With armature voltage limited by the drive, motor speed may be increased by reducing the shunt field current but not without consideration of brush performance, and possible commutation
Trang 1Effects of field weakening on
dc machine performance and maintenance
drives in the paper industry Many mills have inquired about operating motors beyond the original motor rating With armature voltage
limited by the drive, motor speed may be increased by
reducing the shunt field current
but not without consideration of
brush performance, and possible
commutation issues, because the
machine was not designed and tested at those conditions
This article examines and presents test/field data
display-ing the effects of field weakendisplay-ing on dc machine
perform-ance and maintenperform-ance
Control of DC Motor Speed Many industrial processes, including those used in the paper industry, require variable speed, variable torque machines to drive them This function has been reliably provided by dc motors for over a century
To maximize productivity of large capital equipment, it is
often possible to run the equipment at higher speeds than those anticipated when the equipment was originally designed and installed When increas-ing machine speed, there are a number
of factors that must be taken into account to be sure that the equipment can run safely and efficiently without a significant increase in maintenance requirements or even failures
If the driven machinery is found to be capable of run-ning at higher speeds, consideration must be given to the driving machinery, i.e., the dc motors If higher speeds are
Digital Object Identifier 10.1109/MIAS.2010.938392
B Y R I C H A R D D H A L L
& W A L T E R J K O N S T A N T Y
© PHOTODISC
56
Trang 2needed to drive the process equipment, there are several
approaches that can be adopted
1) If a gearbox is used in the drive, a different gear
ratio can be used to obtain a higher output speed
for the same input speed
2) The motors can be replaced with higher speed motors
3) The motors can be replaced with a low base speed
motor to direct drive the machine without a gearbox
4) The existing motors can be operated at higher speed
The first three options may be very expensive in terms of
equipment that must be purchased, modification of the
mounting bases, and downtime for the equipment changes
The fourth option requires little capital or downtime, so in
many cases this would be the preferred option
By varying the supplied armature voltage or excitation
(shunt field) current, dc motor speed can be easily controlled
If the armature voltage is increased, the dc motor will run
faster There is a limitation on the voltage that can be supplied
by dc drives, so it is possible to run out of voltage control
without reaching the desired motor top speed By reducing
the excitation (shunt field) current, the motor speed can be
further increased Many motors are purchased as speed range
motors to run at times with reduced excitation (field
weaken-ing) to obtain higher speeds Sometimes, however, even the
prescribed reduced field will not provide the desired speed
In these cases, the machinery owner may wish to reduce
the excitation current even further to obtain a higher speed
There are a number of factors to be taken into account when
considering the weakening of motor main fields to lower
lev-els It is imperative to stay within the safe mechanical and
electrical speeds of the motor The maximum safe mechanical
speed is higher than the maximum nameplate-rated speed of
the motor but may not be published and might be obtained
from the motor original equipment manufacturer (OEM)
There may be increased vibration or possibly mechanical
res-onant frequencies excited at the higher speed To produce the
same torque with reduced main field excitation, the armature
current will increase, but the armature current must be kept
below the rated current of the motor to prevent overheating
The motor may become unstable as a result of a further
reduction of flux in the main field air gap because of the field
weakening effect of ampere turns in the armature windings,
and the motor may tend to run away and over speed
Commutation may be affected, which can increase brush and
commutator maintenance The conditions for which the
motors are expected to operate are tested and adjusted by the
motor OEM The commutation limitations are particularly
important and not always well understood by many users
The major adjustments that can be made to dc motors
to tune them up for good commutation are:
1) brush position adjustment on the commutator
sur-face or setting electrical neutral
2) the flux adjustment from the commutating fields
(interpoles) to the correct level to assist in the
commu-tation process
Commutation, or current reversal in the armature
wind-ings, occurs as the armature coils pass from under one main
pole to the next This is the area in the motor where the
com-mutating poles or interpoles are located The commutation
process is described in [1] along with basic dc motor theory
The brush holders are mounted on arms that are secured
to a large ring called a brush yoke or rocker ring This ring
can be rotated and secured to set the brush position or neu-tral There a number of techniques that can be used to set neutral at the OEM factory or in the field, including motor repair shops These tests may be done with the motor standing still without power or running with no load
Adjusting the flux from the interpoles, or commutating fields, requires the machine to be operated under load and with controllable loads Some of the techniques used in the field, such as brush potential, may have safety issues as they require working closely with rotating machinery under load This method is discussed in [2] The brush potential method is also not practical for many of the smaller frame size motors used in the paper industry
Tuning DC Machines for Commutation
DC Motor Speed and Torque The speed of dc motors is controlled by adjusting the
The dc motor speed equation is
to the armature circuit; IR, armature current times the resistance of the armature circuit (V); BD, brush drop (V);
U, main field flux—a function of the ampere turns in the main field; and AR, armature reaction—the flux from the ampere turns in the armature
The variables that are controllable to change motor speed
armature voltage is supplied by the drive, and increased volt-age will cause the motor to run at a higher speed The main field flux is varied by changing the main field current The relationship between flux and field current is not linear and is determined by the motor saturation curve (see [1]) At lower flux levels, there is a direct proportion between flux and field current However, at higher flux levels, the curve flattens out, and changes in field current produce less change in the flux levels Since the flux is in the denominator of the earlier equa-tion, decreasing the flux level will increase the motor speed
The dc motors also produce torque to do their work The dc motor torque equation is
The motor will try to produce the torque that is required to drive the load If the main field flux is reduced to increase the motor speed, the armature current will automatically increase, and so the motor supplies the required torque The armature current, on a root-mean-squared basis, must be kept at, or below, the motor-rated current, or the motor will overheat and shorten insulation life Fortunately, the motors used in many paper mill applications operate well below the motor-rated cur-rent, so there is margin to increase the motor loading without overheating This should be reviewed on a case-by-case basis
For good motor performance and commutation, it is
Trang 3as possible If the armature voltage control does not
produce the required speed, only then it is necessary to
weaken the field for obtaining higher speeds
Motor Commutation Adjustment
If commutation is not occurring properly in the dc motor,
there will be increased sparking at the brushes, which causes
faster brush wear and electrical erosion of the commutator
copper This will result in more motor maintenance or repair
The motors must be properly assembled (see [3]) with
control of the following items:
armature
brushes around the commutator
Even with these parameters controlled, there is enough
variation between individual motors that each motor must
be fine tuned for good commutation
The technique used by a number of motor manufacturers
for tuning motors for commutation is called the black-band
method of commutation adjustment It is described in [4]
The black-band method has the great advantage of
being able to adjust both neutral (brush position) and
com-mutating field (interpole) strength under a variety of load
and speed conditions Unfortunately, it requires specialized
equipment and the ability to hold steady load on the
motors Although it is an excellent technique for motor
manufacturers for adjusting new machines before
ship-ment, it is generally not applicable for field work
Black commutation is a condition where there is no visible
sparking at the brushes If a motor can be adjusted for black
commutation, brush and commutator maintenance will be minimized The important adjustments for dc machines are setting the proper brush position on the commutator, or electrical neutral, and the correct interpole strength The black-band method uses a setup as shown in Figure 1 The dc machine under test will have excitation provided
by dc current in the main field The armature circuit includes the armature itself and the commutating fields (interpoles) in series or series/parallel, and in larger machines, a pole face winding (compensating winding) is also connected in series Power for the dc motor is provided
by a drive or, more commonly for black-band testing, a dc generator A dc generator is used because it provides pure
dc with no ripple that is associated with static drives that can contribute to sparking and adversely affect the results The commutating fields provide a magnetic field that gen-erates a voltage in the armature coils undergoing commutation, which helps the current in the coils to reverse direction (see [1]) For this test, a low-voltage generator called a buck-boost generator is placed in parallel with the commutating field This allows some adjustment of current in the commutating field independent of the armature current By purposely misad-justing the strength of the commutating field gradually, visible sparking will occur at the brushes and the limits of spark-free (black) commutation can be found Knowing these commuta-tion limits under various load condicommuta-tions allows the tester to determine permanent adjustments that must be made in brush position (neutral) and the commutation field strength The commutating fields and compensating windings (if used) are in series with the armature, so there is no adjustment in the electrical circuit to vary the magnetic field strength Any adjustment made in the magnetic cir-cuit is by interchanging magnetic (steel) and nonmag-netic (brass or aluminum) shims between the back of the commuting pole and the motor frame
Setting Electrical Neutral
In a properly adjusted dc motor, the brushes will be con-tacting commutator bars connected to coils in the armature that are undergoing commutation or have the current in them reversing Finding the correct position of the brushes
on the commutator is called setting electrical neutral The approximate brush position is set before operating the motor The first adjustment may use a static test of applying 120-V ac current to the shunt fields and shifting the brush yoke to get the minimum ac millivolts between brushes on adjacent brush arms Next, speed reversibility may be checked
at near no load (see [5]) Finally, to set neutral by the black-band method, the machine is operated at rated armature volt-age with little current in the armature circuit There should be
no sparking at the brushes at this point
Next, the buck-boost generator is operated to produce a cur-rent through the commutating fields in the same direction as armature current would normally flow as seen in Figure 2 This
is called boost current The boost current is slowly increased while observing the interface of the brushes and commutator Eventually, the magnetic flux from the commutating fields will miscompensate the motor enough that slight sparking will appear at the brushes The boost current that it takes to first cause sparking is recorded as the boost amperes
The buck-boost generator will then be operated to produce current in the opposite direction of normal current
Black-Band Setup Buck-Boost Generator
Commutating Field
Field
1
Black-band setup.
Light-Load Boost Buck-Boost Generator
Commutating Field
Field
IA ≈ 0
i i
2
Operating with boost current, but low armature current.
58
Trang 4flow in the armature This current will be gradually increased
until there is again slight visual sparking at the brushes, and
this will be recorded as the buck amperes These data will be
plotted on a graph that has buck and boost amperes on the
vertical axis and load amperes expressed as a percentage of
rated load on the horizontal axis as seen in Figure 3
This curve indicates that it takes less boost current to
cause sparking than buck current The center between buck
and boost is in the buck or strong side There should be
equal margins on the boost and buck side for a
well-adjusted machine To correct this, the brush yoke would be
loosened and the brush rigging shifted slightly in the
direc-tion the motor was rotating The test would be repeated
and adjustments made on a trial and error basis until the
center between buck and boost was near zero on the vertical
axis, and the machine was set on electrical neutral
Any time a motor is disassembled or the brush rigging
is moved, neutral should be reset There are a variety of
static and running tests that can be used in the field or
motor shop to accomplish this (see [5])
Load Testing and Adjusting
the Commutating Field Strength
To adjust the machine for loaded conditions, the motor must
be operated with steady and controllable armature current
The motor is set to run under a variety of loads, such
as 50, 100, and 150% rated armature current Under each
load condition, boost current and buck current is
circu-lated in the loop, including the buck-boost generator and
the commutating field coil In Figure 4, current is shown
in the boost direction where the boost current (i) adds to
armature current passes through the buck-boost generator, and the buck-boost current subtracts from the load current
in the commutating field coil Under each load condition, the boost and buck current is adjusted to initiate sparking, and this value is recorded These data are then plotted on the buck-boost curve
The solid area in Figure 5 is between the sparking limits where commutation is black (no sparking) Beyond these limits, there is sparking This black band goes off toward the boost side as load increases (weak) At the higher loads, there is not as much commutation margin on the buck side To correct this and have the black band go straight-out at the center would require removing some nonmag-netic shims behind the commutation pole and replacing them with magnetic shims If the black band were sloped downward, the opposite action would be required
The ideal black band seen in Figure 6 is wide (good commutation margin) and centered at all loads indicating a well-adjusted motor For a motor that is expected to run only
in one direction at base speed, it is not difficult to adjust the machine for good commutation at all loads If the machine
Buck-Boost Curve
Boost Amperes
Buck Amperes Load Amperes (%)
0
No Load Band
Center on Buck
Side (Strong)
Corrective Action: Shift Brush Rigging with Rotation (Motor)
3
Buck-boost curve at no load.
Loaded Boost Buck-Boost Generator
Commutating Field Drive Field
IA
IA + i
i
4
IA
Armature
Boost current with the motor under load.
Buck-Boost Curve Band Center on Boost Side (Weak)
Band Center
No Sparking in Black Area;
Sparking Outside Black Area
Load Amperes (%)
0
Corrective Action: Remove Nonmagnetic Shims and Add Magnetic Shims
5
Black band going weak (boost) with load.
Buck-Boost Curve
Load Amperes (%)
0
Near Perfect Black Band Centered at All Loads
150
6
Trang 5might run in either direction or the direction of rotation is
not known to the motor builder, there must be compromises
in brush position (neutral) The entire black band will shift
slightly to the boost side when the motor is running
clock-wise (CW) and to the buck side when running
counterclock-wise (CCW) If the motor must run at strong and weak main
fields, the black band will slope upward to the boost side at
higher loads, similar to Figure 5, with strong main field (base
speed) and downward to the buck side with weak main fields
(high speed) Again, a compromise in adjustment is needed
With the requirement to be able to run in both the
direc-tions and at base and high speeds, the common areas of the
black band may look like Figure 7, where the band is narrower
overall because of the reversibility requirement and narrows at
the higher loads because of the speed-range requirement There
is not very much commutation margin at the higher loads
If the main fields are to be further weakened to increase
motor speed beyond the speeds for which the motor was
originally adjusted, the black band with the weaker main
field will slope further to the buck side with increasing
load, and there may be no common area of the black band
where there is no sparking In addition, the armature
cur-rent (load) will increase to produce the same torque, so the
machine may be operating in an area where there is
continuous increased sparking, which can result in reduced brush life and more commutator maintenance
When dc motors are operated on rectified power sup-plies, there is ripple current produced from a combination
of silicon-controlled rectifier firing, drive tuning, actual motor operating volts and amps, and total inductance in the circuit High ripple current can affect motor commuta-tion, and typically, larger motors (>1,500 hp) may have line reactors installed to increase inductance in the circuit
to minimize current ripple If the amount of ripple current exceeds half the black-band width, sparking may result Ripple current also affects motor heating and insulation life, as the ripple current squared times the field (or conductor) resistance is direct heat added to the windings Test Data on 500-hp DC Motor
Black-band commutation tests were run on a 500-hp motor (500 V, 1,150/1,500 r/min, model 5CD604KA002A019, and serial number WK-2-10 WK) under a variety of volt-age, speed, and main field current conditions to show the effect of field weakening on commutation The setup is shown in Figure 8
For simplification, the data will be shown for one direc-tion of rotadirec-tion only The upper and lower lines in Figure 9 indicate the limits of the black band Between these limits, there is no sparking (black commutation) Outside these lim-its, there is some sparking The motor can operate to approxi-mately 140% load with no sparking The dark line indicates the center on the black band, indicating that the commutat-ing field flux is slightly strong (high) It is common to adjust the machine this way at the factory, as the black band will tend to shift weaker (toward the boost side) after some time during service This is because as the commutator film builds, commutators become slightly rougher, and brush springs age and lose some force over time
At the top speed, the black band becomes narrower, indi-cating there is less commutation margin as seen in Figure 10 This effect is typical for higher speed operation The black band still tends toward the strong side, and with the narrower limits, sparking would begin at about 115% of the armature-rated current As load increases, sparking levels would increase Buck-Boost Curve
Load Amperes (%)
0
Combined Band Strong and Weak Main Field and Reversible Rotation
150
7
Black band for reversible speed range motor.
8
Motors setup for load testing (Photo courtesy of GE.)
Band Center
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 500 RPM = 1,150 Rotation: CCW
l f = 15.3
9
Black band at base speed 1,150 r/min.
60
Trang 6The shunt fields were further weakened to obtain speeds
above where the motor was originally tested as seen in
Figure 11 The black band (commutation margin) is
nar-rower still At 150% load, it was impossible to extinguish
the sparking by the addition of buck or boost current
Next, the speed was increased by increasing the armature
voltage to 550 V, as seen in Figure 12, rather than with field
weakening alone The motor specifications allow up to 10%
overrated voltage In addition to increasing armature
volt-age, field current had to be reduced slightly to obtain 1,650
r/min The black-band commutation limits were similar to
those obtained by weakening the fields alone (Figure 11)
The commutating pole (interpole) shimming was adjusted
by removing a 0.015-in steel shim and adding a 0.016-in
alu-minum shim in an attempt to eliminate the slope of the black
band toward the buck side The result at the 1,150 r/min base
speed is seen in Figure 13 The black band no longer sloped
to the buck (strong) side with increasing load
When operated at the top speed of 1,500 r/min, after
adjusting commutation fields by removing a 0.015-in steel
shim and adding a 0.016-in aluminum shim behind the commutating poles, the black band still does not slope to the strong (buck) side However, there is once again less commutation margin indicated by the narrower black band at the higher speed as seen in Figure 14
If the shunt field is further weakened to obtain 1,650 r/min after adjusting commutation fields by removing a 0.015-in steel shim and adding a 0.016-in aluminum shim behind the commutation poles, the black band still does not slope to the strong buck side It was impossible to extinguish the sparking with buck or boost current at 150% load as seen in Figure 15
With the slope of the black bands modified by the com-mutating pole shim change, one further adjustment could be made to optimize the commutation if the motors were only going to operate in one rotation That adjustment would be a slight shift in neutral away from the present position where neutral was set for a machine that could operate in either rotation That adjustment would be to make a slight brush shift opposite to the direction of motor rotation (CW shift)
50
100 Band Center
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 500 RPM = 1,500 Rotation: CCW
l f = 9.5
50
100
VA V
V = 500
RPM = 1,500 Rotation: CCW
l f
ll = 9.5 f
10
Black band at top speed 1,500 r/min.
Band Center
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 500 RPM = 1,650 Rotation: CCW
l f = 8.4
Band Center
150
VA V
V = 500
RPM = 1,650 Rotation: CCW
l f
ll = 8.4 f
11
Black band above top speed (1,650 r/min) with field
weakening alone.
50
100 Band Center
Increased Voltage to Increase RPM
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 550 RPM = 1,650 Rotation: CCW
l f = 9.6
50
100 Band Center
Increased Voltage to Increase RPM
150
VA V
V = 550
RPM = 1,650 Rotation: CCW
l f
ll = 9.6 f
12
Black band above top speed (1,650 r/min) by both increased armature voltage and field weakening.
Band Center After –0.015-in Steel + 0.016-in Aluminum
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 500 RPM = 1,150 Rotation: CCW
l f = 14.7
Band Center After –0.015-in Steel + 0.016-in Aluminum
150
VA V
V = 500
RPM = 1,150 Rotation: CCW
l f
ll = 14.7 f
13
Black band at base speed 1,150 r/min after adjusting
Trang 7Although that test was not run, the predictable results would
be as shown in Figure 16 With these adjustments, the motor
would have better commutation at high speed when
operat-ing in the CCW rotation than it would have with the original
adjustment from the factory In other words, the
commuta-tion could be optimized for the speed that is higher than that
was expected at the time the motor was built
This particular motor was not as sensitive to varying the
slope of the black bands with changes in main field current
as some motors might be With the reduction of
commuta-tion margin (black-band width) at the higher speeds, this
fine tuning would improve commutation This would
minimize adverse effects to the motor and reduce the
amount of required motor maintenance caused by
operat-ing speeds increased above the speed where the motor was
originally tested and adjusted
Conclusions
The information presented here is generally known to dc
motor manufacturers but is not common knowledge to dc
motor users As there is a necessity for the equipment to perform beyond its original specifications and adjustment, commutation issues may arise that could increase mainte-nance requirements or downtime Understanding the commutation implications of reducing the motor field may direct a user on a course of action, should commutation deteriorate and maintenance costs increase unacceptably Some applications will tolerate this speed increase and others may not In some cases, it may be possible to shift neutral slightly in the direction of motor rotation to improve commutation at the higher loads in weak field, with a possible sacrifice in performance at lower loads or with full field The motor may be readjusted by the black-band method to improve commutation at the weak field settings at all loads, with some sacrifice of performance at base speed The motor could be returned to the OEM for black-band adjustment with the reduced main field excita-tion or sent to a motor shop with this capability Otherwise,
it may be necessary to consider the other options of obtain-ing a higher speed motor, usobtain-ing a different gearbox or usobtain-ing
a lower base speed motor and eliminating the gearbox References
[1] R D Hall (1985, Apr 23–26) Unraveling the commutation mystery Proc IEEE Pulp and Paper Conf., Greenville, SC, Morgan Advanced Materials and Technology [Online] Available: www.morganamt.com [2] G H Gunnoe, Jr., “Analyzing D-C commutation problems by the brush potential method,” Plant Eng., Apr 1980.
[3] W J Konstanty, “DC motor and generator troubleshooting and main-tenance,” in Conf Rec 1991 Annu Pulp and Paper Industry Tech Conf., June 3–7, 1991, pp 262–272.
[4] G H Gunnoe, Jr., “Fine-tuning D-C commutation by the black-band method,” Plant Eng., Jan 1980.
[5] R D Hall (2007, June) NECP—Tuning DC motors and generators presented at the Western Mining Electrical Association and Mining Electri-cal Maintenance and Safety Association [Online] Available: www.wmea.net
Richard D Hall (rich.hall@morganplc.com) is with National Electrical Carbon Products in Greenville, South Carolina Walter J Konstanty is with General Electric Company in Erie, Pennsylvania This article first appeared as “Commutation of
DC Motors Operated at Reduced Field Current” at the 2009 Pulp and Paper Industry Conference
Band Center After –0.015-in Steel + 0.016-in Aluminum
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 500 RPM = 1,500 Rotation: CCW
l f = 9.2
Band Center After –0.015-in Steel + 0.016-in Aluminum
150
VA V
V = 500
RPM = 1,500 Rotation: CCW
l f
ll = 9.2 f
14
Black band at top speed 1,500 r/min after adjusting
commutation fields.
Band Center After –0.015-in Steel + 0.016-in Aluminum
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 500 RPM = 1,650 Rotation: CCW
l f = 8.2
Band Center After –0.015-in Steel + 0.016-in Aluminum
150
VA V
V = 500
RPM = 1,650 Rotation: CCW
l f
ll = 8.2 f
15
Black band above top speed (1,650 r/min) after adjusting
commutation fields.
50 100 Band Center
After –0.015-in Steel + 0.016-in Aluminum and Shift Brushes Against
Rotation (CW)
0
150 Buck-Boost Curve
Load Amperes (%)
VA = 500 RPM = 1,650 Rotation: CCW
l f = 8.2
50 100 Band Center
After –0.015-in Steel + 0.016-in Aluminum and Shift Brushes Against
Rotation (CW)
150
VA V
V = 500
RPM = 1,650 Rotation: CCW
l f
ll = 8.2 f
16
Expected black band above top speed (1,650 r/min).
62