Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống
1
/ 35 trang
THÔNG TIN TÀI LIỆU
Thông tin cơ bản
Định dạng
Số trang
35
Dung lượng
2 MB
Nội dung
Power Characteristics of Compound Microgrid Composed from PEFC and WindPower Generation 473 period of step input of 6 kW and 8 kW for 3.9 seconds. If a windpower generator is connected to the micro-grid, many fluctuations in the system response characteristics will occur in a short period. If the power produced by windpower generation is supplied to the micro-grid, the dynamic characteristics of power of the micro-grid will be influenced. Figure 8 (b) shows the analysis result of the response error corresponding to Figure 8 (a). If windpower generator is connected to the grid, the response error will become large as the load of the grid becomes small. It is expected that the power range of the fluctuation of the micro- grid will increase as the output of the windpower generation grows. Therefore, when the load of a micro-grid is small compared with the output of windpower generator, the power supply of the independent micro-grid becomes unstable. 5.2 Load response characteristics of cold region houses Figure 9 (a) shows the power demand pattern of a micro-grid formed from ten individual houses in Sapporo in Japan, and assumes a representative day in February (Narita, 1996). This power demand pattern is the average value of each hour, and the sampling time of analyses and the assumption time are written together on the horizontal axis. As a base load of the power demand pattern shown in Fig. 9 (a), F/C (0) is considered as operation of 2.5 kW constant load. Figure 9 (b) and (c) are the power demand patterns when adding load fluctuations (±1 kW and ±3 kW) to Fig. 9 (a) at random. The variation of the load was decided at random within the limits of the range of fluctuation for every sampling time. Fig. 9. 480s demand model for 10 houses in February in Sapporo WindPower 474 Figure 10 shows the response results of F/C (0) to F/C (6) when windpower generation is connected to the micro-grid and the power load has ±1 kW fluctuations. F/C (0) assumed operation with 2.5 kW constant output, with the result that the response of F/C (0) is much less than 2.5 kW in less than the sampling time of 100 s as shown in Figure 10 (a). This reason is because F/C (0) was less than 2.5 kW with the power of windpower generation. Although the micro-grid assumed in this paper controlled the number of operations of F/C (1) to F/C (7) depending on the magnitude of the load, since the power supply of windpower generation existed, there was no operating time of F/C (7). Fig. 10. Response results of each fuel cell 5.3 Power generation efficiency Figure 11 shows the analysis results of the average power generation efficiency of fuel cell systems for every sampling time. The average efficiency of a fuel cell system is the value averaging the efficiency of F/C (0) to F/C (7) operated at each sampling time. However, the fuel cell system to stop is not included in average power generation efficiency. The average power generation efficiency of Figure 11 (a) is 13.4%, and Figure 10 (b) shows 14.3%. The difference in average efficiency occurs in the operating point of a fuel cell system shifting to the efficient side, when load fluctuations are added to the micro-grid. Thus, if load fluctuations are added to the micro-grid, compared with no load fluctuations, the load factor of the fuel cell system shown in Figure 4 will increase. Power Characteristics of Compound Microgrid Composed from PEFC and WindPower Generation 475 Fig. 11. Results of micro-grid average efficiency Fig. 12. Results of efficiency for each fuel cell WindPower 476 Figure 12 shows the power generation efficiency of each fuel cell in the case of connecting windpower generation to the micro-grid of ±1.0kW of load fluctuation. F/C (0) operated corresponding to a base load has maximum power generation efficiency at all sampling times. Since the number of operations of a fuel cell is controlled by the magnitude of the load added to the micro-grid, the operating time falls in the order of F/C (1) to F/C (6). Moreover, there is no time to operate F/C (7) in this operating condition. The relation between the range of fluctuation of the power load and the existence of windpower generation, and the amount of electricity demand of a representative day is shown Fig. 13. When the load fluctuation of the power is large, although the power demand amount of the micro-grid on a representative day increases slightly, it is less than 2%. Moreover, when installing windpower generation, the power demand amount of the micro- grid of a representative day decreases compared with the case of not installing. This decrement is almost equal to the value that integrated the power (average of 0.75 kW) supplied to a grid by the windpower generation of Fig. 4 (b). Fig. 13. Amount of 480s demand model with power fluctuation and windpower generation Figure 14 shows the range of fluctuation of power load and the existence of windpower generation, and the relation to city gas consumption on a representative day of the micro- grid. If the range of fluctuation of the power load becomes large, city gas consumption will decrease. This is because electric power supply cannot follow the load fluctuations of the micro-grid if the range of fluctuation of the power load is large. Moreover, in ±3 kW of load fluctuation, some loads become zero (it sees from 20s to 100s of sampling times) and city gas consumption lowers. In ±3 kW of load fluctuation of the power, it is expected that the power of a micro-grid is unstable and introduction to a real system is not suitable. Power Characteristics of Compound Microgrid Composed from PEFC and WindPower Generation 477 Fig. 14. Analysis result of town gas consumption for 480s demand model with power fluctuation and windpower generation 6. Conclusions A 2.5 kW fuel cell was installed in a house linked to a micro-grid, operation corresponding to a base load was conducted, and the dynamic characteristics of the grid when installing a 1 kW fuel cell system in seven houses were investigated by numerical analysis. A windpower generator outputted to a micro-grid at random within 1.5 kW was installed, and the following conclusions were obtained. 1. Although the settling time (time to converge on ±5% of the target output) of the micro- grid differs with the magnitude of the load, and the parameters of the controller, it is about 4 seconds. 2. When connecting a windpower generator to the micro-grid, the instability of the power of the grid due to supply-and-demand difference is an issue. This issue is remarkable when the load of an independent micro-grid is small compared to the production of electricity of unstable windpower generation. 3. When windpower equipment is connected to the micro-grid with load fluctuation, the operating point of the fuel cell system may shift and power generation efficiency may improve. 7. Acknowledgements This work was partially supported by a Grant-in-Aid for Scientific Research(C) from the JSPS.KAKENHI (17510078). 8. Nomenclature Act : ‘’ If “ action WindPower 478 Act_FC : Each fuel cell operation F /C : Fuel cell h : Capacity of generation W I : Integral parameter P : Proportionality parameter PI : Proportion integration control u : Power load of a micro-grid W ν : Power output W 9. References Abu-Sharkh, S.; Arnold, R. J.; Kohler, J.; Li, R.; Markvart, T.; Ross, J. N.; Steemers, K.; Wilson, P. & Yao, R. (2006). Can microgrids make a major contribution to UK energy supply?. Renewable and Sustainable Energy Reviews, Vol. 10, No. 2, pp. 78-127. Carlos, A. & Hernandez, A. (2005). Fuel consumption minimization of a microgrid. IEEE Transactions on Industry Applications, Vol. 41, No. 3, pp. 673- 681. Ibe, S.; Shinke, N.; Takami, S.; Yasuda, Y.; Asatsu, H. & Echigo, M. (2002). Development of Fuel Processor for Residential Fuel Cell Cogeneration System, Proc. 21 th Annual Meeting of Japan Society of Energy and Resources, pp. 493-496, Osaka, June 12-13, ed., Abe, K. (in Japanese) Kyoto Denkiki Co., Ltd. A system connection inverter catalog and an examination data sheet, 2001. Lindstrom, B. & Petterson, L. (2003). Development of a methanol fuelled reformer for fuel cell applications, J. Power Source, Vol. 118, pp. 71-78. Nagano, S. (2002). Plate-Type Methanol Steam Reformer Using New Catalytic Combustion for a Fuel Cell. Proceedings of SAE Technical Paper Series, Automotive Eng. pp. 10. Narita, K. (1996). The Research on Unused Energy of the Cold Region City and Utilization for the District Heat and Cooling. Ph.D. thesis, Hokkaido University, Sapporo. (in Japanese) Obara, S. & Kudo, K. (2005). Installation Planning of Small-Scale Fuel Cell Cogeneration in Consideration of Load Response Characteristics (Load Response Characteristics of Electric Power Output). Transactions of the Japan Society of Mechanical Engineers, Series B; Vol. 71, No.706, pp. 1678-1685. (in Japanese) Obara, S. & Kudo, K. (2005). Study on Small-Scale Fuel Cell Cogeneration System with Methanol Steam Reforming Considering Partial Load and Load Fluctuation. Transactions of the ASME, Journal of Energy Resources Technology, Vol. 127, pp. 265- 271. Oda, K.; Sakamoto, S.; Ueda, M.; Fuji, A. & Ouki, T. (1999). A Small-Scale Reformer for Fuel Cell Application. Sanyo Technical Review, Vol. 31, No. 2, pp. 99-106, Sanyo Electric Co., Ltd., Tokyo, Japan. (in Japanese) Robert, H. (2004). Microgrid: A conceptual solution. Proceedings of the 35th Annual IEEE Power Electronics Specialists Conference, Vol. 6, pp. 4285-4290. Takeda, Y.; Iwasaki, Y.; Imada, N. & Miyata, T. (2004). Development of Fuel Processor for Rapid Start-up, Proc. 20 th Energy System Economic and Environment Conference, Tokyo, January 29-30, ed., K. Kimura, pp. 343-344. (in Japanese) 21 Large Scale Integration of WindPower in Thermal Power Systems Lisa Göransson and Filip Johnsson Chalmers University of Technology Sweden 1. Introduction This chapter discusses and compares different modifications of wind-thermal electricity generation systems, which have been suggested for the purpose of handling variations in windpower generation. Windpower is integrated into our electricity generation systems to decrease the amount of carbon dioxide emissions associated with the generation of electricity as well as to enhance security of supply. However, the electricity generated by wind varies over time whereas thermal units are most efficient if run continuously at rated power. Thus, depending on the characteristics of the wind-thermal system, part of the decrease in emissions realized by windpower is offset by a reduced efficiency in operation of the thermal units as a result of the variations in generation from wind. This chapter discusses the extent to which it is possible to improve the ability of a wind-thermal system to manage such variations. The first part of the chapter deals with the nature of the variations present in a wind-thermal power system, i.e. variations in load and windpower generation, and the impact of these variations on the thermal units in the system. The second part of the chapter investigates and evaluates options to moderate variations from windpower by integrating different types of storage such as pumped hydro power, compressed air energy storage, flow batteries and sodium sulphur batteries. In addition, the option of interconnecting power systems in a so called “supergrid” is discussed as well as to moderate windpower variations by managing the load on the thermal units through charging and discharging of plug-in hybrid electric vehicles. Data from the powersystem of western Denmark is used to illustrate various aspects influencing the ability of a powersystem to accommodate wind power. Western Denmark was chosen primarily due to its current high windpower grid penetration level (24% in 2005 (Ravn 2001; Eltra 2005)) and that data from western Denmark is easily accessible through Energinet (2006). 2. Impact of windpower variations on thermal plants The power output of a single wind turbine can vary rapidly between zero and full production. However, since the power generated by one turbine is small relative to the capacity of a thermal unit, such fluctuations have negligible impacton the generation pattern of the thermal units in the overall system. With several wind farms in a powerWindPower 480 system, the total possible variation in power output can add up to capacities corresponding to the thermal units and influence the overall generation pattern. At times of low wind speeds, some thermal unit might for example need to be started. The power output of the aggregated windpower is, however, quite different from the power output of a single turbine. Wind speeds depend on weather patterns as well as the landscape around the wind turbines (i.e. roughness of the ground, sea breeze etc.). Thus, the greater the difference in weather patterns and environmental conditions between the locations of the wind turbines, the lower the risk of correlation in power output. In a powersystem with geographically dispersed wind farms, the effect of local environmental conditions onpower output will be reduced. Since it takes some time for a weather front to pass a region, the effect of weather patterns will be delayed from one farm to another, and the alteration in aggregated power output thus takes place over a couple of hours rather than instantaneously. This effect is referred to as power smoothing (Manwell et al. 2005). Western Denmark is a typical example of a region with dispersed windpower generation. The aggregated windpower output for this region during one week in January can be found in Figure 1. As seen in Figure 1, variations in the range of the capacity of thermal units do occur (e.g. between 90 hours and 100 hours the windpower generation decreases with 1 000MW), but the increase or decrease in power over such range takes at least some hours (e.g. approximately 10 hours for the referred to example ). 2.1 Variations in load and windpower generation Figure 2 illustrates the variations in total load (electricity consumption) in western Denmark during the same week as shown in Figure 1. As seen, the amplitude of the windpower variations at current windpower grid penetration (i.e. 24%) and the variations in load are not much different. However, there are two aspects of windpower variations which make these more complicated to manage than fluctuations in load; the unpredictability and the irregularity. Since the total load variations are predictable, it is possible to plan the scheduling of the thermal units to compensate for the load variations. The unpredictability of windpower makes it difficult to accurately schedule units with long start-up times. Variations in a system dominated by base load units create a need for what is here referred to as moderator which is a unit in the powersystem with the ability to reallocate power in time, such as a storage unit or import/export capacity. Since the total load variations are regular, to manage these a moderator would only need to have “storage” capacity which can displace one such variation at a time (i.e. absorb power for a maximum of 12 hours and then deliver this power to the system). Due to the irregularity of windpower variations “storage” capacities of a moderator for this application need to be more extensive than if variations were regular. For the thermal units it is obviously the aggregated impact of the windpower and the total load which is of importance. The load on the thermal units (i.e. the total load reduced by the windpower generation) will become both less predictable and less regular as windpower is introduced to the system. In the Nordic countries, there is some correlation between wind speeds and electric load in the summer, but no correlation of significance in winter time (Holttinen 2005). However, a decrease/increase in windpower output might obviously coincide with an increase/decrease in demand at any time of the year, resulting in large variations in load on the thermal units. At times when windpower output is high and demand is low, systems with windpower in the range of 20% grid penetration or higher Large Scale Integration of WindPower in Thermal Power Systems 481 might face situations where power generation exceeds demand (although this obviously depends on the extent of the variations in load). Without a moderator in the system, which can displace the excess power in time, some of the windpower generated will have to be curtailed in such situations. With base load capacity in the system which has to run continuously, situations where curtailment cannot be avoided will arise more frequently 1 . 0 500 1000 1500 2000 2500 0 20 40 60 80 100 120 140 160 180 Time of the week [hours] Windpower generation [MW] Fig. 1. Windpower generation in western Denmark during the first week in January 2005. Source (Energinet 2006) 1500 2000 2500 3000 3500 4000 0 20 40 60 80 100 120 140 160 180 Time of the week [hours] Total load [MW] Fig. 2. Total load in western Denmark the first week in January 2005. Source (Energinet 2006) 2.2 Response to variations in windpower generation and electricity consumption Variations in load in a wind-thermal powersystem that uses no active strategy for variation management can be managed in three different ways; • by part load operation of thermal units, • by starting/stopping thermal units or • by curtailing wind power. The choice of variation management strategy depends on the properties of the thermal units which are available for management (e.g. in order to choose to stop a unit it obviously has to 1 It should be pointed out that the Nordic system (Nordpool electricity market) of which western Denmark is part, is special in the context of windpower integration, since variations in windpower can, to a certain extent, be managed by hydropower (with large reservoirs). WindPower 482 be running) and the duration of the variation. In a powersystem where cost is minimized, the variation management strategy associated with the lowest cost is obviously chosen. If, for example, the output of windpower and some large base load unit exceeds demand for an hour, curtailment of windpower (or possibly some curtailment in combination with part load of the thermal unit) might be the solution associated with the lowest total system cost. If the same situation lasts for half a day, stopping the thermal unit might be preferable from a cost minimizing perspective. To be able to take variation management decisions into account in the dispatch of units, knowledge of the start-up and part load properties of the thermal units is necessary. Two aspects of the start-up of thermal units will have an immediate impacton the scheduling of the units; the start-up time and the start-up cost. The start-up time is either measured as the time it takes to warm up a unit before it reaches such a state that electricity can be delivered to the grid (time for synchronization) or as the time before it delivers at rated power (time until full production). In both cases, the start-up time ultimately depends on the capacity of the unit, the power plant technology and the time during which the unit has been idle. Small gas turbines have relatively short start-up times, in the range of 15 minutes, and large steam turbines have long start-up times, in the range of several hours. If a large unit has been idle for a few hours, materials might still be warm and the start-up time can be reduced. Table 1 presents the required start-up times of units in the Danish power system. The costs associated with starting a thermal unit are a result of the cost of the fuel required during the warm-up phase and the accelerated component aging due to the stresses on the plant from temperature changes. Lefton et al. (1995) have shown that the combined effect of creep, due to base load operation, and fatigue, due to cycling (start-up/shutdown and load following operation), can significantly reduce the lifetime of materials commonly used in fossil fuel power plants in comparison to creep alone. They estimate the cycling costs (the cost to stop and then restart a unit) of a conventional fossil power plant to $1 500-$500 000 per cycle (around EUR 1 170-400 000) with the range corresponding to differences in cycling ability of different technologies and the duration of the stop. These costs include the cost of increased maintenance, as well as an increase in total system costs due to lower availability of cycled units, and an increase in engineering costs to adapt units to the new situation (i.e. improve the cycling ability). Table 1. Maximum allowed starting time for power plants in the Danish powersystem with nominal maximum power above 25 MW. Source: (Energinet 2007). One alternative to shutting down and restarting a thermal unit is to reduce the load in one or several units. The load reduction in each unit is restricted by the maximum load turn- down ratio. The minimum load level of a thermal unit depends on the power plant technology and the fuel used in combustion units. The minimum load level on the Danish [...]... managing windpower The storage would then consume some of the excess windpower generated at times of high windpower generation levels and return this power to the system at times of low windpower generation levels Literature presents thorough evaluations on the interaction between windpower (i.e a wind farm) and one storage unit Particularly well covered is the interaction between windpower and... emissions with 11% (Göransson & Johnsson 2009b) Figure 5b shows the start-up and part load emissions of the power systems The start-up and part load emissions are higher in the system with 4 748 MW windpower capacity than in the system with 2 374 MW windpower capacity due to the greater system variations in the 4 748 MW windsystem compared to the 2 374 MW windsystem The major part of the reduction... 34(4): 1040-1049 Göransson, L and F Johnsson (2009b) "Moderating power plant cycling in wind- thermal power systems." Submitted Göransson, L., F Johnsson, et al (2009) "Integration of plug-in hybrid electric vehicles in a regional wind- thermal power system. " Submitted Holttinen, H (2005) "Impact of hourly windpower variations on the system operation in the Nordic countries." Wind Energy 8(2): 197-218... electricity consumption [%] Fig 8 Impacton CO2-emissions due to PHEV integration as obtained from the simulations of an isolated wind- thermal power system (vehicle emissions not included) Average system emissions in the system without PHEV:s are 649kgCO2/MWh, thus, in the plot 1% is equivalent to 6.49kg/MWh Source: (Göransson et al 2009) Large Scale Integration of WindPower in Thermal Power Systems 493... windpower capacity (‘‘without wind ’, ‘‘current wind ’ corresponding to around 20% windpower grid penetration and ‘‘34% wind ’ with 34% windpower grid penetration) from simulations of three weeks in July 2005 (Göransson & Johnsson 2009a) As can be seen in Figure 4, the dominating trend is a decrease in import and an increase in export as the windpower capacity in the system increases 484 Wind Power. .. technical solutions for this concern already exist in some wind turbine manufacturers Isolated windy power systems with traditional frequency control problems are the typical example for the privileged application of this recent functionality of the wind turbines 3.2 Windpower control, curtailment and overcapacity The replacement of large conventional power plants by hundreds of wind generation units spread... Curtailed windpower [GWh/year] 1200 2374MW WP daily 2374MW WP weekly 1000 4748MW WP daily 4748MW WP weekly 800 600 400 200 0 0 500 1000 150 0 2000 Moderating capacity [MW] Fig 5 Impact of moderator power rating and capacity on a: total system emissions, b: startup and part load emissions and c: windpower curtailment Source: (Göransson & Johnsson 2009b) Large Scale Integration of WindPower in Thermal Power. .. demand, the variations in windpower exceed the variations in load and, since the variations in windpower often are of longer duration (i.e there can be strong winds affecting a region for more than 12 hours), power or load has to be shifted over longer time spans As mentioned above, a weekly balanced moderator (typically pumped hydro or transmission) would be suitable for a wind- thermal system in this... distribution system operator level and the introduction of wind generation aggregation agents is already enabling to develop and implement the concept of Virtual WindPower Plants It should be noted, however, this concept is much more powerful than just the aggregation of wind generation, this later almost a logical procedure having into consideration its spatial distribution and the cancellation of the... power rating By shifting the windpower generation in time so that the correlation between load and windpower generation is improved, the moderator enables a shift from thermal power to windpower Avoiding 1 000 GWh of wind curtailment per year corresponds to a decrease in system emissions with 0.60 Mtonnes/year2 A decrease of this magnitude is realised in the 4 748 MW windsystem by a 2 000 MW weekly . electricity consumption of PHEV:s correspond to some 12 % of the electricity consumption, wind power curtailment in a system with 20% wind power can be completely avoided. 3.2.1 Impact on a wind- thermal. power generation, and the impact of these variations on the thermal units in the system. The second part of the chapter investigates and evaluates options to moderate variations from wind power. 2006) 2.2 Response to variations in wind power generation and electricity consumption Variations in load in a wind- thermal power system that uses no active strategy for variation management