Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống
1
/ 32 trang
THÔNG TIN TÀI LIỆU
Thông tin cơ bản
Định dạng
Số trang
32
Dung lượng
283,9 KB
Nội dung
HARVARDUNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 1 of 32
H
H
a
a
r
r
v
v
a
a
r
r
d
d
U
U
n
n
i
i
v
v
e
e
r
r
s
s
i
i
t
t
y
y
W
W
i
i
r
r
e
e
a
a
n
n
d
d
C
C
a
a
b
b
l
l
e
e
S
S
t
t
a
a
n
n
d
d
a
a
r
r
d
d
s
s
Disclaimer
This information is collected and composed by QUANG DUNG TECHNOLOGY from Havard.edu. All
information is copyrighted by Harvard University.
http://www.uis.harvard.edu/departmental_telecom/faculty_staff_phones/wcstandards/section6.php
AUTHORIZED & EXCLUSIVE DISTRIBUTOR
Head Office
Suite 202, The Colonnade Building, 27 Nguyen Trung Truc St.,
District 1, Hochiminh City, Vietnam
Tel: 84.8 823-1693 Fax: 84.8 823-1665
Hanoi Office
A11, 3/Fl., Horizon Hotel, 40 Cat Linh St.,
Dong Da District, Hanoi, Vietnam
Tel: 84.4 736-7055 Fax: 84.4 733-2470
Website: www.qd-tek.com.vn
Email: info@qd-tek.com
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 2 of 32
TABLE OF CONTENTS
SECTION I: INTRODUCTION
A. Need For Standards
SECTION II: ABOUT THE HARVARDUNIVERSITY NETWORK (HUN)
Intellipath Telecommunications System
Wire andCable
High-speed Data Network (HSDN)
Telecommunications Facilities Management System (TFMS)
SECTION III: CUSTOMER WIREANDCABLE CONSIDERATIONS
A. Requirements Of Current Applications
B. Physical Environment
C. Building Distribution
D. Space Requirements
E. Electrical Requirements: MDF and IDF
F. Grounding
G. HVAC requirements
H. Cable Access: Internal And External
I. Wire Removal
J. Asbestos Abatement
K. Fire Stopping
SECTION IV: UNIVERSITY INFORMATION SYSTEMS ROLE
A. Provide Design Assistance
B. Notify Verizon of Facilities
C. Develop Implementation Plan
D. Provide Project Management
E. Conduct A Performance Evaluation
F. Administer Data Base
G. Coordinate Moves, Adds, Changes
H. Coordinate Repair
I. Conclusion
SECTION V: CONTRACTOR RESPONSIBILITIES
A. Color Coding
B. Label And Numbering Plan
C. Maintain Records and Documents
SECTION VI: TECHNICAL STANDARDS
A. Jacks
B. Backboards
C. 110 Termination Block Placement
D. VERIZON Network Termination and 110 Point Of Presence (POP)
E. Station Wiring (Horizontal Distribution)
F. Concealment
G. Voice And Data Riser Systems
SECTION VII: INTER-BUILDING CABLE (HSDN)
Fiber Optic Cable Composition
Fiber Optic Cable
Fiber Optic Cable Termination
Fiber Optic Testing and Acceptance
Fiber Optic Functional Specifications
Installation Requirements
Labeling Requirement
Test Requirements
Documentation Requirements
Warrantee Requirements
SECTION VIII: GLOSSARY
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 3 of 32
SECTION I. INTRODUCTION
A. Need For Standards
The HarvardUniversity Network (HUN) addresses the University's expanding need for
a wide variety of voice and data communication services. The University Network is
comprised of an Intellipath network, which provides voice services, integrated with
multiple data networks via wireandcableand a high-speed fiber backbone.
The goals of the University Network are to:
• help control costs
• protect current networking investments
• provide improved service to customers
• prepare the University for future network opportunities
• ensure installation integrity and adhere to building aesthetics
Because the University Network provides a wide variety of communications services,
it is important that the underlying wireandcable structure be sound. Specific wire
and cablestandards have been developed by University Information Systems (UIS).
These standards were developed and adopted by the University as part of its long-
range plan to provide the Harvard community with consistent campus wiring. These
standards ensure that as a department's needs change, or construction and
renovation occurs, users will be able to access new technology efficiently and cost-
effectively.
Wire andcablestandards are designed to assist departments as they plan for change
and expansion. Following these standards is especially important so departments and
the University can take advantage of the expanding array of new network
technologies. To prepare for these evolving technologies, the University has adopted
an "open architecture" approach. The open architecture approach provides a
framework upon which a wide variety of technologies can be built. Voice, data (both
low-speed and high-speed transmission), fax, graphic, wireless, VoIP, and image
transport can all be accommodated within the structure provided by the University
Network wireandcable standards. Some of the benefits of following wireandcable
standards are:
• By incorporating University Network standards in all wireandcable
installations, departments may be comfortable that newly installed equipment
will be compatible with the HarvardUniversity Network.
• By using uniform planning criteria, departments can be sure that appropriate
Network design decisions are made during each design phase.
• By following the recommendations for all wireandcable installations,
departments know there will be a standard Network in place so they can take
advantage of all enhanced services and remain compatible with emerging
technologies.
• By implementing wireandcable administrative procedures, departments are
certain that UIS will be able to support the University Network's telephone and
data capabilities.
All wireandcablestandards contained in this guide conform to industry
recommendations and take into account the wide variety of technology needs and
requirements of the Harvard community.
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 4 of 32
SECTION II. ABOUT THE HARVARDUNIVERSITY NETWORK
(HUN)
A. Overview The University Information Systems has implemented the major
components of the University Network:
• Intellipath Telecommunications System
• WireandCable
• High-speed Data Network (HSDN)
• Telecommunications Facilities Management System (TFMS)
Intellipath Telecommunications System
Intellipath is the name for digital Centrex service that provides telephone service to
the University. UIS has installed the 5ESS digital switching system using Integrated
Services Digital Network (ISDN) standards. ISDN, a series of international standards
that provides a universal interface for digital communications. (see Attachment A)
.
Wire andCable
The wireandcable system is the distribution medium used to transmit voice and
data. The wireandcable system, installed both in and between University buildings,
provides the foundation for transmitting the signaling service from the central
telephone office to the user's telephone and data equipment.
High-speed Data Network (HSDN)
HSDN is the information transportation service linking data networks and devices over
a high-speed fiber optic "backbone" (capacity over 10 Gigabit). Users are able to
access the HSDN through both local area networks and the data communications
capabilities of Intellipath service. Users are also able to access external data networks
via the HSDN.
Telecommunications Facilities Management System (TFMS)
TFMS is an on-line data base that provides UIS with inventory, service order, repair,
billing, and management reporting information about the Network.
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 5 of 32
SECTION III: CUSTOMER WIREANDCABLE CONSIDERATIONS
Before making any wireandcable decisions, building and office managers should
evaluate the requirements of their building based on the criteria described in this
section. A consultant from UIS is available to work with building and office managers
to determine an application's wireandcable requirements and to design a system
that adapts to their physical environment. HarvardUniversity Network consultants will
recommend all wireandcable designs based on the standards set by the major
telecommunications vendors and the Network standards adopted by Harvard. These
standards balance user needs, financial resources, and future technology
requirements.
A. Requirements Of Current Applications
An application's wireandcable requirements may include:
• software or hardware
• local area networks
• transmission speed
• security
• financial options
B. Physical Environment
The location's physical environment may include:
• number and location of users
• existing resources - space, conduits, cable trays, and station wiring
• new construction - location of new wiring closets
• anticipated future growth
• constraints - distance limitations
• building utilities
• security requirements
C. Building Distribution
Each University building houses a Telecommunication Room (MDF) in the basement
and Supporting Telecommunication Room (IDF's) on each floor. Telecommunication
Room design must be carefully planned (see Attachment B)
. Design considerations
include:
• adequate lighting, ventilation, air quality, and power
• ample work space for technicians
• room for all cabling, equipment, and backboards
• accessibility and security
• electrical requirements
• national, local, and building electrical codes
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 6 of 32
A riser cable system in each building links the floors together. For the building's high-
speed data requirements, fiber optic cable is used in addition to the customary copper
twisted pair for the riser cable. The locations of the Telecommunication Room are
essential for the wiring design to be both cost effective and to provide the highest
cable integrity. Ideally, the riser system is designed in a straight vertical line from the
basement MDF closet up through the IDF Telecommunication Rooms on each floor.
Each MDF/IDF should be located in the center of the area to be cabled to minimize the
length of the cable runs.
D. Space Requirements
When departments plan renovations or new construction, it is important to provide
sufficient power, space, and access to the building's utilities during the architectural
planning stages.
• The Main Telecommunication Rooms (TR) (MDF) will be a minimum of 10 feet
by 12 feet.
• Supporting Telecommunication Rooms (IDF) will be a minimum of 8 feet by 10
feet.
• Rooms must be kept clean and dust free at all times.
• Rooms will not be used for any purpose except communications support.
• The recommended height of the finished ceiling to the finished floor will be 8ft.
6in.
• Because Electromagnetic Interference (EMI) causes severe problems with
electronic equipment, communication rooms must not be shared with electrical
feeders, branch circuits or transformers.
• No housekeeping or other materials shall be stored in these rooms.
• Space for plywood (covered with fire-retardant paint) installed a minimum of
6” above finished floor (AFF) in both the MDF and IDF.
• Rooms should be stacked to provide for ease in running the riser, in a straight
vertical line from the basement MDF running to the IDFs.
• Locate the TRs in the center of the area to be cabled to minimize the length of
cable runs.
• Floors, walls, and ceiling shall be sealed, painted, or constructed of a material
to minimize dust. Finishes should be light in color to enhance room lighting.
Floors shall have anti-static properties as per IEC 61000-4-2.
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 7 of 32
• Carpet is prohibited
• Telecommunication rooms shall be located above any threat of flooding. Room
located in basements shall have drains with positive drainage, otherwise sump
pumps must be provided. When sump pumps are required, they shall be
connected to an emergency power supply and a water detection system shall
be provided to notify UIS SOC Operations in the event of a water problems.
• Services that are not communications related are prohibited in these rooms.
This includes, but is not limited to supply storage, janitorial services, etc.
• Doors of the TR shall be a minimum of 1 m (3 ft) wide and 2.13 m (7 ft) high,
without doorsill, hinged to open outward (code permitting) or slide side-to-
side, or be removable. Doors shall be fitted with a lock and have either no
center post or a removable center post to facilitate access for large equipment.
E. Electrical Requirements: MDF and IDF
Power for the MDF and IDF should adhere to the following requirements:
• Each TR shall be furnished with its own dedicated electrical panel. The panel
for each room shall be wired to a panel that is fed from a UPS system that is
connected to the Emergency generator for the building.
• A minimum of two, non-switchable, 30AMP, 208 (NEMA L6-30) Volt alternating
current nominal twist-lock receptacles, each on separate branch circuits, shall
be provided for equipment power. In addition, each space shall have a
minimum of 2 non-switchable 20 Amp (NEMA 5-20), 120 volt alternating
current quad receptacles.
• Proper lighting that produces 50 foot-candles positioned between rows of racks
and/or cabinets, not directly over the top of the rack.
• The grounding busbar is provided by others, but grounding of the conduit and
cable tray is the responsibility of the telecommunications contractor.
• Electrical panels, other than those exclusively serving the telecommunication
room which it is located, are strictly prohibited in telecommunication room.
• Each Work Area (WA) should have two (2) duplex outlets with every outlet.
F. Grounding
All telecommunications rooms shall have a Telecommunications Grounding Busbar
(TGB). A TGB should provide a central ground attachment point for
telecommunications systems, computers and other equipment located in the tele/data
room.
• Provide a suitable telecommunications ground for equipment as required per
ANSI/TIA/EIA-607 (telecommunications grounding), IEEE Emerald Green book
and NEC requirements.
The Telecommunication Main Grounding Busbar (TMGB) installed in the MDF
shall be 20 inches long and 4 inches wide by ¼ inch thick with pre drilled
NEMA bolthole sizing and spacing, Chatsworth Products, Inc. part number
40153-020.
The Telecommunication Grounding Busbar (TGB) installed in the IDF shall be
10 inches long and 2 inches wide by ¼ inch thick with pre drilled NEMA
bolthole sizing and spacing, Chatsworth Products, Inc. part number 13622-
010.
• All cable tray, ladder rack, access floors and Telecommunications racks and/or
cabinets contained within the MDF and the telecommunications room shall be
grounded/ bonded together with #6 AWG, and then bonded/grounded with #6
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 8 of 32
AWG to the Telecommunications Grounding Busbar (TGB). The grounding
busbar shall be provided by the Electrical Installer.
• All aforementioned telecommunications devices shall be grounded/bonded to
the TGB using solid 6 bare copper (AWG wire). Coordinate exact grounding
locations for each component with the Electrical Installer.
Stand-Off Insulator Specifications:
Dielectric Strength:
19,000-21,000 volts S.T.
UL 94V-O Flame Resistant
Finish Color:
Red
Insert Size & Material:
3/8-16 x 5/8”D UNC-2B Aluminum
Dimensions:
2.5”W x 2.5”D
Grounding Busbar (TGB) Specifications:
Provides 3.75” stand-off from backboard.
The 20” busbar (13622-020) has both .25”D and .375”D
All telecommunications rooms shall have a
grounding bar that shall be 20 inches long and 4
inches wide by ¼ inch thick with pre drilled NEMA
bolthole sizing and spacing. Each distribution point
shall be grounded to the main building ground,
NEC and EIA/TIA 607 requirement shall be
followed.
Telecommunications Grounding Busbars
Each distribution point shall be grounded to the main building ground, NEC and
EIA/TIA 607 requirement shall be followed.
• First choice for a ground at the MDF is a busbar connected to the building
ground; second choice is a bus bar connected to a water pipe (with a #6
copper cable).
• First choice for a ground at the IDF is a busbar connected to the building
ground; second choice is a bus bar connected to a water pipe (with a #6
copper cable).
• The grounding busbar is provided by other, grounding of the conduit andcable
tray is the responsibility of its installation contractor.
G. HVAC requirements
• Coordinate electronic equipment BTU output with UIS for proper cooling
requirements to maintain 64F – 75F temperature and 30% min – 55% max
relative humidity. Typically the buildings central air conditioning system is
suitable.
• Maintain positive pressure with a minimum of 1 air change per hour.
• No plumbing, HVAC or electrical conduit shall pass through or be directly above
the telecommunications room.
H. Cable Access: Internal And External
Internal Cable Access
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 9 of 32
• TR’s aligned vertically: coring (drilling) of the floor and placement of sleeves is
generally used.
• TR’s not aligned vertically: raceway systems composed of trays and/or
conduits should be installed.
Departments planning to install their own raceway system should be aware that the
standards require all wire be concealed. Fishing the walls, wire mold, and conduit
placement are three methods of concealing wires. The Universitystandard for station
wire is to fish the walls or use wire mold.
However, as part of a long-range structural plan, if conduit to a station jack location is
desired we recommend:
• 1" conduit stubbed and capped for protection in the ceiling with a pull string
• 2" x 4" electrical work box recessed into the wall (junction box is required for
every work area location).
• Mounting height:
o Standard outlet center: 18" AFF (above finished floor)
o Wall outlet center: 54" AFF
o Handicapped wall outlet: 48" AFF
If the conduit transports more than telecommunications, departments may want to
reassess the conduit's size to provide for additional voice or data communications
demands. In any situation where a conduit is being installed, the fill ratio must be
40%.
When installing conduits, if there are more than two 90-degree angle turns in the
conduit, a pullbox is required. When installing a tray as part of an open raceway
system, the tray must be more than one (1) foot from an electrical source (i.e.
fluorescent light).
To facilitate future cable installations a new pull string, tied off at both ends shall be
installed in conduit simultaneously with the pull-in of cable.
External Cable Access
Four (4) four (4) inch conduits with mule-tape with footage markers shall be installed
and tied off in each must be provided by the customer from the building MDF to the
property line or nearest utility manhole.
I. Wire Removal
Cables that are abandoned in ceilings, riser systems, and air handling systems have
always been a source for fueling smoke and fire. The weight of the cabling has also
strained ceiling, raceway, and riser systems. Often times, abandoned cables have
been left behind when new cabling is installed. NEC 2002 Article 770.3(B) for optical
fiber and Article 800.52(B) for communications cabling states that all accessible
abandoned cable, unless marked for future use, must be removed.
The building owner is financially responsible for removing old abandoned cabling. UIS
is available to help coordinate this effort.
J. Asbestos Abatement
The building owner is responsible for asbestos abatement. UIS is available to help
coordinate this effort.
HARVARD UNIVERSITYWireandCable Standards
Quang Dung Technology Distribution Company Page 10 of 32
K. Fire Stopping
• Provide fireproof seals in accordance with the National Fire Protection
Association (NFPA) and the National Electric Code (NEC), Article 200-221 and
EIA/TIA 569 standards.
• Fire stop all penetrations in accordance with the current edition of the National
Electrical Code.
• Do not use concrete for fire stopping on cable trays, wireways or conduit.
Contractors who use this method will be required to replace all cables affected.
[...]... Universitywireandcablestandards They are required to follow the University' s Technical Standards (see Section VI) for wireandcable installation These standards allow installations to be thoroughly tested for accuracy and to provide UIS with the ability to administer the Network effectively Contractors are required to provide an accurate and consistent account of work completed The University. .. gang 1-port face plate shall be Avaya P/N M10L-246, Commcode 108 258 419 Single gang 4-Port faceplates shall be Avaya P/N M14L-246, Commcode 108 168 550 Single gang 2-port 106 style faceplates shall be Siemon P/N DP-S-20 Quang Dung Technology Distribution Company Page 15 of 32 HARVARDUNIVERSITYWireandCableStandards 9 Single gang 2-port 106 style faceplate shall be Ortronics P/N OR-4030025 6-0 9 10... Page 20 of 32 HARVARDUNIVERSITYWireandCableStandards SECTION VII: INTER-BUILDING CABLE (HSDN) The following specifications describe the installation of the fiber optic cable for the HSDN backbone Fiber Optic Cable Composition Fiber optic installation shall consist of a component that contains 12 strand 62.5/125 um multi-mode and 10/125 um 12 strand single mode fiber cable Fiber Optic Cable The following... "Surveying Standardsand Recovery Notes" Warrantee Requirements All material and workmanship must be covered by a warrantee with a duration of at least one year Quang Dung Technology Distribution Company Page 24 of 32 HARVARDUNIVERSITYWireandCableStandards SECTION VIII: GLOSSARY ANSI: American National Standards Institute Administration: correct and consistent use of color, labeling, and numbering... AVAYA 188 wire troughs (for voice and data) will be mounted across the plywood frame between the VOICE and DATA blocks Cross -wire will run down and through the 188 wire troughs for VOICE and up and through for DATA All cross -wire will be supported in 188 wire troughs 12 Station wire will be installed to transmit high-speed data as either ISDN digitized voice and data or standard data (for example; Ethernet... Company Page 14 of 32 HARVARDUNIVERSITYWireandCableStandards All Fiber Optic Cables will be tested using a Optical power meter, measuring end-toend attenuation for all installed cables, including: all splices, terminated fiber; all connector, and patch panels The total loss shall be measured and reported for each cable at the appropriate operation wavelengths, 850 nm, 1300 nm, 1310 nm and 1550 nm Optical... Functional Specifications 10/125 Micron Single-mode Fiber Specification Functional Specifications - Fiber Cable Maximum Attenuation: @ 1300nm 0.4dB/km @ 1550nm 03.dB/km Quang Dung Technology Distribution Company Page 21 of 32 HARVARDUNIVERSITYWireandCableStandards Maximum Dispersion: @ 1290 - 1330nm 2.6psc/nm-km @ 1550nm 20psec/nm-km Cutoff Wavelength 1030 - 1250nm Specified fiber parameters: Mode... directions, end-to-end All Fiber Optic Cables will be tested using the OTDR, making certain to test and record the optical quality of each cable after installation Testing one direction only Provide all printed readings, both before and after installation, so they can be included in the as-built documentation (Applicable to OSP cable, only) SECTION VI TECHNICAL STANDARDS The following technical standards. . .HARVARD UNIVERSITYWireandCableStandards SECTION IV UNIVERSITY INFORMATION SYSTEMS ROLE University Information Systems (UIS) can provide departments with the following assistance to ensure all wireandcable is installed in a thorough and professional manner UIS will work with departments during the entire installation... provide high-quality and economical voice and data services to the University The wireandcablestandards described in this guide have helped to make the Network a reality for the University community Because the Network's architecture complies with international standards, investments in communications technology made by departments are protected and have put Harvard in an ideal position to take advantage .
Network wire and cable standards. Some of the benefits of following wire and cable
standards are:
• By incorporating University Network standards in all wire. wire and cable standards. They are required to follow the
University& apos;s Technical Standards (see Section VI) for wire and cable installation. These
standards