If isolation of a process line on the cold side of an exchanger can result in excess pressure due to heat input from the warm side, then the line or cold side of the exchanger should be pro-tected by a relief valve If any equipment item or line can be isolated while full of liquid, a relief valve should be provided for thermal expansion of the contained liquid Low process temperatures, solar radiation, heat tracing, or changes in at-mospheric temperature can necessitate thermal overpressure protection Flashing across the relief valve needs to be consid-
Trang 4ered Administrative controls for block valves around heat
ex-changer are discussed in ASME Section VIII, Appendix M
As a practical manner, thermal relief valves are not installed
in all instances where piping systems may be blocked in by two
valves The decision to install a thermal relief valve for
pip-ing systems is typically based on the followpip-ing factors: length
and size of piping, vapor pressure of the fluid at the elevated
temperature possible, volatility and/or toxicity of the fluid,
po-tential for valve leakage (metal vs soft seated valves), and the
presence of automatic shut down valves in the system It is
common to provide thermal relief valves for cryogenic liquid
ap-plications Guidance for when to specify thermal relief and for
sizing of the valve are provided in ISO 23251 (API Std 521).A
sizing equation for a simple thermal relief valve is given later
in this chapter A 19 mm × 25 mm relief valve is commonly
used for liquid filled, non-flashing piping systems containing
non-cryogenic liquids
Utility Failure
Loss of cooling water may occur on an area-wide or
plant-wide basis Commonly affected are fractionating columns and
other equipment utilizing water cooling Cooling water failure
must be considered for individual relief devices In addition, it
is often the governing case in sizing flare systems
Electric power failure, similar to cooling water failure, may
occur on an area-wide or plant-wide basis and may have a
vari-ety of effects Since electric pump and air cooler fan drives are
often employed in process units, a power failure may cause the
immediate loss of reflux to fractionators Motor driven
compres-sors will also shut down Power failures may result in major
device and flare system relief loads
Instrument air system failure, whether related to electric
power failure or not, must be considered in sizing of the flare
system since pneumatic control loops will be interrupted Also
control valves will assume the position as specified on “loss of
air” and the resulting effect on the flare system must be
con-sidered
Fans on air cooled heat exchangers or cooling towers
oc-casionally become inoperative because of a loss of power or a
mechanical breakdown On cooling towers and on air cooled
exchangers where independent operation of the louvers can be
maintained, credit may be taken for the cooling effect obtained
by convection and radiation in still air at ambient conditions
Check Valve Failure
Failure of a check valve to close must be considered A single
check valve is not an effective means for preventing
overpres-sure by reverse flow from a high-presoverpres-sure source In most cases,
focus should be on prevention of reverse flow It is important to
note that, in addition to overpressure of the upstream system,
reverse flow through machinery can destroy rotating
equip-ment, causing loss of containment If this hazard is of concern,
additional means of backflow prevention should be provided
(i.e emergency shut down inter-lock and valve)
For relief purposes, a single check valve is treated as if it is
not there, unless specific maintenance and inspection practices
are adhered to Two check valves in series reduce the likelihood,
and potential magnitude of reverse flow, but over-pressuring
of the low pressure side can still take place due to even small
check valve leaks, assuming the pressure is high enough ISO
23251 (API Std 521) provides specific guidance both on how to
treat check valve failure as a relief scenario,
maintenance/in-spection practices for critical check valves, when relief tion is required, and recommended practices for determining the controlling relief rate
protec-Reflux Failure and/or Loss of Overhead Cooling For Fractionators
The failure of electrical or mechanical equipment that vides cooling or condensation in process streams can cause overpressure in fractionators and process vessels The evalua-tion of relief scenarios for towers, in order to determine the ap-propriate load for the relief device, is complex Various simpli-fied approaches have been used in the past, however the most common method used today is a modified steady state material balance at relief conditions, as described by Nezami.11 Dynamic simulation may also be applied to evaluate the tower relief load
pro-vs time Care should be exercised when using the dynamic proach since the results can be highly dependent on the specific assumptions used, and may not be conservative
ap-Abnormal Heat Input
Reboilers and other process heating equipment are designed with a specified heat input When they are new or recently cleaned, and/or due to loss of control, additional heat input above the normal design can occur In the event of a failure of temperature control, vapor generation can exceed the process system’s ability to condense or otherwise absorb the build-up
of pressure, which may include non-condensables generated by overheating The system should be evaluated at the relief condi-tion using a modified material balance approach
Process Upset
The source of a process upset can vary depending of the plication Therefore this contingency must be analyzed individ-ually based on the specific circumstances For example, guid-ance for fractionation towers is included in reference 11
ap-Liquid Overfilling of a Vessel
Vessels are subject to overfilling and must be protected from overpressure from that source The cause can be an loss of con-trol on the inlet, or a failure of the controls or pump on the outlet
Transients
Transient pressure surges can occur as a result of liquid hammer, steam hammer, or steam condensate induced ham-mer, A pressure relief valve is normally not effective as a pro-tective device for these causes of overpressure, so the focus should be on avoiding transient pressure surges through design and operation, and/or the use of a surge suppressor device
Vacuum Protection
Vessels may be subject to (partial) vacuum from liquid pump out, condensation of volatiles, or other causes Typically, indus-try practices for vessels containing hydrocarbons is to design for the maximum possible vacuum In some services (i.e., very large low design pressure vessels) alternate vacuum protection
Trang 5Centrifugal Compressors — Centrifugal compressor
sys-tems should be analyzed in order to properly understand the
maximum pressure that can occur, and required relief
protec-tion (if any) for each part of the system, during operaprotec-tion
(nor-mal and upset), start-up, and at shutdown, based on the nor(nor-mal
and maximum suction, and/or discharge conditions The
maxi-mum settle out pressure for each portion of the system should
be calculated based on the configuration of the recycle valves,
check valve, seal balance line, and the volumes of the drums,
piping and coolers At compressor shutdown, the pressure in
one portion of the system may temporarily rise to a higher
pres-sure than the overall final settle out prespres-sure
Reciprocating Compressors — Each positive
displace-ment compressor must have a relief valve on the discharge
up-stream of the block and check valves in order to protect the
com-pressor and downstream equipment Commonly, relief valves
are also provided on each individual stage to protect the
inter-stage equipment Reciprocating compressor systems should be
analyzed in order to properly understand the maximum
pres-sure that can occur, and required relief protection for each part
of the system, during operation (normal and upset), start-up,
and at shutdown, based on the normal and maximum suction,
and/or discharge conditions
Fired Heaters — General best practice is to design fired
heaters such that the process side cannot be blocked in
Typical-ly, the heater control system will shut down the heater in case
of loss of flow on the process side, but the safety integrity level
(SIL) may be inadequate to avoid overpressure If there is a
pos-sibility that the process side of a fired heater may be blocked in,
then a relief valve should be provided to protect the heater The
relief valve should be installed on the downstream of the heater
to help ensure flow through the heater upon blocked outlet
Pumps — Relief valves are required on the discharge of
each positive displacement pump Normally, these relief valves
are piped back to the source vessel In some instances, the relief
device discharge can be returned to the suction line, depending
on the service and extent of heat up due to recycle In either
in-stallation, the pressure present at the discharge of the pressure
relief valve must be considered in determining the set pressure
of a conventional pressure relief valve Isolation valves around
the pressure relief valves may not be required, if the recycle is
to the suction line and the pump itself can be isolated for
main-tenance Many small metering pumps will have built-in
inter-nal relief protection As these interinter-nal reliefs are typically not
identified in facility documentation (e.g., P&IDs, critical device
lists, etc.), they are typically not tested or maintained For this
reason, they generally should not be relied upon as a means to
prevent overpressure
Atmospheric Storage Tanks, and Low Pressure Tanks
— Atmospheric storage tanks are typically protected against
overpressure and vacuum due to process conditions and
atmo-spheric changes In addition, relief protection for fire and other
upset conditions is required Tanks are commonly protected by
weighted or spring loaded pallet operated relief devices
(con-servation vents) A pilot-operated pressure relief can also be
utilized Storage tanks with diameters of 15 m or larger may be
fitted with a frangible roof (weak roof to shell attachment which
will fail upon overpressure); such a roof-to-shell joint serves as
emergency pressure relief device in lieu of a separate fire relief
valve valve (See API Std 650) All other tanks require fire
over-pressure protection by an emergency relief vent
Pressure relief requirements and relief device sizing for
at-mospheric tanks and any tanks, vessels, or other equipment
designed for less than 103 kPa (ga), are covered by ISO 28300
(API Std 2000), which sets thermal breathing rates, and fire relief rules for this equipment Note that the fire sizing equa-tions for low pressure equipment covered by ISO 28300 (API Std 2000) differ from those in ISO 23251 (API Std 521)
At a minimum, design of overpressure protection for tanks should consider: liquid movement into the tank, tank breathing due to weather changes that heat the tank, inert gas pad and/or purge regulator failure, internal and external heat transfer devic-
es, failure of vent collection systems, utility failure, blow-through
of gas from a higher pressure source, composition changes, cooling failure upstream of the tank, fire, and overfilling
At a minimum, design of vacuum protection for tanks should consider: liquid movement out of the tank due to pump transfer, liquid movement out of the tank due to opening of a drain valve, tank breathing due to weather changes that cool the tank, fail-ure of inert pads, utility failures
SPECIAL RELIEF SYSTEM CONSIDERATIONS
Administrative Controls
Administrative controls are procedures that, in combination with mechanical locking elements, are intended to ensure that personnel actions do not compromise the overpressure protec-tion of the equipment They include, as a minimum, document-
ed operation and maintenance procedures, and training of erator and maintenance personnel in these procedures [ASME Boiler & Pressure Vessel Code Section VIII, Appendix M]
op-Block Valves in the Relief Path
ASME Section VIII, Appendix M, provides requirements, cluding specific administrative controls, for block valves associ-ated with the inlet and outlet of pressure relief devices, block valves around equipment, such as heat exchangers, which may be isolated and drained for maintenance, and block valves between two pieces of equipment protected by a single relief device
in-High Integrity Protection Systems (HIPS)
A High Integrity Protection System (HIPS) is an mented system that has multiple redundancies to ensure the system is reliable and will react with desired effects as close to 100% of the time as possible As part of this, the instruments and valves, and the safeguarding system, are rated and main-tained to a stricter standard than most instruments These sys-tems are even on a different control system The instruments have a Safety Instrument Level (SIL); the higher the level the more reliable the system HIPS are typically used to mitigate flare loads that otherwise would become excessively large, or where a pressure relief valve would not adequately protect the system See Section 4 of the Data Book for more information on High Integrity Protection Systems (HIPS)
instru-In some very limited instances (i.e loss of control for an let valve downstream of a large packed pipeline upstream of
in-a trein-ating fin-acility, or protection in-agin-ainst runin-awin-ay rein-action,) in-a High Integrity Protection System may be considered to replace the requirement for a pressure relief device This is now rec-ognized by ASME Section VIII, Division 1 (UG-140),15 with a number of requirements including:
• The user shall ensure that the MAWP of the vessel is greater than the highest pressure that can reasonably
be expected to be achieved by the system The user shall conduct a detailed analysis of all credible overpressure scenarios
Trang 6• This analysis shall utilize an organized, systematic process
safety analysis approach such as: a Hazards and
Operabil-ity (HAZOP) review; a failure mode, effects and criticalOperabil-ity
analysis (FMECA); fault tree analysis; event tree analysis;
what-if analysis, or other similar methodology
• Instrumentation associated with a HIPS shall be tested
at regular intervals to ensure it functions per design
• Documentation of the HIPS system design and testing
shall be developed and maintained
The user shall consult ASME Section VIII, Division 1
(UG-140) for the complete set of requirements for the use of HIPS as
a means of overpressure protection
Emergency Depressuring
Emergency depressuring system are commonly used in
natural gas facilities The system can be automatically
actu-ated or operator actuactu-ated, on emergency shutdown of a piece
of equipment, a process unit, or an entire facility The purpose
of the depressurization system is one or more of the following:
1) minimize risk of loss of containment due to fire/runaway
re-action for pressure vessels, 2) minimize risk of fire, explosion,
or release of toxic gas due to partial loss of containment (e.g.,
piping or flange leak), or 3) minimize risk of fire, explosion, or
release of toxic gas due to partial or total seal/packing failure of
rotating equipment
Depressurization systems are often used to prevent
poten-tial stress rupture of a vessel when the metal temperature is
raised above the design temperature due to an abnormal heat
source This source is usually from a fire, but could also be from
a runaway exothermic reaction or other source of heat This
type of rupture can occur before a vessel reaches the set
pres-sure of relief devices on the vessel A general guideline is that a
depressurization system should be able to reduce the pressure
in the vessel to 50% of the design pressure in 15 minutes in
the event of a pool fire However, the required depressurization
time is dependent on the vessel material and wall thickness A
detailed discussion of emergency depressurization design basis
is provided in ISO 23251 (API Std 521)
Another application for a depressurization system is to
re-duce the consequences of a leak by quickly reducing the
pres-sure of the system/plant/compressor By reducing the
equip-ment pressure, both the leak rate and the total inventory of
fluid leaked can be reduced A general criterion for system
de-pressurization is to reduce the pressure in the system to 690
kPa (ga) in fifteen minutes or less
For compressors, the depressurization time is partially a
function of the location of the machine, and de-pressurization
times of less than 15 minutes is often used For compressors
located in buildings, a depressurization time of 3-5 minutes to
near atmospheric pressure are not uncommon
For each application, the designer must verify that all
com-ponents (especially vessel internals and machinery elastomer
seals) can withstand the chosen de-pressurization rate In
ad-dition, cold metal temperatures can be developed both in the
source vessel and the flare system during de-pressuring Both
systems must be designed for these conditions
Note that the ASME Pressure Vessel Section VIII code
re-quires a pressure relief device or HIPS to be installed to protect
the vessel even if a depressuring system is used
Low Temperature Flaring
Natural gas plants frequently have more than one flare system (i.e high pressure flare, low pressure flare, cryogen-
ic flare) The segregation of flare systems should be carefully evaluated, based on the fluid compositions, temperatures, and allowable back pressures in the relief header Several incidents have raised industry awareness on the need to properly con-sider segregation of flare headers and systems
When low temperature streams are relieved, the flare tem piping and equipment exposed to cryogenic temperature may require stainless steel or other acceptable alloys The sys-tem should be designed for the coldest process stream to be re-lieved including the cooling effect of the expanding fluid (Joule-Thomson effect) Materials selection should be made according
sys-to applicable code recommendations
Industry experience has shown that formation of limited tity of hydrates at a relief valve outlet can typically be handled safely However, relieving large amounts of hydrates, or solid
quan-CO2/H2S/ methane solids to a closed flare system should be
avoid-ed Industry experience has shown that pure CO2 can be safely vented to the atmosphere, utilizing proper design practices
SET PRESSURE FOR PRESSURE
RELIEVING DEVICES
Several pressure relief devices are certified and approved under Section VIII of the ASME Boiler and Pressure Vessel Code covering unfired pressure vessels They include spring loaded direct-acting pressure relief valves, pilot operated pres-sure relief valves, and rupture disks and shearing pin devices When the governing code is ANSI B31.3or ANSI B31.8, other types of pressure relieving devices such as monitoring regula-tors, series regulators, weight-loaded relief valves, liquid seals, etc are permitted The discussion below is limited to ASME, Section VIII, devices The devices must be compatible with the service and the overall design of the system See ASME, Sec-tion I, for fired boiler relieving criteria
Conventional Pressure Relief Valves
In a conventional pressure relief valve, the inlet pressure to the valve is directly opposed by a spring Tension on the spring
is set to keep the valve shut at normal operating pressure but allow the valve to open when the pressure reaches relieving conditions This is a differential pressure valve Most conven-tional safety-relief valves available to the petroleum industry have disks which have a greater area, AD, than the nozzle seat area, AN The effect of back pressure on such valves is illustrat-
ed in Fig 5-3b If the bonnet is vented to atmospheric pressure, the back pressure acts with the vessel pressure so as to over-come the spring force, FS, thus making the relieving pressure less than when set with atmospheric pressure on the outlet However, if the spring bonnet is vented to the valve discharge rather than to the atmosphere, the back pressure acts with the
Trang 7spring pressure so as to increase the opening pressure If the
back pressure were constant, it could be taken into account in
adjusting the set pressure In operation the back pressure is not
constant when a number of valves discharge into a manifold
A cut-away of a conventional relief valve is shown in Fig
5-3a Materials of construction for relief valves vary by service
Balanced Pressure Relief Valves
Balanced safety-relief valves incorporate means for
mini-mizing the effect of back pressure on the performance
charac-teristics — opening pressure, closing pressure, lift, and
reliev-ing capacity
These valves are of two types, the piston type and the
bel-lows type A cross section drawing of a balanced (belbel-lows) relief
valve is shown in Fig 5-4a In the piston type, of which several
variations are manufactured, the guide is vented so that the
back pressure on opposing faces of the valve disk cancels itself;
the top face of the piston, which has the same area, AP, as the
nozzle seat area, AN, is subjected to atmospheric pressure by
venting the bonnet The bonnet-vented gases from balanced
pis-ton-type valves should be disposed of with a minimum
restric-tion and in a safe manner
In the bellows type of balanced valve, the effective bellows
area, AB, is the same as the nozzle seat area, AN, and, by
at-tachment to the valve body, excludes the back pressure from
acting on the top side of that area of the disk The disk area
ex-tending beyond the bellows and seat area cancel, so that there
are no unbalanced forces under any downstream pressure The
bellows covers the disk guide so as to exclude the working fluid
from the bonnet To provide for a possible bellows failure or
leak, the bonnet must be vented separately from the discharge
The balanced safety-relief valve makes higher pressures in
the relief discharge manifolds possible Balanced-type valves
should have bonnet vents large enough to assure no appreciable
back pressure during design flow conditions If the valve is in
a location in which atmospheric venting (usually not a large
amount) presents a hazard, the vent should be piped to a safe
location independent of the valve discharge system The user
should obtain performance data on the specific type of valve
being considered A diagram of the force balance for piston and
bellows balanced pressure relief valves is shown in Fig 5-4b
Pilot Operated Pressure Relief Valves
A pilot operated pressure relief valve consists of two
princi-pal parts, a main valve and a pilot The valve utilizes a piston
instead of a shaft Inlet pressure is directed to the top of the
main valve piston More area is exposed to pressure on the top
of the piston than on the bottom so pressure, instead of a spring,
holds the main valve closed At the set pressure, the pilot opens,
reducing the pressure on top of the piston thereby allowing the
main valve to open fully For some applications, pilot-operated
relief valves are available in minimum friction, light-weight
diaphragm construction (in place of heavy pistons)
Pilot operated valves can allow backflow if downstream
pressure exceeds set points Backflow prevention is required
on valves, connected to common relief headers, where protected
equipment can be depressured and isolated while connected to
an active flare header, where a vacuum could occur at the inlet,
or where the downstream is connected to a system or vessel
where the pressure could exceed the inlet pressure
A check valve, split piston type valve, or backflow preventer
in the pilot line can be used
A typical pilot operated relief valve is shown in Fig 5-5 Pilot operated valves may be used in liquid or vapor services These valves contain nonmetallic components (elastomers), therefore fluid pressure and temperature, fluid characteristics, polymer-ization, fouling, solids, and corrosion can limit their use.Pilot operated valves are available with snap-action or mod-ulating action The modulating type relieves only the amount of fluid required to control the overpressure
When specifying pilot operated pressure relief valves, the elastomers chosen for the o-rings, and seals should be carefully considered Temperature (maximum and minimum), chemical compatibility (for the principle and trace components, and for potential liquid carryover), and resistance to explosive de-com-pression, are all factors in the choice of elastomers
Seat Leakage, and Resilient Pressure Seat Relief Valves
Some leakage can be expected through the seats of with al-to-metal seated, conventional or balanced type relief valves, when the operating pressure rises too close to the set pressure Allowable seat leakage rates are specified in API Std 527.16 Re-silient seat pressure relief valves (see Fig 5-6), with either an O-ring seat seal or a plastic seat, can provide seat integrities which are significantly higher than metal seated valves API Std 52716 specifies that, soft seated, pressure relief valves shall have zero bubbles/minute leakage at the same test pressures as metal seated valves This can allow bubble tight operation to 90%, of the set pressure, or higher Proper elastomer choice is critical for resilient seat pressure relief valves
met-Vapor Trim vs Liquid Trim For Pressure Relief Valves
Pressure relief valves handling gas or vapor are supplied with vapor trim Valves which releive liquid, two-phase, or po-tentially two-phase fluids, require a liquid trim It is important that the supplier is properly informed of the full range of expect-
ed operation when procuring pressure relief valves In addition, liquid trim pressure relief valves have a significantly higher blowdown as compared to vapor trim In these applications the designer must be prudent to allow sufficient pressure margin between the operating pressure and the relief valve set pres-sure to ensure reclosure of the valve following a relief event
Rupture Disk
A rupture disk consists of a thin diaphragm held between flanges The disk is designed to rupture and relieve pressure within tolerances established by ASME Code Section VIII Rup-ture disks can be used in gas processing plants, upstream of relief valves, to reduce minor leakage and valve deterioration
In these installations, the pressure in the cavity between the rupture disk and the relief valve should be monitored to detect
a ruptured or leaking disk In some applications a rupture disk with a higher pressure rating is installed in parallel to a relief valve
Rupture disks should be used as the primary relieving vice only if using a pressure relief valve is not practical Some examples of such situations are:
de-(a) Rapid rates of pressure rise A pressure relief valve tem does not react fast enough or cannot be made large enough to prevent overpressure (e.g., an exchanger rup-tured tube case or a runaway reaction in a vessel)
Trang 8sys-(b) Large relieving area required Because of extremely
high flow rates and/or low relieving pressure, providing
the required relieving area with a pressure relief valve
system is not practical
(c) A pressure relief valve system is susceptible to being
plugged, and thus inoperable, during service
All rupture disks have a manufacturing design range (MDR),
which essentially specifies the user’s tolerancefor variations in
the burst pressure Furthermore, disk temperature can have a
significant affect on the pressure at which the disk will open
Therefore, it is essential that the designer communicate the
de-sired MDR and the full range of expected operating and relief
temperatures when specifying requirements for a rupture disk
This will help ensure that the disk ruptures and provides relief
flow at the desired pressure rather than at a pressure higher or lower than the stamped pressure
A rupture disk is subject to fatigue failure due to operating pressure cycles To establish recommended replacement inter-vals, consult rupture disk suppliers
Shearing Pin Device (Rupture Pin)
A shearing pin device is a non-closing pressure relief-device actuated by differential pressure, or static inlet pressure, de-signed to function by the shearing of a load-carrying member that supports a pressure-containing member The devices are sanctioned by ASME Section VIII, and may be used for circum-stances where rupture disks may also be appropriate They have the advantage that the pin can be replaced without re-moving a piping flange
FIG 5-2 Pressure Level Relationships for Pressure Relief Valves 14
Courtesy American Petroleum Institute
Trang 9FIG 5-4a Balanced Bellows Pressure Relief Valve 14
FIG 5-4b Effect of Back Pressure on Set Pressure of Balanced Pressure Relief Valve 14
FIG 5-3b Effect of Back Pressure for Conventional
Pressure Relief Valve 14
FIG 5-3a Conventional Pressure Relief Valve 14
Courtesy of American Petroleum Institute
Courtesy of American Petroleum Institute
Courtesy of American Petroleum Institute Courtesy of American Petroleum Institute
Trang 10FIG 5-6 O-Ring Seals — For Conventional and Bellows
Pressure Relief Valves
RETAINERSCREW
Courtesy Lonergan Company
FIG 5-5
Pilot Operated Pressure Relief Valve 14
Courtesy of American Petroleum Institute
Trang 11SIZING OF RELIEF DEVICES
After the required relief capacity of a relief valve has been
determined, the minimum orifice area required must be
calcu-lated Industry standards for orifice designation, orifice area,
valve dimensions, valve body sizes, and pressure ratings are
available The standard orifices available — by letter
designa-tion, orifice area, and valve body size — are shown in Fig 5-7
In addition to the standard sizes, many relief valves are
manufactured with orifice areas smaller than “D”, and some
pilot-operated relief valves contain orifice areas larger than
“T.” Manufacturers should be contacted for information on
non-standard sizes
The set pressure and the overpressure allowed must be
with-in the limits permitted by the applicable codes System analysis
must include downstream piping For example, consider the use
of a relief valve made for a vessel with a maximum allowable
working pressure of 1000 kPa (ga) The relief valve set pressure
is 1000 kPa (ga), and the maximum allowable overpressure is
10% [100 kPa (ga)] The vessel pressure, when relieving, must
be limited to 1100 kPa (ga) [1000 kPa (ga) set pressure plus 100
kPa (ga) maximum overpressure] Pressure buildup downstream
of the relief valve should never cause the vessel pressure to
ex-ceed the maximum allowable overpressure
API vs Pressure Relief Valve Supplier
Discharge Coefficient/Orifice Area
API Std 520 Part I (clause 5.2)14 provides a thorough
discus-sion of the distinctions between the API effective area and the
actual flow area of a pressure relief valve, as well as those
be-tween the API effective coefficient of discharge and the ASME
certified coefficient of discharge The designer is cautioned
nev-er to mix the API effective orifice area and discharge coefficient
with the certified values of these parameters Furthermore,
final selection of pressure relief valve and sizing of associated
(inlet/outlet) piping should always use the certified values
Sizing for Gas or Vapor Relief
The rate of flow through a relief valve nozzle is dependent
on the absolute upstream pressure (as indicated in Equation
5-1, Equation 5-2, and Equation 5-3) and is independent of the
downstream pressure as long as the downstream pressure is
less than the critical-flow pressure (See API Std 520-1)
Howev-er, if the downstream pressure increases above the critical-flow
pressure, the flow through the relief valve is materially reduced
(e.g., when the downstream pressure equals the upstream
pres-sure, there is no flow)
The critical-flow pressure, PCF, may be estimated by the
per-fect gas relationship shown in Equation 5-5
As a rule of thumb if the downstream pressure at the relief
valve is greater than one-half of the valve inlet pressure (both
pressures in absolute units), then the relief valve nozzle will
experience subcritical flow
Critical Flow — Safety valves in gas or vapor service may
be sized by use of one of these equations:14
C1 can be obtained from Figs 5-8, and 5-9 Note that the
ideal gas specific heat ratio k = Cp/Cv has to be used for the
determination of C1 in Equation 5-3 The ideal gas specific heat ratio is independent of pressure The heat capacity ratio used should be based on the upstream relieving temperature Note that most process simulators will provide real gas specific heats
at the process pressure and temperature These should not be used in the above equation because if this value is used, the pressure relief device may be undersized For real gases with
a compressibility of less than 0.8 or greater than 1.1, API Std
520 Part I states that use of the ideal gas specific heat ratio can introduce significant error, and a more thermodynamically sound approach should be considered.14 The Theoretical Mass Flux Isentropic Expansion Method as described in API Std 520 Part I provides this foundation
Kb can be obtained from Figs 5-10 and 5-11 For final sign, Kd should be obtained from the valve manufacturer A value for Kd of 0.975 may be used for preliminary sizing
de-Subcritical Flow — For downstream pressures, P2, in cess of the critical-flow pressure, PCF, the flow through the pres-sure relief valve is subcritical Under these conditions, Equation 5-414 may be used to calculate the required effective discharge area for a conventional relief valve that has its spring setting adjusted to compensate for superimposed backpressure, or for a pilot operated relief valve
Sizing for Steam Relief
Safety-relief valves in steam service are sized by a fication of Napier’s steam flow formula Valve manufacturers can supply saturated steam capacity tables A correction fac-tor, Ksh, must be applied for safety valves in superheated steam service
modi-For safety-relief valves in steam service, the required area may be estimated from the following equations from the ASME Code Section VIII, Div 1 and API-520-1:14
A = (1.905) W (P1) (Ksh) • Kd Kb Kc Kn Eq 5-6
Kn = 1 for P1 < 10 339 kPa (abs)
Trang 12TurbulentFlow — Conventional and balanced bellows
re-lief valves in liquid service may be sized by use of Equation
5-8.14 Pilot-operated relief valves should be used in liquid service
only when the manufacturer has approved the specific
applica-tion
A = (7.07) (Vl) √ G
(Kd) (Kc) (Kw) (Kv) √ (P1 – Pb) Eq5-8
LaminarFlow — For liquid flow with Reynolds numbers
less than 4,000, the valve should be sized first with Kv = 1 in
order to obtain a preliminary required discharge area, A From
manufacturer standard orifice sizes, the next larger orifice size,
A´, should be used in determining the Reynolds number, Re,
from the following relationship:14
After the Reynolds number is determined, the factor Kv is
obtained from Fig 5-15 Divide the preliminary area (A´) by Kv
to obtain an area corrected for viscosity If the corrected area
exceeds the standard orifice area chosen, repeat the procedure
using the next larger standard orifice
SizingforThermalRelief
The following may be used to approximate relieving rates of
liquids expanded by thermal forces where no vapor is generated
at relief valve setting and maximum temperature.These
calcu-lations assume the liquid is non-compressible.13
(B) (Q)
Vl = 1000 Eq5-11
• (G) (S)Typical values of the liquid expansion coefficient, B, at 15°C
For heating by atmospheric conditions, such as solar
radia-tion, the surface area of the item or line in question should be
calculated Solar radiation [typically 787–1040 W/m2] should be
determined for the geographic area and applied to the surface area to approximate Q (W)
When the flow rate is calculated, the necessary area for lief may be found from the turbulent liquid flow equations
re-SizingaPressureReliefDevice
forTwoPhaseFlow
For two phase fluids and flashing liquids, a choking enon limits the flow through the pressure relief valve nozzle, in
phenom-a mphenom-anner similphenom-ar to the choking of phenom-a gphenom-as in criticphenom-al flow In order
to estimate the relief capacity of a nozzle, it is necessary to timate the choking pressure and then determine the two phase physical properties at these conditions The historical method
es-of calculating areas for liquid and vapor relief separately, and then adding the two areas together to get the total orifice size does not produce a conservative relief device size
Improved sizing methods have been developed using the lowing assumptions:
fol-• The fluid is in thermodynamic equilibrium through the nozzle
• The overall fluid is well mixed and can be represented by weighted averaging the gas and liquid densities (this is sometimes referred to as the non-slip assumption).Use of these assumptions has been found to produce a result which in most instances is close to the real flow rate through the nozzle, and which almost always will result in a conservative calculation of the required nozzle area However, these methods require additional equilibrium data along the isentropic expan-sion path through the relief valve Refer to API Std 520, Part
1, for a description of the sizing methods for two-phase liquid vapor relief Two methods are described in API Std 520, Part
1, Annex C; the Omega method and the Mass FluxIsentropic Expansion Method.14
SizingforFireforPartially
LiquidFilledSystems
The method of calculating the relief rate for fire sizing may
be obtained from ISO 23251 (API Std 521) , API Standard 2510 , NFPA 58, and possibly other local codes or standards Each of these references approach the problem in a slightly different manner Note that NFPA-58 applies only to U.S marine termi-nals, or U.S terminals at the end of DOT regulated pipelines.Most systems requiring fire relief will contain liquids and/or liquids in equilibrium with vapor Fire relief capacity in this situation is equal to the amount of vaporized liquid generated from the heat energy released from the fire and absorbed by the liquid containing vessel The difficult part of this procedure is the determination of heat absorbed Several methods are avail-able, including ISO/API, and U.S National Fire Protection As-sociation ISO 23251 (API Std 521) applies to the Petroleum and Natural Gas Industries, and is the standard most common-
ly used to assess fire heat load in these services
ISO 23251/API Std 52113 expresses relief requirements in terms of heat input from the fire to a vessel containing liquids, where adequate drainage and fire fighting equipment exist
The environment factor, F, in Equation 5-12 is determined from Fig 5-16 Credit for insulation can be taken only if the in-sulation system can withstand the fire and the impact of water
Trang 13from a fire hose Specific criteria are provided in ISO 23251/
API Std 521 The appropriate equation to use where adequate
drainage and fire fighting equipment do not exist is also
pro-vided in this Standard
A w in equation 5-12 is the total wetted surface, in square
me-ters Wetted surface is the surface wetted by liquid when the
ves-sel is filled to the maximum operating level It includes at least
that portion of a vessel within a height of 8 m above grade In
the case of spheres and spheroids, the term applies to that
por-tion of the vessel up to the elevapor-tion of its maximum horizontal
diameter or a height of 8 m, whichever is greater Grade usually
refers to ground grade but may be any level at which a sizable
area of exposed flammable liquid may be present
The amount of vapor generated is calculated from the latent
heat of the material at the relieving pressure of the valve For
fire relief only, this may be calculated at 121% of maximum
allowable working pressure All other conditions must be
cal-culated at 110% of maximum allowable working pressure for
single relief devices
Latent heat data may be obtained by performing flash
calcu-lations Mixed hydrocarbons will boil over a temperature range
depending on the liquid composition; therefore, consideration
must be given to the condition on the batch distillation curve
which will cause the largest relief valve orifice area
require-ments due to the heat input of a fire Generally the calculation
is continued until some fraction of the fluid is boiled off Other
dynamic simulation methods are also available The latent heat
of pure and some mixed paraffin hydrocarbon materials may be
estimated using Fig A.1 of ISO 23251 / API Std 521.13
When the latent heat is determined, required relieving
ca-pacity may be found by:13
The value W is used to size the relief valve orifice using
Equation 5-1 or Equation 5-4
For vessels containing only vapor, ISO 23251 (API Std 521)13
has recommended the following equation for determining
re-quired relief area based on fire:
183.3 (F´) (A3)
A = Eq 5-14
√ P1
F´ can be determined using Equation 5-15.13 If the result is
less than 0.01, then use F´ = 0.01 If insufficient information is
available to use Equation 5-15, then use F´ = 0.045
F´ = 0.1406 (Tw – T1)1.25 Eq 5-15
(C1) (Kd) T10.6506
To take credit for insulation, ISO 23251 (API Std 521)
re-quires the insulation material to function effectively at
tem-peratures of 900°C, and to retain its shape, and most of its
in-tegrity in covering the vessel in a fire, and during fire fighting
Typically, this requires proper insulation, plus an insulation
jacket constructed of a suitable material, and banding that can
withstand the fire conditions However, other systems may be
able to meet these requirements
Sizing for Fire for Liquid
Full or Nearly Full Equipment
For totally or near totally liquid filled systems, the
control-ling relief condition can be single vapor phase, liquid phase, or
two phase, depending on the fluid, liquid level, vessel size and
configuration, and location of the relief device For many gas plant applications, the assumption of single phase vapor relief
is adequate for pressure relief valve sizing See ISO 23251 (API Std 521) for further guidance
Sizing for Fire For Supercritical Fluids
Sometimes, the phase condition at the relieving pressure and temperature will be supercritical API recommends to consider
a dynamic approach where the vessel contents are assumed to
be single phase (supercritical), and a step by step heat flux is applied to the vessel walls [See ISO 23251 (API Std 521),] and Ouderkirk10 for details The same methodology can also be ap-plied for gas filled systems
Heavy hydrocarbons can be assumed to crack (i.e., to mally decompose), and it is the user’s responsibility to estimate the effective or equivalent latent heat for these applications Traditionally, a minimum latent heat value of 116 kJ/kg has been used if the conditions can not be quantified
ther-When a vessel is subjected to fire temperatures, the resulting metal temperature may greatly reduce the pressure rating of the vessel, in particular for vessels in vapor service Design for this situation should consider an emergency depressuring system and/or a water spray system to keep metal temperatures cooler For additional discussion on temperatures and flow rates due to depressurization and fires refer to Reference 7
RELIEF VALVE INSTALLATION
Relief valve installation requires careful consideration of inlet piping, pressure sensing lines (where used), and startup procedures Poor installation may render the safety relief valve inoperable or severely restrict the valve’s relieving capacity Either condition compromises the safety of the facility Many relief valve installations have block valves before and after the relief valve for in-service testing or removal; however, these block valves must be sealed or locked open, and administrative controls must be in place, to prevent inadvertent closure
Inlet Piping
The proper design of inlet piping to safety relief valves is extremely important Relief valves should not be installed at physically convenient locations unless inlet pressure losses are given careful consideration The ideal location is the direct con-nection to protected equipment to minimize inlet losses API STD 520 , Part II recommends a maximum non-recoverable pressure loss to a relief valve of three percent of set pressure, except for remote sensing pilot-operated pressure relief valves This pressure loss shall be the total of the inlet loss, line loss, and the block valve loss (if used) The loss should be calculated using the maximum rated flow through the safety relief valve
Discharge Piping and Backpressure
Proper discharge and relief header piping size is critical for the functioning of a pressure relief valve Inadequate piping can result in reduced relief valve capacity, cause unstable opera-tion, and/or, relief device damage
The pressure existing at the outlet of a pressure relief valve
is defined as backpressure Backpressure which is present at the outlet of a pressure relief valve, when it is required to op-erate, is defined as superimposed backpressure Backpressure which develops in the discharge system, after the pressure re-lief valve opens, is built-up backpressure The magnitude of pressure which exists at the outlet of the pressure relief valve,