Causes, Evaluation and Repair of Reapproved 1998 Cracks in Concrete Structures Grant T.. The causes of cracks in concrete structures are summarized The proce-dures used to evaluate crac
Trang 1Causes, Evaluation and Repair of
Reapproved 1998
Cracks in Concrete Structures
Grant T H&orsen*t Chairman
Randall W Poston Secretary
Wii Hansen
M Nadim Hassoun Tony C Iiu$
Edward G Nawy Harry M Palmbaum
Keith A Pashina
Andrew Scanlon$
Ernest K Schrader Wimal Suaris Lewis H Tuthill Zenon A Zielinski
* Contributing Author
t Member of Task Group which prepared these revisions
$ Principal Author
0 Chairman of Task Group which prepared these revisions
Note: Associate members Masayatsu Ohtsu, Robert L Yuan, and Consulting Member LeRoy Lutz contribute to the revision of this document.
The causes of cracks in concrete structures are summarized The
proce-dures used to evaluate cracking in concrete and the principal techniques for
the repair of cracks are presented The key methods of crack repair are
discussed and guidance is provided for their proper application
Keywords: autogenous healing; beams (supports); cement-aggregate reactions;
concrete construction; concrete pavements; concrete slabs; concretes;
consol-idation; corrosion; cracking (fracturing); drilling; drying shrinkage; epoxy resins;
evaluation; failure; grouting, heat of hydration; mass concrete; methacrylates; mix
proportioning; plastics, polymers and resins; precast concrete; prestressed
concrete; reinforced concrete; repairs;resurfacing; sealing settlement (structural);
shrinkage; specifications; structural design; tension; thermal expansion; volume
1.2-Cracking of plastic concrete
1.3-Cracking of hardened concrete
ACI Committee Reports, Guides, Standard Practices, and
Commentaries are intended for guidance in designing,
plan-ning, executing, or inspecting construction and in preparing
specifications References to these documents shall not be
made in the Project Documents If items found in these
documents are desired to be a part of the Project
Docu-ments, they should be phrased in mandatory language and
incorporated into the Project Documents.
Chapter 2-Evaluation of cracking, pg 224.1R-9
2.1-Introduction2.2-Determination of location and extent of concretecracking
2.3-Selection of repair procedures
Chapter 3-Methods of crack repair, pg 224.1R-13
3.1-Introduction3.2-Epoxy injection3.3-Routing and sealing3.4-Stitching
3.5-Additional reinforcement3.6-Drilling and plugging3.7-Gravity filling3.8-Grouting3.9-Drypacking3.10-Crack arrest3.11-Polymer impregnation3.12-Overlay and surface treatments3.13-Autogenous healing
AC1 224.1R-93 supersedes ACI 224.1R-90 and became effective September 1, 1993.
Copyright d 1993, American Concrete Institute.
All rights reserved including rights of reproduction and use in any form or by any means, including the making of copies by any photo process, or by any elec- tronic or mechanical devices, printed or written or oral, or recording for sound
or visual reproduction or for use in any knowledge or retrieval system or device, unless permission in writing is obtained from the copyright proprietors.
224.1R-l
Trang 2Cracks in concrete have many causes They may affect
appearance only, or they may indicate significant
struc-tural distress or a lack of durability Cracks may
repre-sent the total extent of the damage, or they may point to
problems of greater magnitude Their significance
de-pends on the type of structure, as well as the nature of
the cracking For example, cracks that are acceptable for
buildings may not be acceptable in water-retaining
struc-tures
The proper repair of cracks depends on knowing the
causes and selecting the repair procedures that take these
causes into account; otherwise, the repair may only be
temporary Successful long-term repair procedures must
attack the causes of the cracks as well as the cracks
themselves
To aid the practitioner in pinpointing the best solution
to a cracking problem, this report discusses the causes,
evaluation procedures, and methods of repair of cracks
in concrete Chapter 1 presents a summary of the causes
of cracks and is designed to provide background for the
evaluation of cracks Chapter 2 describes evaluation
tech-niques and criteria Chapter 3 describes the methods of
crack repair and includes a discussion of a number of
techniques that are available Many situations will require
a combination of methods to fully correct the problem
Preface to the 1991 Revision
Following the initial publication of ACI 224.1R in
1985, the Committee processed two minor revisions One
revision, published as ACI 224.lR-89 simply updated the
format of recommended references A second minor
revi-sion contained minor technical revirevi-sions and editorial
corrections in the document, and added a new section to
Chapter 3, regarding the use of high-molecular-weight
methacrylates as sealer/healers
During 1990 a Committee 224 Task Croup reviewed
the document and recommended the revisions contained
herein Chapter 1 has been altered in only minor detail
The introduction to Chapter 2 has been revised
exten-sively, and additional minor revisions have been made to
the rest of the Chapter In Chapter 3, the section on
routing and sealing has been rewritten to include flexible
sealing and overbanding of cracks, and it is updated to
reflect current materials and construction practices
Sec-tion 3.2 on epoxy injection has been revised to be
some-what more general and reflect current practice The
for-mer section on high-molecular-weight methacrylates hasbeen moved to Section 3.7 and retitled “Gravity Filling.”This recognizes the point that “high-molecular-weightmethacrylate” is a material, and not a method Refer-ences are presented in Chapter 5; citations throughoutthe text have been revised to employ the author/dateformat Several new references have been added.Additional revision of the report is ongoing Commit-tee 224 invites comment from the readers and users ofthis report on new developments, or alternate viewpoints
on the Causes, Evaluation, and Repair of Cracks in crete Structures.
Con-CHAPTER 1-CAUSES AND CONTROL
OF CRACKING 1.1-Introduction
This chapter presents a brief summary of the causes ofcracks and means for their control Cracks are categor-ized as occurring either in plastic concrete or hardenedconcrete (Kelly 1981; Price 1982) In addition to the in-formation provided here, further details are presented inACI 224R and articles by Carlson et al (1979), Kelly(1981), Price (1982),, and Abdun-Nur (1983) Additionalreferences are cited throughout the chapter
1.2-Cracking of plastic concrete 1.2.1 Plastic shrinkage cracking-"Plastic shrinkage
cracking (Fig 1.1) occurs when subjected to a veryrapid loss of moisture caused by a combination of factorswhich include air and concrete temperatures, relativehumidity, and wind velocity at the surface of the con-crete These factors can combine to cause high rates ofsurface evaporation in either hot or cold weather.”When moisture evaporates from the surface of freshlyplaced concrete faster than it is replaced by bleed water,the surface concrete shrinks Due to the restraint pro-vided by the concrete below the drying surface layer, ten-sile stresses develop in the weak, stiffening plastic con-crete, resulting in shallow cracks of varying depth which
Fig 1.1-Typical plastic shrinkage cracking (Price 1982)
Trang 3Fig 1.2-Crack formed due to obstructed settlement (Price
Fig 1.3-Settlement cracking as a function of bar size,
slump and cover (Dakhil et al 1975)
may form a random, polygonal pattern, or may appear as
essentially parallel to one another These cracks are often
fairly wide at the surface They range from a few inches
to many feet in length and are spaced from a few inches
to as much as 10 ft (3 m) apart Plastic shrinkage cracks
begin as shallow cracks but can become full-depth cracks
Since plastic shrinkage cracking is due to a differential
volume change in the plastic concrete, successful control
measures require a reduction in the relative volume
change between the surface and other portions of the
concrete
Steps can be taken to prevent a rapid moisture loss
due to hot weather and dry winds (ACI 224R, ACI
302.1R, ACI 305R) These measures include the use of
fog nozzles to saturate the air above the surface and the
use of plastic sheeting to cover the surface between
finishing operations Windbreaks to reduce the wind
velocity and sunshades to reduce the surface temperatureare also helpful, and it is good practice to schedule flatwork after the windbreaks have been erected
1.2.2 Settlement cracking - After initial placement,
vibration, and finishing, concrete has a tendency to tinue to consolidate During this period, the plastic con-crete may be locally restrained by reinforcing steel, aprior concrete placement, or formwork This local re-straint may result in voids and/or cracks adjacent to therestraining element (Fig 1.2) When associated with rein-forcing steel, settlement cracking increases with in-creasing bar size, increasing slump, and decreasing cover(Dakhil et al 1975) This is shown in Fig 1.3 for alimited range of these variables The degree of settlementcracking may be intensified by insufficient vibration or
con-by the use of leaking or highly flexible forms
Form design (ACI 347R) and vibration (and tion), provision of a time interval between the placement
revibra-of concrete in columns or deep beams and the placement
of concrete in slabs and beams (ACI 309.2R), the use ofthe lowest possible slump, and an increase in concretecover will reduce settlement cracking
1.3-Cracking of hardened concrete 1.3.1 Drying shrinkage-A common cause of cracking
in concrete is restrained drying shrinkage Dryingshrinking is caused by the loss of moisture from thecement paste constituent, which can shrink by as much as
1 percent Fortunately, aggregate provides internal straint that reduces the magnitude of this volume change
re-to about 0.06 percent On wetting, concrete tends re-toexpand
These moisture-induced volume changes are a teristic of concrete If the shrinkage of concrete couldtake place without restraint, the concrete would notcrack It is the combination of shrinkage and restraint(usually provided by another part of the structure or bythe subgrade) that causes tensile stresses to develop.When the tensile strength of concrete is exceeded, it willcrack Cracks may propagate at much lower stresses thanare required to cause crack initiation
charac-In massive concrete elements, tensile stresses arecaused by differential shrinkage between the surface andthe interior concrete The larger shrinkage at the surfacecauses cracks to develop that may, with time, penetratedeeper into the concrete
The magnitude of the tensile stresses induced by ume change is influenced by a combination of factors, in-cluding the amount of shrinkage, the degree of restraint,the modulus of elasticity, and the amount of creep Theamount of drying shrinkage is influenced mainly by theamount and type of aggregate and the water content ofthe mix The greater the amount of aggregate, thesmaller the amount of shrinkage (Pickett 1956) Thehigher the stiffness of the aggregate, the more effective
vol-it is in reducing the shrinkage of the concrete (i.e., the
shrinkage of concrete containing sandstone aggregatemay be more than twice that of concrete with granite,
Trang 4basalt, or limestone (Carlson 1938)) The higher the
water content, the greater the amount of drying
shrink-age (U.S Bureau of Reclamation 1975)
Surface crazing (alligator pattern) on walls and slabs
is an example of drying shrinkage on a small scale
Crazing usually occurs when the surface layer of the
concrete has a higher water content than the interior
concrete The result is a series of shallow, closely spaced,
fine cracks
Drying shrinkage can be reduced by increasing the
amount of aggregate and reducing the water content A
procedure that will help reduce settlement cracking, as
well as drying shrinkage in walls, is reducing the water
content of the concrete as the wall is placed from the
bottom to the top Using this procedure, bleed water
from the lower portions of the wall will tend to equalize
the water content within the wall To be successful, this
procedure needs careful control of the concrete and
pro-per consolidation
Shrinkage cracking can be controlled by using
contrac-tion joints and steel detailing Shrinkage cracking may
also be reduced by using shrinkage-compensating cement
The reduction or elimination of subslab restraint can also
be effective in reducing shrinkage cracking in
slabs-on-grade (Wimsatt et al 1987) In cases where crack control
is particularly important, the minimum requirements of
AC I 318 are not always adequate These points are
dis-cussed in greater detail iu AC I 224R, which describes
additional construction practices designed to help control
the drying shrinkage cracking that does occur, and in
AC I 224.3R, which describes the use and function of
joints in concrete construction
1.3.2 Thermal stresses-Temperature differences within
a concrete structure may be caused by portions of the
structure losing heat of hydration at different rates or by
the weather conditions cooling or heating one portion of
the structure to a different degree or at a different rate
than another portion of the structure These temperature
differences result in differential volume changes When
the tensile stresses due to the differential volume changes
exceed the tensile stress capacity, concrete will crack The
effects of temperature differentials due to different rates
of heat dissipation of the heat of hydration of cement are
normally associated with mass concrete (which can
in-clude large columns, piers, beams, and footings, as well
as dams), while temperature differentials due to changes
in the ambient temperature can affect any structure
Cracking in mass concrete can result from a greater
temperature on the interior than on the exterior The
temperature gradient may be caused by either the center
of the concrete heating up more than the outside due to
the liberation of heat during cement hydration or more
rapid cooling of the exterior relative to the interior Both
cases result in tensile stresses on the exterior and, if the
tensile strength is exceeded, cracking will occur The
ten-sile stresses are proportional to the temperature
differ-ential, the coefficient of thermal expansion, the effective
modulus of elasticity (which is reduced by creep), and the
degree of restraint (Dusinberre 1945; Houghton 1972,1976) The more massive the structure, the greater thepotential for temperature differential and restraint.Procedures to help reduce thermally-induced crackinginclude reducing the maximum internal temperature, de-laying the onset of cooling, controlling the rate at whichthe concrete cools, and increasing the tensile strength ofthe concrete These and other methods used to reducecracking in massive concrete are presented in ACI207.1R, ACI 207.2R, ACI 207.4R, and ACI 224R.Hardened concrete has a coefficient of thermal expan-sion that may range from 4 to 9 x lOA F (7 to 11 x 10”C), with a typical value of 5.5 x lOA F (10 x lOA C).When one portion of a structure is subjected to a tem-perature-induced volume change, the potential for ther-mally-induced cracking exists Designers should give spe-cial consideration to structures in which some portionsare exposed to temperature changes, while other portions
of the structure are either partially or completely tected A drop in temperature may result in cracking inthe exposed element, while increases in temperature maycause cracking in the protected portion of the structure.Temperature gradients cause deflection and rotation instructural members; if restrained, serious stresses canresult (Priestly 1978; Hoffman et al 1983; ACI 343R).Allowing for movement by using properly designed con-traction joints and correct detailing will help alleviatethese problems
pro-1.3.3 Chemical reaction-Deleterious chemical
reac-tions may cause cracking of concrete These reacreac-tionsmay be due to materials used to make the concrete ormaterials that come into contact with the concrete after
it has hardened
Some general concepts for reducing adverse chemicalreactions are presented here, but only pretesting of themixture or extended field experience will determine theeffectiveness of a specific measure
Concrete may crack with time as the result of slowlydeveloping expansive reactions between aggregate con-taining active silica and alkalies derived from cement
hydration, admixtures, or external sources (e.g., curing
water, ground water, alkaline solutions stored or used inthe finished structure.)
The alkali-silica reaction results in the formation of aswelling gel, which tends to draw water from other por-tions of the concrete This causes local expansion andaccompanying tensile stresses, and may eventually result
in the complete deterioration of the structure Controlmeasures include proper selection of aggregates, use oflow alkali cement, and use of pozzolans, which them-selves contain very fine, highly active silicas The firstmeasure may preclude the problem from occurring, whilethe later two measures have the effect of decreasing thealkali to reactive silica ratio, resulting in the formation of
a nonexpanding calcium alkali silicate
Certain carbonate rocks participate in reactions withalkalies which, in some instances, produce detrimental ex-pansion and cracking These detrimental alkali-carbonate
Trang 5reactions are usually associated with argillaceous
dolomitic limestones which have a very fine grained
(cryptocrystalline) structure (ACI 201.2R) The affected
concrete is characterized by a network pattern of cracks
The reaction is distinguished from the alkali-silica
reaction by the general absence of silica gel surface
deposits at the crack The problem may be minimized by
avoiding reactive aggregates, dilution with nonreactive
aggregates, use of a smaller maximum size aggregate, and
use of low-alkali cement (ACI 201.2R)
Sulfate-bearing waters are a special durability problem
for concrete When sulfate penetrates hydrated cement
paste, it comes in contact with hydrated calcium
alumi-nate Calcium sulfoaluminate is formed, with a
subse-quently large increase in volume, resulting in high local
tensile stresses that lead to cracking which causes
development of closely spaced cracking and
deteriora-tion ASTM C 150 Types II and V portland cement,
which are low in tricalcium aluminate, will reduce the
severity of the problem The blended cements specified
in ASTM C 595 are also useful in this regard In severe
cases, some pozzolans, known to impart additional
resis-tance to sulfate attack, could be used after adequate
testing
Detrimental conditions may also occur from the
appli-cation of deicing salts to the surface of hardened
con-crete Concrete subjected to water soluble salts should be
amply air entrained, have adequate cover of the
rein-forcing steel, and be made of high-quality, low
per-meability concrete
The effects of these and other problems relating to the
durability of concrete are discussed in greater detail in
ACI 201.2R
The calcium hydroxide in hydrated cement paste will
combine with carbon dioxide in the air to form calcium
carbonate Since calcium carbonate has a smaller volume
than the calcium hydroxide, shrinkage will occur
(com-monly known as carbonation shrinkage) This situation
may result in significant surface crazing and may be
especially serious on freshly placed surfaces during the
first 24 hours when improperly vented combustion
heaters are used to keep concrete warm during the
winter months
With the exception of surface carbonation, very little
can be done to protect or repair concrete that has been
subjected to the types of chemical attack described above
(ACI 201.2R)
1.3.4 Weathering-The weathering processes that can
cause cracking include freezing and thawing, wetting and
drying, and heating and cooling Cracking of concrete
due to natural weathering is usually conspicuous, and it
may give the impression that the concrete is on the verge
of disintegration, even though the deterioration may not
have progressed much below the surface
Damage from freezing and thawing is the most
com-mon weather-related physical deterioration Concrete
may be damaged by freezing of water in the paste, in the
aggregate, or in both (Powers 1975)
Damage in hardened cement paste from freezing iscaused by the movement of water to freezing sites and byhydraulic pressure generated by the growth of ice crystals(Powers 1975)
Aggregate particles are surrounded by cement pastewhich prevents the rapid escape of water When the ag-gregate particles are above a critical degree of saturation,the expansion of the absorbed water during freezing maycrack the surrounding cement paste or damage the aggre-gate itself (Callan 1952; Snowdon and Edwards 1962).Concrete is best protected against freezing andthawing through the use of the lowest practical water-cement ratio and total water content, durable aggregate,and adequate air entrainment Adequate curing prior toexposure to freezing conditions is also important Allow-ing the structure to dry after curing will enhance itsfreezing and thawing durability
Other weathering processes that may cause cracking inconcrete are alternate wetting and drying, and heatingand cooling Both processes produce volume changes thatmay cause cracking If the volume changes are excessive,cracks may occur, as discussed in Sections 1.3.1 and 1.3.2
1.3.5 Corrosion of reinforcement-Corrosion of a metal
is an electrochemical process that requires an oxidizingagent, moisture, and electron flow within the metal; aseries of chemical reactions takes place on and adjacent
to the surface of the metal (ACI 201.2R)
The key to protecting metal from corrosion is to stop
or reverse the chemical reactions This may be done bycutting off the supplies of oxygen or moisture or by sup-plying excess electrons at the anodes to prevent theformation of the metal ions (cathodic protection).Reinforcing steel usually does not corrode in concretebecause a tightly adhering protective oxide coating forms
in the highly alkaline environment This is known aspassive protection
Reinforcing steel may corrode, however, if the linity of the concrete is reduced through carbonation or
alka-if the passivity of this steel is destroyed by aggressive ions(usually chlorides) Corrosion of the steel produces ironoxides and hydroxides, which have a volume much great-
er than the volume of the original metallic iron (Verbeck1975) This increase in volume causes high radial burstingstresses around reinforcing bars and results in local radialcracks These splitting cracks can propagate along the
bar, resulting in the formation of longitudinal cracks (i.e.,
parallel to the bar) or spalling of the concrete A broadcrack may also form at a plane of bars parallel to a con-crete surface, resulting in delamination, a well-knownproblem in bridge decks
Cracks provide easy access for oxygen, moisture, andchlorides, and thus, minor splitting cracks can create acondition in which corrosion and cracking are acceler-ated
Cracks transverse to reinforcement usually do notcause continuing corrosion of the reinforcement if theconcrete has low permeability This is due to the fact thatthe exposed portion of a ba.r at a crack acts as an anode
Trang 6At early ages, the wider the crack, the greater the
cor-rosion, simply because a greater portion of the bar has
lost its passive protection However, for continued
cor-rosion to occur, oxygen and moisture must be supplied to
other portions of the same bar or bars that are
elec-trically connected by direct contract or through hardware
such as chair supports If the combination of density and
cover thickness is adequate to restrict the flow of oxygen
and moisture, then the corrosion process is self sealing
(Verbeck 1975)
Corrosion can continue if a longitudinal crack forms
parallel to the reinforcement, because passivity is lost at
many locations, and oxygen and moisture are readily
available along the full length of the crack
Other causes of longitudinal cracking, such as high
bond stresses, transverse tension (for example, along
stir-rups or along slabs with two-way tension), shrinkage, and
settlement, can initiate corrosion
For general concrete construction, the best protection
against corrosion-induced splitting is the use of concrete
with low permeability and adequate cover Increased
con-crete cover over the reinforcing is effective in delaying
the corrosion process and also in resisting the splitting
and spalling caused by corrosion or transverse tension
(Gergely 1981; Beeby 1983) In the case of large bars and
thick covers, it may be necessary to add small transverse
reinforcement (while maintaining the minimum cover
re-quirements) to limit splitting and to reduce the surface
crack width (ACI 345R)
In very severe exposure conditions, additional
pro-tective measures may be required A number of options
are available, such as coated reinforcement, sealers or
overlays on the concrete, corrosion-inhibiting admixtures,
and cathodic protection (NCHRP Synthesis 57) Any
pro-cedure that effectively prevents access of oxygen and
moisture to the steel surface or reverses the electron flow
at the anode will protect the steel In most cases,
con-crete must be allowed to breathe, that is any concon-crete
surface treatment must allow water to evaporate from the
concrete
1.3.6 Poor construction practices-A wide variety of
poor construction practices can result in cracking in
concrete structures Foremost among these is the
com-mon practice of adding water to concrete to improve
workability Added water has the effect of reducing
strength, increasing settlement, and increasing drying
shrinkage When accompanied by a higher cement
con-tent to help offset the decrease in strength, an increase
in water content will also mean an increase in the
tem-perature differential between the interior and exterior
portions of the structure, resulting in increased thermal
stresses and possible cracking By adding cement, even if
the water-cement ratio remains constant, more shrinkage
will occur since the relative paste volume is increased
Lack of curing will increase the degree of cracking
within a concrete structure The early termination of
curing will allow for increased shrinkage at a time when
the concrete has low strength The lack of hydration of
the cement, due to drying, will result not only in creased long-term strength, but also in the reduced dur-ability of the structure
de-Other construction problems that may cause crackingare inadequate formwork supports, inadequate consolida-tion, and placement of construction joints at points ofhigh stress Lack of support for forms or inadequate con-solidation can result in settlement and cracking of theconcrete before it has developed sufficient strength tosupport its own weight, while the improper location ofconstruction joints can result in the joints opening atthese points of high stress
Methods to prevent cracking due to these and otherpoor construction procedures are well known (see ACI224R, ACI 302.1R, ACI 304R, ACI 305R, ACI 308, ACI309R, ACI 345R, and ACI 347R), but require special at-tention during construction to insure their proper exe-cution
1.3.7 Construction overloads-Loads induced during
construction can often be far more severe than those perienced in service Unfortunately, these conditions mayoccur at early ages when the concrete is most susceptible
ex-to damage and they often result in permanent cracks.Precast members, such as beams and panels, are mostfrequently subject to this abuse, but cast-in-place con-crete can also be affected A common error occurs whenprecast members are not properly supported duringtransport and erection The use of arbitrary or conven-ient lifting points may cause severe damage Lifting eyes,pins, and other attachments should be detailed or ap-proved by the designer When lifting pins are impractical,access to the bottom of a member must be provided sothat a strap may be used The PCI Committee on QualityControl Performance Criteria (1985, 1987) provides addi-tional information on the causes, prevention and repair
of cracking related to fabrication and shipment of precast
or prestressed beams, columns, hollow core slabs anddouble tees
Operators of lifting devices must exercise caution and
be aware that damage may be caused even when the per lifting accessories are used A large beam or panellowered too fast, and stopped suddenly, results in animpact load that may be several times the dead weight ofthe member Another common construction error thatshould be avoided is prying up one corner of a panel tolift it off its bed or “break it loose.”
pro-When considering the support of a member for ment, the designer must be aware of loads that may beinduced during transportation Some examples that occurduring shipment of large precast members via tractor andtrailer are jumping curbs or tight highway corners, torsiondue to differing roadway superelevations between thetrailer and the tractor, and differential acceleration of thetrailer and the tractor
ship-Pretensioned beams can present unique cracking lems at the time of stress release-usually when thebeams are less than one day old Multiple strands must
prob-be detensioned following a specific pattern, so as not to
Trang 7place unacceptable eccentric loads on the member If all
of the strands on one side of the beam are released while
the strands on the other side are still stressed, cracking
may occur on the side with the unreleased strands These
cracks are undesirable, but should close with the release
of the balance of the strands
In the case of a T-beam with a heavily reinforced
flange and a highly prestressed thin web, cracks may
develop at the web-flange junction
Another practice that can result in cracks near beam
ends is tack welding embedded bearing plates to the
casting bed to hold them in place during concrete
place-ment The tack welds are broken only after enough
pre-stress is induced during pre-stress transfer to break them
Until then, the bottom of the beam is restrained while
the rest of the beam is compressed Cracks will form near
the bearing plates if the welds are too strong
Thermal shock can cause cracking of steam-cured
con-crete if it is treated improperly The maximum rate of
cooling frequently used is 70 F (40 C) per hour (ACI
517.2R; Verbeck 1958; Shideler and Toennies 1963;
Kirk-bride 1971b) When brittle aggregate is used and the
strain capacity is low, the rate of cooling should be
decreased Even following this practice, thermally
in-duced cracking often occurs Temperature restrictions
should apply to the entire beam, not just locations where
temperatures are monitored If the protective tarps used
to contain the heat are pulled back for access to the
beam ends when cutting the strands, and if the ambient
temperatures are low, thermal shock may occur
Temper-ature recorders are seldom located in these critical areas
Similar conditions and cracking potential exist with
precast blocks, curbs, and window panels when a rapid
surface temperature drop occurs
It is believed by many (ACI 517.2R; Mansfield 1948;
Nurse 1949; Higginson 1961; Jastnebski 1961; Butt et al
1969; Kirkbride 1971a; Concrete Institute of Australia
1972; PCI Energy Committee 1981) that rapid cooling
may cause cracking only in the surface layers of very
thick units and that rapid cooling is not detrimental to
the strength or durability of standard precast products
(PCI Energy Committee 1981) One exception is
trans-verse cracking observed in pretensioned beams subjected
to cooling prior to detensioning For this reason,
pre-tensioned members should be depre-tensioned immediately
after the steam-curing has been discontinued (PCI
Energy Committee 1981)
Cast-in-place concrete can be unknowingly subjected
to construction loads in cold climates when heaters are
used to provide an elevated working temperature within
a structure Typically, tarps are used to cover windows
and door openings, and high volume heaters are
oper-ated inside the enclosed area If the heaters are locoper-ated
near exterior concrete members, especially thin walls, an
unacceptably high thermal gradient can result within the
members The interior of the wall will expand in relation
to the exterior Heaters should be kept away from the
exterior walls to minimize this effect Good practice also
requires that this be done to avoid localized dryingshrinkage and carbonation cracking
Storage of materials and the operation of equipmentcan easily result in loading conditions during constructionfar more severe than any load for which the structurewas designed Tight control must be maintained to avoidoverloading conditions Damage from unintentional con-struction overloads can be prevented only if designersprovide information on load limitations for the structureand if construction personnel heed these limitations
1.3.8 Errors in design and detailing-The effects ofimproper design and/or detailing range from poorappearance to lack of serviceability to catastrophicfailure These problems can be minimized only by athorough understanding of structural behavior (meanthere in the broadest sense)
Errors in design and detailing that may result inunacceptable cracking include use of poorly detailedreentrant comers in walls, precast members and slabs,improper selection and/or detailing of reinforcement,restraint of members subjected to volume changes caused
by variations in temperature and moisture, lack of quate contraction joints, and improper design of foun-dations, resulting in differential movement within thestructure Examples of these problems are presented byKaminetzky (1981) and Price (1982)
ade-Reentrant comers provided a location for the centration of stress and, therefore, are prime locationsfor the initiation of cracks Whether the high stressesresult from volume changes, in-plane loads, or bending,the designer must recognize that stresses are always highnear reentrant comers Well-known examples are windowand door openings in concrete walls and dapped endbeams, as shown in Fig 1.4 and 1.5 Additional properlyanchored diagonal reinforcement is required to keep theinevitable cracks narrow and prevent them from pro-pagating
con-“;
Fig 1.4-Typical crack pattern at reentrant corners (Price 1982)
Trang 8/
Fig 1.5-Typical cracking pattern of dapped end at service
load*
The use of an inadequate amount of reinforcing may
result in excessive cracking A typical mistake is to lightly
reinforce a member because it is a “nonstructural
mem-ber.” However, the member (such as a wall) may be tied
to the rest of the structure in such amanner that it is
required to carry a major portion of the load once the
structure begins to deform The “nonstructural element”
then begins to carry loads in proportion to its stiffness
Since this member is not detailed to act structurally,
unsightly cracking may result even though the safety of
the structure is not in question
The restraint of members subjected to volume changes
results frequently in cracks Stresses that can occur in
concrete due to restrained creep, temperature
differen-tial, and drying shrinkage can be many times the stresses
that occur due to loading A slab, wall, or a beam
re-strained against shortening, even if prestressed, can easily
develop tensile stresses sufficient to cause cracking
Pro-perly designed walls should have contraction joints
spaced from one to three times the wall height Beams
should be allowed to move Cast-in-place post-tensioned
construction that does not permit shortening of the
prestressed member is susceptible to cracking in both the
member and the supporting structure (Libby 1977) The
problem with restraint of structural members is especially
serious in pretensioned and precast members that may be
welded to the supports at both ends When combined
with other problem details (such as reentrant comers),
results may be catastrophic (Kaminetzky 1981; Mast
1981)
Improper foundation design may result in excessive
differential movement within a structure If the
differ-ential movement is relatively small, the cracking lems may be only visual in nature However, if there is amajor differential settlement, the structure may not beable to redistribute the loads rapidly enough, and a fail-ure may occur One of the advantages of reinforced con-crete is that, if the movement takes place over a longenough period of time, creep will allow at least someload redistribution to take place
prob-The importance of proper design and detailing willdepend on the particular structure and loading involved.Special care must be taken in the design and detailing ofstructures in which cracking may cause a major service-ability problem These structures also require continuousinspection during all phases of construction to supple-ment the careful design and detailing
1.3.9 Externally applied loads-It is well known that
load-induced tensile stresses result in cracks in concretemembers This point is readily acknowledged and ac-cepted in concrete design Current design procedures(ACI 318 and AASHTO) Standard Specifications forHighway Bridges) use reinforcing steel, not only to carrythe tensile forces, but to obtain both an adequate dis-triiution of cracks and a reasonable limit on crack width.Current knowledge of flexural members provides thebasis for the following general conclusions about the var-iables that control cracking: Crack width increases withincreasing steel stress, cover thickness and area of con-crete surrounding each reinforcing bar Of these, steelstress is the most important variable The bar diameter
is not a major consideration The width of a bottomcrack increases with an increasing strain gradient betweenthe steel and the tension face of the beam
The equation considered to best predict the mostprobable maximum surface crack width in bending wasdeveloped by Gergely and Lutz (1968) A simplified ver-sion of this equation is:
w = 0.076 #Ifs (d,A)” x 1O-3 (1.1)
in which w = most probable maximum crack width, in.;
B = ratio of distance between neutral axis and tensionface to distance between neutral axis and centroid ofreinforcing steel (taken as approximately 1.20 for typicalbeams in buildings); f, = reinforcing steel stress, ksi; d,
= thickness of cover from tension fiber to center of barclosest thereto, in.; and A = area of concrete symmetricwith reinforcing steel divided by number of bars, in2
A modification of this equation is used in ACI 318,which effectively limits crack widths to 0.016 in (0.41mm) for interior exposure and 0.013 in (0.33 mm) forexterior exposure However, considering the informationpresented in Section 1.3.5 which indicates little cor-relation between surface crack width for cracks transverse
to bars and the corrosion of reinforcing, these limits donot appear to be justified on the basis of corrosioncontrol
*From Alan H Mattock and Timothy C Chan (1979) "Design and Behavior
of Dapped-end Beams,” Joumal, Prestressed Concrete Institute, V 24, NO 6, Nov.-Dec., pp 28-45.
Trang 9There have been anumber of equations developed for
prestressed concrete members (ACI 224R), but no single
method has achieved general acceptance
The maximum crack width in tension members is
larger than that predicted by the expression for flexural
members (Broms 1965; Broms and Lutz 1965) Absence
of a strain gradient and compression zone in tension
members is the probable reason for the larger crack
widths
On the basis of limited data, the following expression
has been suggested to estimate the maximum crack width
in direct tension (ACI 224R):
w = 0.10 f s (d c A)0.33 x 10 -3 (1.2)Additional information on cracking of concrete in direct
tension is provided in ACI 224.2R
Flexural and tensile crack widths can be expected to
increase with time for members subjected to either
sus-tained or repetitive loading Although a large degree of
scatter is evident in the available data, a doubling of
crack width with time can be expected (Abeles et al
1968; Bennett and Dave 1969; Illston and Stevens 1972;
Holmberg 1973; Rehm and Eligehausen 1977)
Although work remains to be done, the basic
princi-ples of crack control for load-induced cracks are well
understood Well-distriiuted reinforcing offers the best
protection against undesirable cracking Reduced steel
stress, obtained through the use of a larger amount of
steel, will also reduce the amount of cracking While
reduced cover will reduce the surface crack width,
de-signers must keep in mind, as pointed out in Section
per-pendicular to reinforcing steel do not have a major effect
on the corrosion of the steel, while a reduction in cover
will be detrimental to the corrosion protection of the
reinforcing
CHAPTER 2-EVALUATION OF CRACKING
2.1-Introduction
When anticipating repair of cracks in concrete, it is
important to first identify the location and extent of
cracking It should be determined whether the observed
cracks are indicative of current or future structural
prob-lems, taking into consideration the present and
antici-pated future loading conditions The cause of the
crack-ing should be established before repairs are specified
Drawings, specifications, and construction and
main-tenance records should be reviewed If these documents,
along with field observations, do not provide the needed
information, a field investigation and structural analysis
should be completed before proceeding with repairs
The causes of cracks are discussed in Chapter 1 A
detailed evaluation of observed cracking can determine
which of those causes applies in a particular situation
Cracks need to be repaired if they reduce the strength,
stiffness, or durability of the structure to an unacceptable
level, or if the function of the structure is seriouslyimpaired In some cases, such as cracking in water-re-taining structures, the function of the structure willdictate the need for repair, even if strength, stiffness, orappearance are not significantly affected Cracks in pave-ments and slabs-on-grade may require repair to preventedge spalls, migration of water to the subgrade, or totransmit loads In addition, repairs that improve theappearance of the surface of a concrete structure may bedesired
2.2-Determination of location and extent of concrete cracking
Location and extent of cracking, as well as information
on the general condition of concrete in a structure, can
be determined by both direct and indirect observations,nondestructive and destructive testing, and tests of corestaken from the structure Information may also be ob-tained from drawings and construction and maintenancerecords
2.2.1 Direct and indirect observation-The locations and
widths of cracks should be noted on a sketch of thestructure A grid marked on the surface of the structurecan be useful to accurately locate cracks on the sketch.Crack widths can be measured to an accuracy of about0.001 in (0.025 mm) using a crack comparator, which is
a small, hand-held microscope with a scale on the lensclosest to the surface being viewed (Fig 2.1) Crackwidths may also be estimated using a clear comparatorcard having lines of specified width marked on the card.Observations such as spalling, exposed reinforcement,surface deterioration, and rust staining should be noted
on the sketch Internal conditions at specific crack tions can be observed with the use of flexible shaft fiber-scopes or rigid borescopes
loca-Crack movement can be monitored with mechanicalmovement indicators of the types shown in Fig 2.2 Theindicator, or crack monitor, shown in Fig 2.2 (a) gives adirect reading of crack displacement and rotation Theindicator in Fig 2.2 (b) (Stratton et al 1978) amplifiesthe crack movement (in this case, 50 times) and indicatesthe maximum range of movement during the measure-ment period Mechanical indicators have the advantage
Fig 2.1-Comparator for measuring crack widths (courtesy
of Edmound Scientific Co.)
Trang 10Newly Mounted Monitor
Monitor After Crack Movement
(a)-Crack monitor (courtesy of Avongard)
CRACK ON GIRDER FACE
SEE ISOMETRIC SECTION AT
\
(b)-Crack movement indicator (Stratton et al 1978)
Figure 2.2
Trang 11Fig 2.3-Pachometer (reinforcing bar locator) (courtesy of
James Instruments)
that they do not require moisture protection If more
detailed time histories are desired, a wide range of
transducers (most notably linear variable differential
transformers or LVDT'S) and data acquisition systems
(ranging from strip chart recorders to computer-based
systems) are available
Sketches can be supplemented by photographs
docu-menting the condition of the structure at the time of
investigation Guidance for making a condition survey of
concrete in service is given in ACI 201.1R, ACI 201.3R,
ACI 207.3R, ACI 345.1R, and ACI 546.1R
2.2.2 Nondestructive testing-Nondestructive tests can
be made to determine the presence of internal cracks
and voids and the depth of penetration of cracks visible
at the surface
Tapping the surface with a hammer or using a chain
drag are simple techniques to identify laminar cracking
near the surface A hollow sound indicates one or more
cracks below and parallel to the surface
The presence of reinforcement can be determined
using a pachometer (Fig 2.3) (Malhotra 1976) A
num-ber of pachometers are available that range in capability
from merely indicating the presence of steel to those that
may be calibrated to allow the experienced user a closer
determination of depth and the size of reinforcing steel
In some cases, however, it may be necessary to remove
the concrete cover (often by drilling or chipping) to
identify the bar sizes or to cahbrate cover measurements,
especially in areas of congested reinforcement
Receiving Transducer
Direct Transmission Increased Path Length Due to Dlscontlnuity Partial Depth Crack Alternate Configuration
a) Pulse transmitted through member
Fig 2.4-Ultrasonic testing through-transmission technique
If corrosion is a suspected cause of cracking, the *
easiest approach to investigate for corrosion entails theremoval of a portion of the concrete to directly observethe steel Corrosion potential can be detected by electri-cal potential measurements using a suitable referencehalf cell The most commonly used is a copper-coppersulfate half cell (ASTM C 876; Clear and Hay 1973); itsuse also requires access to a portion of the reinforcingsteel
With properly trained personnel and careful tion, it is possible to detect cracks using ultrasonicnondestructive test equipment (ASTM C 597) The mostcommon technique is through-transmission testing usingcommercially available equipment (Malhotra and Carino1991; Knab et al 1983) A mechanical pulse is trans-mitted to one face of the concrete member and received
evalua-at the opposite face, as shown Fig 2.4 The time takenfor the pulse to pass through the member is measuredelectronically If the distance between the transmittingand receiving transducers is known, the pulse velocity can
be calculated
When access is not available to opposite faces, ducers may be located on the same face [Fig 2.4(a)].While this technique is possible, the interpretation ofresults is not straightforward