Method for operating keypad

Một phần của tài liệu Tài liệu biến tần ENC EDS1000 manual (Trang 44 - 48)

4.2 Operation and use of key board

4.2.5 Method for operating keypad

Can carry on various operation to the inverter through keypad for example:

(1) Status parameter display switching:

After pressing key display C group status supervision parameter; after displaying one supervision parameter code for 1 second, will display this parameter value automatically.

electrification

ENTER ENTER

MENU Second-class

menu

First class menu Third-class

menu

MENU/ESC

MENU /ESC ENTER/DATAstore para.

Editing status Waiting status

parameter Display or run status parameter display or failure alarm display

Set frequency

Switch display run parameter Frequency

setting mode Digital provision MENU /ESC

ESC MENU

ENTER

DATA ENTER

ESC DATA MENU

SHIFT

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 4 Run and operation explanation for inverter

Fig. 4-6 waiting status parameter display operating example Description:

1> All status parameters C-00 C-14 can be displayed when the inverter leaves factory. You can make a change by modifying function code F2.11, F2.12 if you want to, for detail please refer to F2.11, F2.12function code description.

2> Can press key to switch into constant supervision C-01 display status directly when the user see about status supervision parameter.

(2) Function code parameter setting

Take function code F2.06 modified from 5.00Hz to 6.00Hz as example.

Boldface in Fig.4-7 shows flickering digit.

Fig.4-7 example for parameter setting and modification

Description: under third-class menu, if the parameter has no blinking digit this function code can’t be modified possible reasons are as follows:

1> This function code shouldn’t be modified, for example actualdetected status parameter, run record parameter etc.

2> This function code can’t be modified under run status and can be changed after stopping running

ENTER DATA

50.00 -F0- -F2- F2.00 F2.06

05.00 -F2-

Key-press operation

order Enter into

editing Status display first-class menu

Choose F2 group function code

Function group confirmation go into second-class menu

Choose function code F2.06

Go back to First-class

menu Exit editing

status

Store modified value,back to second-class menu Display next function code LEDdisplayed

content

05.00

F2.07 06.00

Function code confirmation, Enter into third-class menu Parameter

modification, Choose parameter digit

Parameter modification, 5 6 ESC

MENU ENTER

DATA ENTER

DATA

SHIFT ENTER

DATA ESC

MENU ESC

MENU LED displayed content

1s 1s

50.00 C-01 Set frequency

Key-press operation order

Output frequency Output current

Output voltage Pulse input

Para. value C-02 Para. value

C-03 1s parameter C-14

1s parameter

SHIFT SHIFT

SHIFT SHIFT

SHIFT

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 4 Run and operation explanation for inverter

3> Parameter protected. All the function code can’t be modified when function code F2.13=1 or 2 in order to avoid wrong operation. Need to set the function code F2.13 to 0 if you want to edit function code parameter.

(3) Specified frequency adjustment for common run

Take example modifying specified frequency from 50.00Hz to 40.00Hz at F0.00=0 during running for explanation.

Fig. 4-8 set frequency adjustment operation example (4) Jog run operation

For example, keypad as current run command channel, jog run frequency 5Hz, waiting status.

Fig.4-9 Jog run operating example

(5) Operation for entering to function code editing status after setting user password

“user password”FF.00 is set to 6886 . Boldfaced digit in Fig.4-7 shows blinking bit.

Fig.4-10 inputting password to go into function code operation 0.0.0.6 6.0.0.6 0.0.0.0

50.00 0.0.0.6

6.8.0.6 6.0.0.6 6.8.8.6

-F0- 6.8.0.6

Nonediting status

user password effective, go into password validation status

At first last Digit flash, Increase to 6

move cursor position to first digit

Increase to 6

Increase to 8

Increase to 8

Move to second digit Press confirmation

Key, pass validation, Go into editing status

Move to third digit LED displayed

content Key-press operation order

ENTER DATA

SHIFT ESC

MENU

SHIFT SHIFT

5.00 50.00

0.01 50.00

release

waiting waiting

Display run output frequency

Output frequency Increased by 5Hz LED displayed

content Key-press operation

order Display set frequency

press keep

Output frequency Fall down to 0Hz Stop running

0.01

REVJOG REV

JOG REV

JOG

50.00 45.00 40.00

Press decreasing button for one time

Adjust frequency based on requirement 49.99

Stop pressing after set value reached, go back to normal display status after 1 second LED displayed

content Key-press operation order

www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 4 Run and operation explanation for inverter

(6) See about failure parameter under failure status:

Fig.4-11 failure status searching operation example Description:

1> If press key under failure status the user can see about Fd group function code parameter, search range Fd.06 Fd.14 LED first display function code number when the user press key and display parameter digit of this function code after 1s.

2> When the user see about failure parameter can press key directly to switch back to failure alarm display status (E0XX)

(7) keypad key-press locking operation

Under unlocked keypad situation press key for 5s to lock the keypad.

For detailed operation please refer to 2nd bit of F2.13 function code.

(8) keypad key-press unlocking operation

Under locked keypad situation press key for 5s to unlock the keypad.

1s 1s 1s

1s

E001 Fd.06 50:00 Fd.07 45:00 Fd.08 5.5

Fd.09 380

Fd.13 1111

1s Fd.14

1500 1s

Failure set freq. Failure output freq. Failure current

Failure output volt.

Failure terminal status Failure run time

LED displayed content

Key-press operation order

SHIFT SHIFT SHIFT

SHIFT SHIFT

SHIFT SHIFT

SHIFT

SHIFT

ENTER DATA

ESC MENU

ESC MENU