11-1 Chapter 11 HEAT EXCHANGERS Types of Heat Exchangers 11-1C Heat exchangers are classified according to the flow type as parallel flow, counter flow, and crossflow arrangement In parallel flow, both the hot and cold fluids enter the heat exchanger at the same end and move in the same direction In counter-flow, the hot and cold fluids enter the heat exchanger at opposite ends and flow in opposite direction In cross-flow, the hot and cold fluid streams move perpendicular to each other 11-2C In terms of construction type, heat exchangers are classified as compact, shell and tube and regenerative heat exchangers Compact heat exchangers are specifically designed to obtain large heat transfer surface areas per unit volume The large surface area in compact heat exchangers is obtained by attaching closely spaced thin plate or corrugated fins to the walls separating the two fluids Shell and tube heat exchangers contain a large number of tubes packed in a shell with their axes parallel to that of the shell Regenerative heat exchangers involve the alternate passage of the hot and cold fluid streams through the same flow area In compact heat exchangers, the two fluids usually move perpendicular to each other 11-3C A heat exchanger is classified as being compact if β > 700 m2/m3 or (200 ft2/ft3) where β is the ratio of the heat transfer surface area to its volume which is called the area density The area density for doublepipe heat exchanger can not be in the order of 700 Therefore, it can not be classified as a compact heat exchanger 11-4C In counter-flow heat exchangers, the hot and the cold fluids move parallel to each other but both enter the heat exchanger at opposite ends and flow in opposite direction In cross-flow heat exchangers, the two fluids usually move perpendicular to each other The cross-flow is said to be unmixed when the plate fins force the fluid to flow through a particular interfin spacing and prevent it from moving in the transverse direction When the fluid is free to move in the transverse direction, the cross-flow is said to be mixed 11-5C In the shell and tube exchangers, baffles are commonly placed in the shell to force the shell side fluid to flow across the shell to enhance heat transfer and to maintain uniform spacing between the tubes Baffles disrupt the flow of fluid, and an increased pumping power will be needed to maintain flow On the other hand, baffles eliminate dead spots and increase heat transfer rate 11-6C Using six-tube passes in a shell and tube heat exchanger increases the heat transfer surface area, and the rate of heat transfer increases But it also increases the manufacturing costs 11-7C Using so many tubes increases the heat transfer surface area which in turn increases the rate of heat transfer PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-2 11-8C Regenerative heat exchanger involves the alternate passage of the hot and cold fluid streams through the same flow area The static type regenerative heat exchanger is basically a porous mass which has a large heat storage capacity, such as a ceramic wire mash Hot and cold fluids flow through this porous mass alternately Heat is transferred from the hot fluid to the matrix of the regenerator during the flow of the hot fluid and from the matrix to the cold fluid Thus the matrix serves as a temporary heat storage medium The dynamic type regenerator involves a rotating drum and continuous flow of the hot and cold fluid through different portions of the drum so that any portion of the drum passes periodically through the hot stream, storing heat and then through the cold stream, rejecting this stored heat Again the drum serves as the medium to transport the heat from the hot to the cold fluid stream The Overall Heat Transfer Coefficient 11-9C Heat is first transferred from the hot fluid to the wall by convection, through the wall by conduction and from the wall to the cold fluid again by convection 11-10C When the wall thickness of the tube is small and the thermal conductivity of the tube material is high, which is usually the case, the thermal resistance of the tube is negligible 11-11C The heat transfer surface areas are Ai = πD1 L and Ao = πD L When the thickness of inner tube is small, it is reasonable to assume Ai ≅ Ao ≅ As 11-12C No, it is not reasonable to say hi ≈ h0 ≈ h 11-13C When the wall thickness of the tube is small and the thermal conductivity of the tube material is high, the thermal resistance of the tube is negligible and the inner and the outer surfaces of the tube are almost identical ( Ai ≅ Ao ≅ As ) Then the overall heat transfer coefficient of a heat exchanger can be determined to from U = (1/hi + 1/ho)-1 11-14C None 11-15C When one of the convection coefficients is much smaller than the other hi > 1/ho ) and thus U i = U = U ≅ hi 11-16C The most common type of fouling is the precipitation of solid deposits in a fluid on the heat transfer surfaces Another form of fouling is corrosion and other chemical fouling Heat exchangers may also be fouled by the growth of algae in warm fluids This type of fouling is called the biological fouling Fouling represents additional resistance to heat transfer and causes the rate of heat transfer in a heat exchanger to decrease, and the pressure drop to increase 11-17C The effect of fouling on a heat transfer is represented by a fouling factor Rf Its effect on the heat transfer coefficient is accounted for by introducing a thermal resistance Rf /As The fouling increases with increasing temperature and decreasing velocity PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-3 11-18 The heat transfer coefficients and the fouling factors on tube and shell side of a heat exchanger are given The thermal resistance and the overall heat transfer coefficients based on the inner and outer areas are to be determined Assumptions The heat transfer coefficients and the fouling factors are constant and uniform Analysis (a) The total thermal resistance of the heat exchanger per unit length is R= R= + + R fi ln( Do / Di ) R fo 1 + + + + 2πkL hi Ai Ai Ao ho Ao (700 W/m °C)[π (0.012 m)(1 m)] + (0.0005 m °C/W) [π (0.012 m)(1 m)] ln(1.6 / 1.2) (0.0002 m °C/W) + 2π (380 W/m.°C)(1 m) [π (0.016 m)(1 m)] (700 W/m °C)[π (0.016 m)(1 m)] = 0.0837°C/W (b) The overall heat transfer coefficient based on the inner and the outer surface areas of the tube per length are R= Outer surface D0, A0, h0, U0 , Rf0 Inner surface Di, Ai, hi, Ui , Rfi 1 = = UA U i Ai U o Ao Ui = 1 = = 317 W/m °C RAi (0.0837 °C/W)[π (0.012 m)(1 m)] Uo = 1 = = 238 W/m °C RAo (0.0837 °C/W)[π (0.016 m)(1 m)] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-4 11-19 EES Prob 11-18 is reconsidered The effects of pipe conductivity and heat transfer coefficients on the thermal resistance of the heat exchanger are to be investigated Analysis The problem is solved using EES, and the solution is given below "GIVEN" k=380 [W/m-C] D_i=0.012 [m] D_o=0.016 [m] D_2=0.03 [m] h_i=700 [W/m^2-C] h_o=1400 [W/m^2-C] R_f_i=0.0005 [m^2-C/W] R_f_o=0.0002 [m^2-C/W] "ANALYSIS" R=1/(h_i*A_i)+R_f_i/A_i+ln(D_o/D_i)/(2*pi*k*L)+R_f_o/A_o+1/(h_o*A_o) L=1 [m] “a unit length of the heat exchanger is considered" A_i=pi*D_i*L A_o=pi*D_o*L 0.074 R [C/W] 0.07392 0.07085 0.07024 0.06999 0.06984 0.06975 0.06969 0.06964 0.06961 0.06958 0.06956 0.06954 0.06952 0.06951 0.0695 0.06949 0.06948 0.06947 0.06947 0.06946 0.073 R [C/W ] k [W/mC] 10 30.53 51.05 71.58 92.11 112.6 133.2 153.7 174.2 194.7 215.3 235.8 256.3 276.8 297.4 317.9 338.4 358.9 379.5 400 0.072 0.071 0.07 0.069 50 100 150 200 250 300 350 400 k [W /m -C] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-5 hi [W/m2C] 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 R [C/W] 0.085 0.08462 0.0798 0.07578 0.07238 0.06947 0.06694 0.06473 0.06278 0.06105 0.05949 0.0581 0.05684 0.05569 0.05464 0.05368 0.05279 0.05198 0.05122 0.05052 0.04987 0.04926 0.08 ho [W/m2C] 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 R [C/W] R [C/W ] 0.07 0.065 0.06 0.055 0.05 0.045 500 700 900 1100 1300 1500 1800 2000 h i [W /m -C] 0.076 0.074 0.072 R [C/W ] 0.07515 0.0742 0.07334 0.07256 0.07183 0.07117 0.07056 0.06999 0.06947 0.06898 0.06852 0.06809 0.06769 0.06731 0.06696 0.06662 0.06631 0.06601 0.06573 0.06546 0.0652 0.075 0.07 0.068 0.066 0.064 1000 1200 1400 1600 h o [W /m -C] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-6 11-20 A water stream is heated by a jacketted-agitated vessel, fitted with a turbine agitator The mass flow rate of water is to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant Properties The properties of water at 54°C are (Table A-9) k = 0.648 W/m.°C ρ = 985.8 kg/m μ = 0.513 × 10 -3 kg/m ⋅ s Pr = 3.31 The specific heat of water at the average temperature of (10+54)/2=32°C is 4178 J/kg.°C (Table A-9) Analysis We first determine the heat transfer coefficient on the inner wall of the vessel Re = n& D a2 ρ μ = Nu = 0.76 Re hj = (60/60 s -1 )(0.2 m) (985.8 kg/m ) 2/3 0.513 × 10 −3 kg/m ⋅ s Pr 1/ = 0.76(76,865) 2/3 (3.31) = 76,865 1/ = 2048 Water 10ºC k 0.648 W/m.°C Nu = (2048) = 2211 W/m °C Dt 0.6 m The heat transfer coefficient on the outer side is determined as follows 54ºC 54ºC Steam 100ºC ho = 13,100(T g − T w ) −0.25 = 13,100(100 − T w ) −0.25 ho (T g − Tw ) = h j (Tw − 54) 13,100(100 − Tw ) − 0.25 (100 − Tw ) = 2211(Tw − 54) 13,100(100 − Tw ) 0.75 = 2211(Tw − 54) → Tw = 89.2°C ho = 13,100(100 − Tw ) −0.25 = 13,100(100 − 89.2) −0.25 = 7226 W/m ⋅ C Neglecting the wall resistance and the thickness of the wall, the overall heat transfer coefficient can be written as ⎛ 1 ⎞ U =⎜ + ⎟ ⎜ h j ho ⎟ ⎠ ⎝ −1 ⎞ ⎛ =⎜ + ⎟ 2211 7226 ⎝ ⎠ −1 = 1694 W/m ⋅ C From an energy balance [m& c (Tout − Tin )] water = UAΔT m& w (4178)(54 − 10) = (1694)(π × 0.6 × 0.6)(100 − 54) m& w = 0.479 kg/s = 1725 kg/h PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-7 11-21 Water flows through the tubes in a boiler The overall heat transfer coefficient of this boiler based on the inner surface area is to be determined Assumptions Water flow is fully developed Properties of the water are constant Properties The properties of water at 110°C are (Table A-9) ν = μ / ρ = 0.268 × 10 −6 m /s k = 0.682 W/m K Pr = 1.58 Analysis The Reynolds number is Re = V avg D h ν = (3.5 m/s)(0.01 m) 0.268 × 10 − m / s = 130,600 which is greater than 10,000 Therefore, the flow is turbulent Assuming fully developed flow, Nu = and h= hDh = 0.023 Re 0.8 Pr 0.4 = 0.023(130,600) 0.8 (1.58) 0.4 = 342 k Outer surface D0, A0, h0, U0 , Rf0 Inner surface Di, Ai, hi, Ui , Rfi k 0.682 W/m.°C Nu = (342) = 23,324 W/m °C Dh 0.01 m The total resistance of this heat exchanger is then determined from R = Rtotal = Ri + R wall + Ro = ln( Do / Di ) 1 + + 2πkL hi Ai ho Ao ln(1.4 / 1) (23,324 W/m °C)[π (0.01 m)(5 m)] [2π (14.2 W/m.°C)(5 m)] + (8400 W/m °C)[π (0.014 m)(5 m)] = 0.00157°C/W = and R= + 1 ⎯ ⎯→ U i = = = 4055 W/m °C U i Ai RAi (0.00157°C/W)[π (0.01 m)(5 m)] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-8 11-22 Water is flowing through the tubes in a boiler The overall heat transfer coefficient of this boiler based on the inner surface area is to be determined Assumptions Water flow is fully developed Properties of water are constant The heat transfer coefficient and the fouling factor are constant and uniform Properties The properties of water at 110°C are (Table A-9) ν = μ / ρ = 0.268 × 10 −6 m /s k = 0.682 W/m K Pr = 1.58 Analysis The Reynolds number is Re = V avg D h ν = (3.5 m/s)(0.01 m) 0.268 × 10 − m / s = 130,600 which is greater than 10,000 Therefore, the flow is turbulent Assuming fully developed flow, Nu = and h= Outer surface D0, A0, h0, U0 , Rf0 Inner surface Di, Ai, hi, Ui , Rfi hD h = 0.023 Re 0.8 Pr 0.4 = 0.023(130,600) 0.8 (1.58) 0.4 = 342 k k 0.682 W/m.°C Nu = (342) = 23,324 W/m °C Dh 0.01 m The thermal resistance of heat exchanger with a fouling factor of R f ,i = 0.0005 m °C/W is determined from R= R f ,i ln( Do / Di ) 1 + + + 2πkL hi Ai Ai ho Ao R= + 0.0005 m °C/W [π (0.01 m)(5 m)] (23,324 W/m °C)[π (0.01 m)(5 m)] ln(1.4 / 1) + + 2π (14.2 W/m.°C)(5 m) (8400 W/m °C)[π (0.014 m)(5 m)] = 0.00475°C/W Then, R= 1 ⎯ ⎯→ U i = = = 1340 W/m °C U i Ai RAi (0.00475°C/W)[π (0.01 m)(5 m)] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-9 11-23 EES Prob 11-21 is reconsidered The overall heat transfer coefficient based on the inner surface as a function of fouling factor is to be plotted Analysis The problem is solved using EES, and the solution is given below "GIVEN" T_w=110 [C] Vel=3.5 [m/s] L=5 [m] k_pipe=14.2 [W/m-C] D_i=0.010 [m] D_o=0.014 [m] h_o=8400 [W/m^2-C] R_f_i=0.0005 [m^2-C/W] "PROPERTIES" k=conductivity(Water, T=T_w, P=300) Pr=Prandtl(Water, T=T_w, P=300) rho=density(Water, T=T_w, P=300) mu=viscosity(Water, T=T_w, P=300) nu=mu/rho "ANALYSIS" Re=(Vel*D_i)/nu "Re is calculated to be greater than 10,000 Therefore, the flow is turbulent." Nusselt=0.023*Re^0.8*Pr^0.4 h_i=k/D_i*Nusselt A_i=pi*D_i*L A_o=pi*D_o*L R=1/(h_i*A_i)+R_f_i/A_i+ln(D_o/D_i)/(2*pi*k_pipe*L)+1/(h_o*A_o) U_i=1/(R*A_i) 3000 2550 2100 Ui [W/m2C] 2883 2520 2238 2013 1829 1675 1546 1435 1339 1255 1181 1115 1056 1003 955.2 U i [W /m -C] Rf,i [m2C/W] 0.0001 0.00015 0.0002 0.00025 0.0003 0.00035 0.0004 0.00045 0.0005 0.00055 0.0006 0.00065 0.0007 0.00075 0.0008 1650 1200 750 0.0001 0.0002 0.0003 0.0004 0.0005 0.0006 0.0007 0.0008 R f,i [m -C/W ] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-10 11-24 Refrigerant-134a is cooled by water in a double-pipe heat exchanger The overall heat transfer coefficient is to be determined Assumptions The thermal resistance of the inner tube is negligible since the tube material is highly conductive and its thickness is negligible Both the water and refrigerant-134a flow are fully developed Properties of the water and refrigerant-134a are constant Properties The properties of water at 20°C are (Table A-9) ρ = 998 kg/m Cold water D0 ν = μ / ρ = 1.004 × 10 − m /s Di k = 0.598 W/m.°C Pr = 7.01 Analysis The hydraulic diameter for annular space is Dh = Do − Di = 0.025 − 0.01 = 0.015 m Hot R-134a The average velocity of water in the tube and the Reynolds number are V avg = m& ρAc = V avg D h Re = ν m& ⎛ D − Di ρ ⎜π o ⎜ ⎝ = ⎞ ⎟ ⎟ ⎠ = 0.3 kg/s ⎛ (0.025 m) − (0.01 m) (998 kg/m )⎜ π ⎜ ⎝ (0.729 m/s)(0.015 m) 1.004 × 10 − m / s ⎞ ⎟ ⎟ ⎠ = 0.729 m/s = 10,890 which is greater than 4000 Therefore flow is turbulent Assuming fully developed flow, Nu = hD h = 0.023 Re 0.8 Pr 0.4 = 0.023(10,890) 0.8 (7.01) 0.4 = 85.0 k ho = k 0.598 W/m.°C Nu = (85.0) = 3390 W/m °C Dh 0.015 m and Then the overall heat transfer coefficient becomes U= 1 + hi h o = 1 5000 W/m °C + = 2020 W/m °C 3390 W/m °C PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-18 11-45 Oil is heated by water in a 1-shell pass and 6-tube passes heat exchanger The rate of heat transfer and the heat transfer surface area are to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant Properties The specific heat of oil is given to be 2.0 kJ/kg.°C Analysis The rate of heat transfer in this heat exchanger is Q& = [ m& c p (Tout − Tin )] oil = (10 kg/s)(2.0 kJ/kg °C)(46°C − 25°C) = 420 kW The logarithmic mean temperature difference for counter-flow arrangement and the correction factor F are ΔT1 = Th,in − Tc ,out = 80°C − 46°C = 34°C ΔT2 = Th,out − Tc ,in = 60°C − 25°C = 35°C ΔTlm,CF = ΔT1 − ΔT2 34 − 35 = = 34.5°C ln(ΔT1 / ΔT2 ) ln(34 / 35) t − t1 46 − 25 ⎫ = = 0.38 ⎪ T1 − t1 80 − 25 ⎪ ⎬ F = 0.94 T − T2 80 − 60 R= = = 0.95⎪ ⎪⎭ 46 − 25 t − t1 P= Water 80°C 46°C Oil 25°C 10 kg/s 60°C shell pass tube passes Then the heat transfer surface area on the tube side becomes Q& 420 kW ⎯→ As = = = 13.0 m Q& = UAs FΔTlm,CF ⎯ UFΔTlm,CF (1.0 kW/m °C)(0.94)(34.5°C) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-19 11-46 Steam is condensed by cooling water in the condenser of a power plant The mass flow rate of the cooling water and the rate of condensation are to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant Properties The heat of vaporization of water at 50°C is given to be hfg = 2383 kJ/kg and specific heat of cold water at the average temperature of 22.5°C is given to be cp = 4180 J/kg.°C Analysis The temperature differences between the steam and the cooling water at the two ends of the condenser are ΔT1 = Th,in − Tc ,out = 50°C − 27°C = 23°C ΔT2 = Th,out − Tc ,in = 50°C − 18°C = 32°C Steam 50°C 27°C and ΔTlm = ΔT1 − ΔT2 23 − 32 = = 27.3°C ln(ΔT1 / ΔT2 ) ln(23 / 32) Then the heat transfer rate in the condenser becomes Q& = UA ΔT = ( 2400 W/m °C)(42 m )( 27 3°C) = 2752 kW s 18°C lm The mass flow rate of the cooling water and the rate of condensation of steam are determined from Q& = [m& c (T − T )] p m& cooling = water out in Q& c p (Tout − Tin ) = cooling water Water 50°C 2752 kJ/s = 73.1 kg/s (4.18 kJ/kg.°C)(27°C − 18°C) Q& 2752 kJ/s ⎯→ m& steam = = = 1.15 kg/s Q& = (m& h fg ) steam ⎯ h fg 2383 kJ/kg PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-20 11-47 Water is heated in a double-pipe parallel-flow heat exchanger by geothermal water The required length of tube is to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant Properties The specific heats of water and geothermal fluid are given to be 4.18 and 4.31 kJ/kg.°C, respectively Analysis The rate of heat transfer in the heat exchanger is Q& = [ m& c p (Tout − Tin )] water = (0.2 kg/s)(4.18 kJ/kg °C)(60 °C − 25°C) = 29.26 kW Then the outlet temperature of the geothermal water is determined from Q& 29.26 kW ⎯→ Tout = Tin − = 140°C − = 117.4°C Q& = [m& c p (Tin − Tout )]geot.water ⎯ (0.3 kg/s)(4.31 kJ/kg.°C) m& c p The logarithmic mean temperature difference is 60°C ΔT1 = Th ,in − Tc ,in = 140°C − 25°C = 115°C ΔT2 = Th ,out − Tc ,out = 117.4°C − 60°C = 57.4°C and ΔTlm = Brine 140°C ΔT1 − ΔT2 115 − 57.4 = = 82.9°C ln(ΔT1 / ΔT2 ) ln(115 / 57.4) The surface area of the heat exchanger is determined from Q& 29.26 kW ⎯→ As = = = 0.642 m Q& = UAs ΔTlm ⎯ UΔTlm (0.55 kW/m )(82.9°C) Water 25°C Then the length of the tube required becomes ⎯→ L = As = πDL ⎯ As 0.642 m = = 25.5 m πD π (0.008 m) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-21 11-48 EES Prob 11-47 is reconsidered The effects of temperature and mass flow rate of geothermal water on the length of the tube are to be investigated Analysis The problem is solved using EES, and the solution is given below "GIVEN" T_w_in=25 [C] T_w_out=60 [C] m_dot_w=0.2 [kg/s] C_p_w=4.18 [kJ/kg-C] T_geo_in=140 [C] m_dot_geo=0.3 [kg/s] C_p_geo=4.31 [kJ/kg-C] D=0.008 [m] U=0.55 [kW/m^2-C] "ANALYSIS" Q_dot=m_dot_w*C_p_w*(T_w_out-T_w_in) Q_dot=m_dot_geo*C_p_geo*(T_geo_in-T_geo_out) DELTAT_1=T_geo_in-T_w_in DELTAT_2=T_geo_out-T_w_out DELTAT_lm=(DELTAT_1-DELTAT_2)/ln(DELTAT_1/DELTAT_2) Q_dot=U*A*DELTAT_lm A=pi*D*L L [m] 53.73 46.81 41.62 37.56 34.27 31.54 29.24 27.26 25.54 24.04 22.7 21.51 20.45 19.48 18.61 17.81 17.08 16.4 15.78 15.21 14.67 55 50 45 40 L [m ] Tgeo,in [C] 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 35 30 25 20 15 10 100 120 140 160 180 200 T geo,in [C] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-22 L [m] 46.31 35.52 31.57 29.44 28.1 27.16 26.48 25.96 25.54 25.21 24.93 24.69 24.49 24.32 24.17 24.04 23.92 50 45 40 L [m ] mgeo [kg/s] 0.1 0.125 0.15 0.175 0.2 0.225 0.25 0.275 0.3 0.325 0.35 0.375 0.4 0.425 0.45 0.475 0.5 35 30 25 20 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 m geo [kg/s] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-23 11-49E Glycerin is heated by hot water in a 1-shell pass and 8-tube passes heat exchanger The rate of heat transfer for the cases of fouling and no fouling are to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible Heat transfer coefficients and fouling factors are constant and uniform The thermal resistance of the inner tube is negligible since the tube is thin-walled and highly conductive Properties The specific heats of glycerin and water are given to be 0.60 and 1.0 Btu/lbm.°F, respectively Analysis (a) The tubes are thin walled and thus we assume the inner surface area of the tube to be equal to the outer surface area Then the heat transfer surface area of this heat exchanger becomes As = nπDL = 8π (0.5 / 12 ft)(500 ft) = 523.6 ft The temperature differences at the two ends of the heat exchanger are Glycerin 65°F ΔT1 = Th,in − Tc ,out = 175°F − 140°F = 35°F 120°F ΔT2 = Th ,out − Tc ,in = 120°F − 65°F = 55°F and ΔTlm,CF = ΔT1 − ΔT2 35 − 55 = = 44.25°F ln(ΔT1 / ΔT2 ) ln(35 / 55) 175°F The correction factor is t − t1 120 − 175 ⎫ = = 0.5 ⎪ 65 − 175 T1 − t1 ⎪ ⎬ F = 0.70 T1 − T2 65 − 140 R= = = 1.36⎪ ⎪⎭ t − t1 120 − 175 P= Hot Water 140°F In case of no fouling, the overall heat transfer coefficient is determined from U= 1 + hi ho = 50 Btu/h.ft °F + = 3.7 Btu/h.ft °F Btu/h.ft °F Then the rate of heat transfer becomes Q& = UAs FΔTlm,CF = (3.7 Btu/h.ft °F)(523.6 ft )(0.70)(44.25°F) = 60,000 Btu/h (b) The thermal resistance of the heat exchanger with a fouling factor is R= = R fi 1 + + hi Ai Ai ho Ao (50 Btu/h.ft °F)(523.6 ft ) = 0.0005195 h.°F/Btu 2 + 0.002 h.ft °F/Btu 523.6 ft + (4 Btu/h.ft °F)(523.6 ft ) The overall heat transfer coefficient in this case is R= 1 ⎯ ⎯→ U = = = 3.68 Btu/h.ft °F UAs RAs (0.0005195 h.°F/Btu)(523.6 ft ) Then rate of heat transfer becomes Q& = UAs FΔTlm,CF = (3.68 Btu/h.ft °F)(523.6 ft )(0.70)(44.25°F) = 59,680 Btu/h PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-24 11-50 During an experiment, the inlet and exit temperatures of water and oil and the mass flow rate of water are measured The overall heat transfer coefficient based on the inner surface area is to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible Fluid properties are constant Properties The specific heats of water and oil are given to be 4180 and 2150 J/kg.°C, respectively Analysis The rate of heat transfer from the oil to the water is Q& = [ m& c p (Tout − Tin )]water = (3 kg/s)(4.18 kJ/kg °C)(55 °C − 20°C) = 438.9 kW The heat transfer area on the tube side is Ai = nπDi L = 24π (0.012 m)(2 m) = 1.8 m The logarithmic mean temperature difference for counterflow arrangement and the correction factor F are Oil 120°C 55°C ΔT1 = Th,in − Tc ,out = 120°C − 55°C = 65°C ΔT2 = Th ,out − Tc ,in = 45°C − 20°C = 25°C ΔTlm,CF = ΔT1 − ΔT2 65 − 25 = = 41.9°C ln(ΔT1 / ΔT2 ) ln(65 / 25) t − t1 55 − 20 ⎫ = = 0.35 ⎪ T1 − t1 120 − 20 ⎪ ⎬ F = 0.70 T − T2 120 − 45 R= = = 2.14⎪ ⎪⎭ 55 − 20 t − t1 P= 20°C Water kg/s 24 tubes 145°C Then the overall heat transfer coefficient becomes Q& 438.9 kW ⎯→ U i = = = 8.31 kW/m °C Q& = U i Ai FΔTlm,CF ⎯ Ai FΔTlm,CF (1.8 m )(0.70)(41.9°C) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-25 11-51 Ethylene glycol is cooled by water in a double-pipe counter-flow heat exchanger The rate of heat transfer, the mass flow rate of water, and the heat transfer surface area on the inner side of the tubes are to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant Properties The specific heats of water and ethylene glycol are given to be 4.18 and 2.56 kJ/kg.°C, respectively Analysis (a) The rate of heat transfer is Q& = [ m& c (T − T )] p in out Cold Water 20°C glycol = (3.5 kg/s)(2.56 kJ/kg.°C)(80°C − 40°C) = 358.4 kW Hot Glycol 80°C 3.5 kg/s (b) The rate of heat transfer from water must be equal to the rate of heat transfer to the glycol Then, ⎯→ m& water = Q& = [m& c p (Tout − Tin )] water ⎯ = Q& 40°C 55°C c p (Tout − Tin ) 358.4 kJ/s = 2.45 kg/s (4.18 kJ/kg.°C)(55°C − 20°C) (c) The temperature differences at the two ends of the heat exchanger are ΔT1 = Th,in − Tc,out = 80°C − 55°C = 25°C ΔT2 = Th,out − Tc ,in = 40°C − 20°C = 20°C and ΔTlm = ΔT1 − ΔT2 25 − 20 = = 22.4°C ln(ΔT1 / ΔT2 ) ln(25 / 20) Then the heat transfer surface area becomes Q& 358.4 kW ⎯→ Ai = = = 64.0 m Q& = U i Ai ΔTlm ⎯ U i ΔTlm (0.25 kW/m °C)(22.4°C) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-26 11-52 Water is heated by steam in a double-pipe counter-flow heat exchanger The required length of the tubes is to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant Properties The specific heat of water is given to be 4.18 kJ/kg.°C The heat of condensation of steam at 120°C is given to be 2203 kJ/kg Analysis The rate of heat transfer is Q& = [m& c p (Tout − Tin )] water Steam 120°C = (3 kg/s)(4.18 kJ/kg.°C)(80°C − 17°C) = 790.02 kW Water The logarithmic mean temperature difference is ΔT1 = Th ,in − Tc,out = 120° C − 80° C = 40° C ΔT2 = Th ,in − Tc,in = 120° C − 17° C = 103° C ΔTlm = 17°C kg/s 80°C ΔT1 − ΔT2 40 − 103 = = 66.6° C ln( ΔT1 / ΔT2 ) ln(40 / 103) The heat transfer surface area is ⎯→ Ai = Q& = U i Ai ΔTlm ⎯ Q& 790.02 kW = = 7.9 m U i ΔTlm (15 kW / m ° C) (66.6° C) Then the length of tube required becomes ⎯→ L = Ai = πDi L ⎯ Ai 7.9 m = = 100.6 m πDi π (0.025 m) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-27 11-53 Oil is cooled by water in a thin-walled double-pipe counter-flow heat exchanger The overall heat transfer coefficient of the heat exchanger is to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant The thermal resistance of the inner tube is negligible since the tube is thin-walled and highly conductive Properties The specific heats of water and oil are given to be 4.18 and 2.20 kJ/kg.°C, respectively Analysis The rate of heat transfer from the water to the oil is Hot oil 150°C kg/s Cold water Q& = [m& c p (Tin − Tout )] oil 22°C 1.5 kg/s = (2 kg/s)(2.2 kJ/kg.°C)(150°C − 40°C) = 484 kW 40°C The outlet temperature of the water is determined from Q& Q& = [m& c p (Tout − Tin )] water ⎯ ⎯→ Tout = Tin + m& c p = 22°C + 484 kW = 99.2°C (1.5 kg/s)(4.18 kJ/kg.°C) The logarithmic mean temperature difference is ΔT1 = Th,in − Tc ,out = 150°C − 99.2°C = 50.8°C ΔT2 = Th,out − Tc ,in = 40°C − 22°C = 18°C ΔTlm = ΔT1 − ΔT2 50.8 − 18 = = 31.6°C ln(ΔT1 / ΔT2 ) ln(50.8 / 18) Then the overall heat transfer coefficient becomes Q& 484 kW U= = = 32.5 kW/m °C As ΔTlm π (0.025 m)(6 m)(31.6°C) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-28 11-54 EES Prob 11-53 is reconsidered The effects of oil exit temperature and water inlet temperature on the overall heat transfer coefficient of the heat exchanger are to be investigated Analysis The problem is solved using EES, and the solution is given below "GIVEN" T_oil_in=150 [C] T_oil_out=40 [C] m_dot_oil=2 [kg/s] C_p_oil=2.20 [kJ/kg-C] T_w_in=22 [C] m_dot_w=1.5 [kg/s] C_p_w=4.18 [kJ/kg-C] D=0.025 [m] L=6 [m] "ANALYSIS" Q_dot=m_dot_oil*C_p_oil*(T_oil_in-T_oil_out) Q_dot=m_dot_w*C_p_w*(T_w_out-T_w_in) DELTAT_1=T_oil_in-T_w_out DELTAT_2=T_oil_out-T_w_in DELTAT_lm=(DELTAT_1-DELTAT_2)/ln(DELTAT_1/DELTAT_2) Q_dot=U*A*DELTAT_lm A=pi*D*L 55 50 45 40 35 30 32.5 35 37.5 40 42.5 45 47.5 50 52.5 55 57.5 60 62.5 65 67.5 70 U [kW/m2C] 53.22 45.94 40.43 36.07 32.49 29.48 26.9 24.67 22.7 20.96 19.4 18 16.73 15.57 14.51 13.53 12.63 U [kW /m -C] Toil,out [C] 30 25 20 15 10 30 35 40 45 50 55 60 65 T oil,out [C] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 70 11-29 38 36 34 32 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 U [kW/m2C] 20.7 21.15 21.61 22.09 22.6 23.13 23.69 24.28 24.9 25.55 26.24 26.97 27.75 28.58 29.46 30.4 31.4 32.49 33.65 34.92 36.29 U [kW /m -C] Tw,in [C] 30 28 26 24 22 20 13 17 21 25 T w ,in [C] PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-30 11-55 The inlet and outlet temperatures of the cold and hot fluids in a double-pipe heat exchanger are given It is to be determined whether this is a parallel-flow or counter-flow heat exchanger Analysis In parallel-flow heat exchangers, the temperature of the cold water can never exceed that of the hot fluid In this case Tcold out = 50°C which is greater than Thot out = 45°C Therefore this must be a counterflow heat exchanger 11-56 Cold water is heated by hot water in a double-pipe counter-flow heat exchanger The rate of heat transfer and the heat transfer surface area of the heat exchanger are to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant The thermal resistance of the inner tube is negligible since the tube is thin-walled and highly conductive Properties The specific heats of cold and hot water are given to be 4.18 and 4.19 kJ/kg.°C, respectively Analysis The rate of heat transfer in this heat exchanger is Q& = [m& c (T − T )] p out in cold water = (1.25 kg/s)(4.18 kJ/kg.°C)(45°C − 15°C) = 156.8 kW Cold Water 15°C 1.25 kg/s Hot water 100°C kg/s 45°C The outlet temperature of the hot water is determined from Q& 156.8 kW ⎯→ Tout = Tin − = 100°C − = 87.5°C Q& = [m& c p (Tin − Tout )] hot water ⎯ (3 kg/s)(4.19 kJ/kg.°C) m& c p The temperature differences at the two ends of the heat exchanger are ΔT1 = Th ,in − Tc ,out = 100°C − 45°C = 55°C ΔT2 = Th,out − Tc ,in = 87.5°C − 15°C = 72.5°C and ΔTlm = ΔT1 − ΔT2 55 − 72.5 = = 63.3°C ln(ΔT1 / ΔT2 ) ln(55 / 72.5) Then the surface area of this heat exchanger becomes Q& 156.8 kW ⎯→ As = = = 2.81 m Q& = UAs ΔTlm ⎯ UΔTlm (0.880 kW/m °C)(63.3°C) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-31 11-57 Engine oil is heated by condensing steam in a condenser The rate of heat transfer and the length of the tube required are to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant The thermal resistance of the inner tube is negligible since the tube is thin-walled and highly conductive Properties The specific heat of engine oil is given to be 2.1 kJ/kg.°C The heat of condensation of steam at 130°C is given to be 2174 kJ/kg Analysis The rate of heat transfer in this heat exchanger is Q& = [ m& c (T − T )] = (0.3 kg/s)(2.1 kJ/kg °C)(60 °C − 20°C) = 25.2 kW p out in oil The temperature differences at the two ends of the heat exchanger are ΔT1 = Th,in − Tc ,out = 130°C − 60°C = 70°C Steam 130°C ΔT2 = Th,out − Tc ,in = 130°C − 20°C = 110°C Oil and ΔTlm = ΔT1 − ΔT2 70 − 110 = = 88.5°C ln(ΔT1 / ΔT2 ) ln(70 / 110) 60°C 20°C 0.3 kg/s The surface area is Q& 25.2 kW = = 0.44 m As = UΔTlm (0.65 kW/m °C)(88.5°C) Then the length of the tube required becomes ⎯→ L = As = πDL ⎯ As 0.44 m = = 7.0 m πD π (0.02 m) PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission 11-32 11-58E Water is heated by geothermal water in a double-pipe counter-flow heat exchanger The mass flow rate of each fluid and the total thermal resistance of the heat exchanger are to be determined Assumptions Steady operating conditions exist The heat exchanger is well-insulated so that heat loss to the surroundings is negligible and thus heat transfer from the hot fluid is equal to the heat transfer to the cold fluid Changes in the kinetic and potential energies of fluid streams are negligible There is no fouling Fluid properties are constant Properties The specific heats of water and geothermal fluid are given to be 1.0 and 1.03 Btu/lbm.°F, respectively Analysis The mass flow rate of each fluid is determined from Q& = [m& c (T − T )] p m& water = out in Q& c p (Tout − Tin ) = water 40 Btu/s = 0.667 lbm/s (1.0 Btu/lbm.°F)(200°F − 140°F) Q& = [m& c p (Tout − Tin )] geo water m& geo water = Q& c p (Tout − Tin ) = 40 Btu/s = 0.431 lbm/s (1.03 Btu/lbm.°F)(270°F − 180°F) The temperature differences at the two ends of the heat exchanger are ΔT1 = Th ,in − Tc ,out = 270°F − 200°F = 70°F ΔT2 = Th,out − Tc ,in = 180°F − 140°F = 40°F Hot brine and ΔTlm = ΔT1 − ΔT2 70 − 40 = = 53.61°F ln(ΔT1 / ΔT2 ) ln(70 / 40) Cold Water 140°F 180°F 270°F Then Q& 40 Btu/s Q& = UAs ΔTlm ⎯ ⎯→ UAs = = = 0.7462 Btu/s o F ΔTlm 53.61°F U= 1 ⎯ ⎯→ R = = = 1.34 s ⋅ °F/Btu RAs UAs 0.7462 Btu/s.°F PROPRIETARY MATERIAL © 2007 The McGraw-Hill Companies, Inc Limited distribution permitted only to teachers and educators for course preparation If you are a student using this Manual, you are using it without permission ... 11-45 Oil is heated by water in a 1-shell pass and 6-tube passes heat exchanger The rate of heat transfer and the heat transfer surface area are to be determined Assumptions Steady operating conditions... be a counterflow heat exchanger 11-56 Cold water is heated by hot water in a double-pipe counter-flow heat exchanger The rate of heat transfer and the heat transfer surface area of the heat exchanger... to heat transfer and causes the rate of heat transfer in a heat exchanger to decrease, and the pressure drop to increase 11-17C The effect of fouling on a heat transfer is represented by a fouling