Digitalmodules-SM322digitaloutput
Overview
z
Digital outputs
z
For connecting solenoid valves, contactors, low-power motors, lamps and motor starters
Application
Digital outputmodules can be used to outputdigital signals from the control to the process. They convert the internal signal levels of the S7-300 into the
external signal levels required for the process.
They are suitable e.g., for connecting solenoid valves, contactors, small-power motors, lamps and motor starters.
Design
Digital outputmodules are characterized by the following features:
z
Compact configuration:
Green LEDs for indicating the signal statuses at the outputs
Slots for the front connector, protected by a front cover
Labeling area on the front cover.
z
Easy installation:
There are no slot rules. The output addresses are defined by the slots.
When they are used in the ET 200M in combination with active bus modules, hot-swapping is possible.
z
User-friendly wiring
z
RC filter (for relay module 6ES7 322-1HF20):
Relay module 6ES7 322-1HF20-0AA0 features a switchable RC attenuation network (300 Ω/0.1 µF) for reducing arcing across the contacts when
switching large inductive loads (power factor = 0.4).The result is, for example:
Increase in the life of the contacts from 100,000 to 200,000 switching operations for controlling a motor starter for a NEMA motor of frame size 5
Function
Digital outputmodules convert the internal signal level of the PLC into the external signal levels required for the process.
When used with low leakage current, for example IEC type I input circuits, the network can be disconnected so that a false ON state is not signaled.
Di
g
ital modules-SM322 di
g
ital out
p
ut CA 01
Seite 1 von 5
Technical specifications
6ES7 322-1BH01-0AA0 6ES7 322-1BH10-0AA0 6ES7 322-1BL00-0AA0 6ES7 322-8BF00-0AB0 6ES7 322-5GH00-0AB0 6ES7 322-1CF00-0AA0
Voltages and currents
Load voltage L+
Rated value (DC) 24 V
24 V
24 V
24 V
24 V; 24/48
48 V; 48 to 125 V DC
Current consumption
z from load voltage L+
(no load), max.
80 mA
110 mA
160 mA
90 mA
200 mA
2 mA
z from backplane bus 5
V DC, max.
80 mA
70 mA
110 mA
70 mA
100 mA
100 mA
z Power dissipation,
typical
4.9 W
5 W
6.6 W
5 W
2.8 W
7.2 W
Connection system
z Requisite front
connector
20-pin
20-pin
40-pin
20-pin
40-pin
20-pin
Digital outputs
z Number of digital
outputs
16
16
32
8
16
8
z Length of cable
shielded, max.
1,000 m
1,000 m
1,000 m
1,000 m
1,000 m
1,000 m
z Length of cable
unshielded, max.
600 m
600 m
600 m
600 m
600 m
600 m
z Short-circuit
protection of the
output
Yes; electronic
Yes; electronic
Yes; electronic
Yes; electronic
No; provided externally
Yes; electronic
z Limitation of voltage
induced on circuit
interruption to
L+ (-53 V)
L+ (-53 V)
L+ (-53 V)
L+ (-45 V)
M (-1V)
z
Lamp load, max.
5 W
5 W
5 W
5 W
2.5 W
15 W; 15 W (48 V) or 40
W (125 V)
Output voltage
for 1 signal L+ (-0.8 V)
L+ (-0.8 V)
L+ (-0.8 V)
L+ (-0.8 V to -1.6 V)
L+ (-0.25 V)
L+ (-1.2 V)
Output current
for 1 signal rated
value
0.5 A
0.5 A
0.5 A
0.5 A
0.5 A
1.5 A
for 1 signal
permissible
range for 0 to 40
°C, min.
5 mA
5 mA
5 mA
10 mA
10 mA
for 1 signal
permissible
range for 0 to 40
°C, max.
0.6 A
0.6 A
0.6 A
0.6 A
1.5 A
for 1 signal
permissible
range for 40 to
60 °C, min.
5 mA
5 mA
5 mA
10 mA
10 mA
for 1 signal
permissible
range for 40 to
60 °C, max.
0.6 A
0.6 A
0.6 A
0.6 A
1.5 A
for 1 signal
minimum load
current
5 mA
5 mA
5 mA
10 mA
10 mA
for 1 signal
permissible surge
current, max.
1.5 A; for 50 ms, 1 A2s
one-off
3 A; for 10 ms
for 0 signal
residual current,
max.
0.5 mA
0.5 mA
0.5 mA
0.5 mA
10 µA
0.5 mA
Switching frequency
at resistive load,
max.
100 Hz
1,000 Hz
100 Hz
100 Hz
10 Hz
25 Hz
at inductive load,
max.
0.5 Hz
0.5 Hz
0.5 Hz
2 Hz
0.5 Hz
at lamp load,
max.
10 Hz
10 Hz
10 Hz
10 Hz
0.5 Hz
10 Hz
Summation current of the
outputs (per group)
z
vertical mounting
positions
up to 40°C., max. 2 A
2 A
2 A
4 A
4 A
z horizontal mounting
positions
up to 40°C., max. 4 A
4 A
4 A
4 A
6 A
up to 50°C., max.
4 A
up to 60°C., max. 3 A
3 A
3 A
3 A
0.5 A
3 A
Di
g
ital modules-SM322 di
g
ital out
p
ut CA 01
Seite 2 von 5
z
all other mounting
positions
up to 40°C., max.
0.5 A
Status information/
interrupts/ diagnostics
Interrupts
Diagnostic
interrupt
No
No
No
Yes; by channel
Yes; parameterizable
No
Diagnostics
Diagnostics No
No
No
Yes
Yes; Parameters can be
assigned
No
Insulation
z Insulation tested with
500 V DC
500 V DC
500 V DC
500 V DC
1500 V AC
1500 V AC
Potentials/ electrical
isolation
Digital output functions
between the
channels, in
groups of
8
8
8
8
1
4
between the
channels and the
backplane bus
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Dimensions and weight
z
Weight, approx.
190 g
200 g
260 g
210 g
260 g
250 g
z Width
40 mm
40 mm
40 mm
40 mm
40 mm
40 mm
z Height
125 mm
125 mm
125 mm
125 mm
125 mm
125 mm
z
Depth
120 mm
120 mm
120 mm
120 mm
120 mm
120 mm
6ES7 322-1BF01-0AA0 6ES7 322-1FF01-0AA0 6ES7 322-5FF00-0AB0 6ES7 322-1FH00-0AA0 6ES7 322-1FL00-0AA0 6ES7 322-1HF01-0AA0
Voltages and currents
Load voltage L+
Rated value (DC) 24 V
24 V
Load voltage L1
Rated value (AC)
230 V
230 V
230 V
120 V
Current consumption
z from load voltage L+
(no load), max.
60 mA
2 mA
110 mA
z from load voltage L1
(no load), max.
2 mA
2 mA
3 mA
10 mA
110 mA
z from backplane bus 5
V DC, max.
40 mA
100 mA
100 mA
200 mA
190 mA
40 mA
z Power dissipation,
typical
6.8 W
8.6 W
8.6 W
8.6 W
25 W
3.2 W
Connection system
z Requisite front
connector
20-pin
20-pin
40-pin
20-pin
20-pin
20-pin
Digital outputs
z Number of digital
outputs
8
8
8
16
32
8; Relay
z Length of cable
shielded, max.
1,000 m
1,000 m
1,000 m
1,000 m
1,000 m
1,000 m
z Length of cable
unshielded, max.
600 m
600 m
600 m
600 m
600 m
600 m
z Short-circuit
protection of the
output
Yes; electronic
Yes; Fusing
Yes; provided externally
Yes; Fuse 8A, 250 V;
each group
No
z
Limitation of voltage
induced on circuit
interruption to
L+ (-48 V)
z Lamp load, max.
10 W
50 W
50 W
50 W
50 W
50 W
Output voltage
for 1 signal L+ (-0.8 V)
L1 (-1.5 V)
L1 (-8.5V)
L+(-0.8V)
L1 (-0.8 V)
Output current
for 1 signal rated
value
2 A
2 A
2 A
1 A
1 A
for 1 signal
permissible
range for 0 to 40
°C, min.
5 mA
10 mA
10 mA
10 mA
10 mA
for 1 signal
permissible
range for 0 to 40
°C, max.
2.4 A
2 A
2 A
1 A
1 A
for 1 signal 5 mA
10 mA
10 mA
10 mA
10 mA
Di
g
ital modules-SM322 di
g
ital out
p
ut CA 01
Seite 3 von 5
permissible
range for 40 to
60 °C, min.
for 1 signal
permissible
range for 40 to
60 °C, max.
2.4 A
1 A
1 A
0.5 A
1 A
for 1 signal
minimum load
current
5 mA
10 mA
10 mA
10 mA
10 mA
5 mA
for 1 signal
permissible surge
current, max.
20 A; max. 1 AC cycle
20 A; with 2 half-waves
20 A; with 2 half-waves
10 A; per group (for 2 AC
cycles)
for 0 signal
residual current,
max.
0.5 mA
2 mA
2 mA
2 mA
2 mA
Switching frequency
at resistive load,
max.
100 Hz
10 Hz
10 Hz
10 Hz
10 Hz
2 Hz
at inductive load,
max.
0.5 Hz
0.5 Hz
0.5 Hz
0.5 Hz
0.5 Hz
0.5 Hz
at lamp load,
max.
10 Hz
1 Hz
1 Hz
1 Hz
1 Hz
2 Hz
Mechanical, max.
10 Hz
Summation current of the
outputs (per group)
z vertical mounting
positions
up to 40°C., max. 4 A
2 A
4 A
2 A
4 A
z horizontal mounting
positions
up to 40°C., max.
4 A
8 A
4 A
4 A
up to 60°C., max. 4 A
2 A
4 A
2 A
3 A
Relay outputs
z
Rated supply voltage
of the relay L+ (DC)
24 V
z
Number of operating
cycles
300,000
Switching capacity of the
contacts
at inductive load,
max.
2 A; 2 A (230 V AC), 2 A
(24 V DC)
at resistive load,
max.
2 A
Status information/
interrupts/ diagnostics
Interrupts
Diagnostic
interrupt
No
No
Yes; parameterizable
No
No
No
Diagnostics
Diagnostics No
Yes
Yes; OFF / last value /
substitute value
Yes
Yes
No
Insulation
z Insulation tested with
500 V DC
1500 V AC
1500 V AC
4000 V DC
4000 V DC
1500 V AC
Potentials/ electrical
isolation
Digital output functions
between the
channels, in
groups of
4
4
1
8
8
2
between the
channels and the
backplane bus
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Dimensions and weight
z
Width
40 mm
40 mm
40 mm
40 mm
80 mm
40 mm
z Height
125 mm
125 mm
125 mm
125 mm
125 mm
125 mm
z Depth
120 mm
120 mm
120 mm
120 mm
117 mm
120 mm
z Weight, approx.
190 g
275 g
275 g
275 g
500 g
190 g
6ES7 322-1HF10-0AA0 6ES7 322-5HF00-0AB0 6ES7 322-1HH01-0AA0
Voltages and currents
Load voltage L+
Rated value (DC) 120 V
24 V
120 V
Load voltage L1
Rated value (AC) 230 V
230 V
230 V
Current consumption
40 mA
100 mA
100 mA
Di
g
ital modules-SM322 di
g
ital out
p
ut CA 01
Seite 4 von 5
z
from backplane bus 5 V DC, max.
z Power dissipation, typical
4.2 W
3.5 W
4.5 W
Connection system
z Requisite front connector
40-pin
40-pin
20-pin
Digital outputs
z
Number of digital outputs
8; Relay
8; Relay
16; Relay
z Length of cable shielded, max.
1,000 m
1,000 m
1,000 m
z Length of cable unshielded, max.
600 m
600 m
600 m
z Short-circuit protection of the output
No; provided externally
No; provided externally
z Lamp load, max.
1,500 W; 230 V AC
1,500 W; 230 V AC
50 W; 230 V AC
Output current
for 1 signal minimum load current 5 mA
10 mA
10 mA
Switching frequency
at resistive load, max. 2 Hz
2 Hz
1 Hz
at inductive load, max. 0.5 Hz
0.5 Hz
0.5 Hz
at lamp load, max. 2 Hz
2 Hz
1 Hz
Mechanical, max. 10 Hz
10 Hz
10 Hz
Summation current of the outputs (per group)
z vertical mounting positions
up to 40°C., max. 5 A
5 A
8 A
z horizontal mounting positions
up to 60°C., max. 5 A
5 A
8 A
Relay outputs
z
Rated supply voltage of the relay L+ (DC)
24 V
24 V
z Number of operating cycles
300,000; 300000 (24 V DC, at 2 A), 200000
(120 V AC, at 3 A), 100000 (230 V AC, at 3 A)
100,000; 100000 (24 V DC, at 5 A), 100000
(230 V AC, at 5 A)
100,000; 50000 (24 V DC, at 2 A), 700000
(120 V AC, at 2 A), 100000 (230 V AC, at 2 A)
Switching capacity of the contacts
at inductive load, max. 3 A; 3 A (230 V AC), 2 A (24 V DC)
5 A; 5 A (230 V AC), 5 A (24 V DC)
2 A; 2 A (230 V AC), 2 A (24 V DC)
at resistive load, max. 8 A; 8 A (230 V AC), 5 A (24 V DC)
5 A; 5 A (230 V AC), 5 A (24 V DC)
2 A; 2 A (230 V AC), 2 A (24 V DC)
Status information/ interrupts/ diagnostics
Interrupts
Diagnostic interrupt No
Yes; parameterizable
No
Diagnostics
Diagnostics No
Yes; OFF / last value / substitute value
No
Insulation
z Insulation tested with
2000 V AC
1500 V AC
1500 V AC
Potentials/ electrical isolation
Digital output functions
between the channels, in groups of 1
1
8
between the channels and the
backplane bus
Yes; Optocoupler
Yes; Optocoupler
Yes; Optocoupler
Dimensions and weight
z Weight, approx.
320 g
320 g
250 g
z Width
40 mm
40 mm
40 mm
z
Height
125 mm
125 mm
125 mm
z Depth
120 mm
120 mm
120 mm
Di
g
ital modules-SM322 di
g
ital out
p
ut CA 01
Seite 5 von 5
. mm
120 mm
6ES7 32 2-1 BF0 1-0 AA0 6ES7 32 2-1 FF0 1-0 AA0 6ES7 32 2-5 FF0 0-0 AB0 6ES7 32 2-1 FH0 0-0 AA0 6ES7 32 2-1 FL0 0-0 AA0 6ES7 32 2-1 HF0 1-0 AA0
Voltages and currents
.
Di
g
ital modules - SM 322 di
g
ital out
p
ut CA 01
Seite 1 von 5
Technical specifications
6ES7 32 2-1 BH0 1-0 AA0 6ES7 32 2-1 BH1 0-0 AA0 6ES7 32 2-1 BL0 0-0 AA0