UFC 3-410-02A
15 May 2003
UNIFIED FACILITIES CRITERIA (UFC)
HEATING, VENTILATING, AND AIR
CONDITIONING (HVAC) CONTROL
SYSTEMS
APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED
UFC 3-410-02A
15 May 2003
1
UNIFIED FACILITIES CRITERIA (UFC)
HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) CONTROLSYSTEMS
Any copyrighted material included in this UFC is identified at its point of use.
Use of the copyrighted material apart from this UFC must have the permission of the
copyright holder.
U.S. ARMY CORPS OF ENGINEERS (Preparing Activity)
NAVAL FACILITIES ENGINEERING COMMAND
AIR FORCE CIVIL ENGINEER SUPPORT AGENCY
Record of Changes (changes are indicated by \1\ /1/)
Change No. Date Location
This UFC supersedes TI 810-11, dated 30 November 1998. The format of this UFC does not
conform to UFC 1-300-01; however, the format will be adjusted to conform at the next revision.
The body of this UFC is a document of a different number.
UFC 3-410-02A
15 May 2003
2
FOREWORD
\1\
The Unified Facilities Criteria (UFC) system is prescribed by MIL-STD 3007 and provides
planning, design, construction, sustainment, restoration, and modernization criteria, and applies
to the Military Departments, the Defense Agencies, and the DoD Field Activities in accordance
with
USD(AT&L) Memorandum dated 29 May 2002. UFC will be used for all DoD projects and
work for other customers where appropriate. All construction outside of the United States is
also governed by Status of forces Agreements (SOFA), Host Nation Funded Construction
Agreements (HNFA), and in some instances, Bilateral Infrastructure Agreements (BIA.)
Therefore, the acquisition team must ensure compliance with the more stringent of the UFC, the
SOFA, the HNFA, and the BIA, as applicable.
UFC are living documents and will be periodically reviewed, updated, and made available to
users as part of the Services’ responsibility for providing technical criteria for military
construction. Headquarters, U.S. Army Corps of Engineers (HQUSACE), Naval Facilities
Engineering Command (NAVFAC), and Air Force Civil Engineer Support Agency (AFCESA) are
responsible for administration of the UFC system. Defense agencies should contact the
preparing service for document interpretation and improvements. Technical content of UFC is
the responsibility of the cognizant DoD working group. Recommended changes with supporting
rationale should be sent to the respective service proponent office by the following electronic
form:
Criteria Change Request (CCR). The form is also accessible from the Internet sites listed
below.
UFC are effective upon issuance and are distributed only in electronic media from the following
source:
• Whole Building Design Guide web
site http://dod.wbdg.org/.
Hard copies of UFC printed from electronic media should be checked against the current
electronic version prior to use to ensure that they are current.
AUTHORIZED BY:
______________________________________
DONALD L. BASHAM, P.E.
Chief, Engineering and Construction
U.S. Army Corps of Engineers
______________________________________
DR. JAMES W WRIGHT, P.E.
Chief Engineer
Naval Facilities Engineering Command
______________________________________
KATHLEEN I. FERGUSON, P.E.
The Deputy Civil Engineer
DCS/Installations & Logistics
Department of the Air Force
______________________________________
Dr. GET W. MOY, P.E.
Director, Installations Requirements and
Management
Office of the Deputy Under Secretary of Defense
(Installations and Environment)
TI 810-11
30 November 1998
Technical Instructions
Heating, Ventilating, and
Air Conditioning (HVAC)
Control Systems
Headquarters
U.S. Army Corps of Engineers
Engineering and Construction Division
Directorate of Military Programs
Washington, DC 20314-1000
CEMP-E TI 810-11
30 November 1998
TECHNICAL INSTRUCTIONS
HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) CONTROL SYSTEMS
Any copyrighted material included in this document is identified at its point of use.
Use of the copyrighted material apart from this document must have the permission of the copyright
holder.
Approved for public release; distribution is unlimited.
Record of Changes (changes indicated \1\ /1/ )
No. Date Location
This Technical Instruction covers material previously contained in TM 5-815-3,
dated July 1991
.
CEMP-E TI 810-11
30 November 1998
FOREWORD
These technical instructions (TI) provide design and construction criteria and apply to all U.S.
Army Corps of Engineers (USACE) commands having military construction responsibilities. TI
will be used for all Army projects and for projects executed for other military services or work
for other customers where appropriate.
TI are living documents and will be periodically reviewed, updated, and made available to
users as part of the HQUSACE responsibility for technical criteria and policy for new military
construction. CEMP-ET is responsible for administration of the TI system; technical content of
TI is the responsibility of the HQUSACE element of the discipline involved. Recommended
changes to TI, with rationale for the changes, should be sent to HQUSACE, ATTN: CEMP-ET,
20 Massachusetts Ave., NW, Washington, DC 20314-1000.
TI are effective upon issuance. TI are distributed only in electronic media through the
TECHINFO Internet site http://www.hnd.usace.army.mil/techinfo/index.htm and the
Construction Criteria Base (CCB) system maintained by the National Institute of Building
Sciences at Internet site http://www.nibs.org/ccb/. Hard copies of these instructions produced
by the user from the electronic media should be checked against the current electronic version
prior to use to assure that the latest instructions are used.
FOR THE COMMANDER:
DWIGHT A. BERANEK, P.E.
Chief, Engineering and Construction Division
for Military Programs
CEMP-E TI 810-11
30 November 1998
i
HEATING, VENTILATING AND AIR CONDITIONING (HVAC) CONTROL SYSTEMS
Table of Contents
Page
CHAPTER 1. GENERAL
Paragraph 1. Purpose 1-1
2. Scope 1-1
3. References 1-1
4. Policy 1-1
5. Control system designer guidance 1-1
6. Design concept 1-2
7. DDC versus SLDC 1-2
8. Control system standards 1-5
9. Project implementation 1-7
10. Design package requirements for HVACcontrolsystems 1-8
11. EMCS interface with standard local control panels 1-10
12. Fan starter control circuit override by external controlsystems 1-13
13. Coordination with HVAC system balancing 1-13
14. Symbols 1-13
15. Explanation of terms 1-13
CHAPTER 2. HVACCONTROL SYSTEM EQUIPMENT, EQUIPMENT USES AND HVACCONTROL
LOOPS
Paragraph 1. General 2-1
2. Control system operating modes and process variables 2-1
3. Control system equipment 2-2
4. Control loops 2-14
CEMP-E TI 810-11
30 November 1998
ii
Table of Contents (cont’d)
5. Open control loops 2-14
6. Closed control loops 2-14
7. Application of open-loop control and closed-loop control to HVAC systems. 2-15
8. Typical control modes 2-15
9. Standard HVAC system control loops 2-20
10. Sizing and selection of control system devices 2-20
11. Sizing of the air compressor motor 2-20
12. Determination of control valve flow coefficient (K / C ) 2-22
v v
13. Calculation of liquid control valve flow coefficient (K / C ) 2-22
v v
14. Calculation of steam control valve flow coefficient (K / C ) 2-25
v v
15. Determining valve actuator close-off pressure ratings 2-29
16. Surge protection provisions for transmitter and control wiring 2-30
CHAPTER 3. STANDARD CONTROL LOOPS
Paragraph 1. General 3-1
2. Cooling coil temperature control loop 3-1
3. Outside air preheat coil temperature control loop 3-1
4. Heating coil temperature control loop 3-2
5. Mixed air temperature and economizer control loops 3-5
6. Minimum outside air control loop for VAV HVACsystems 3-7
7. Supply duct static pressure control loop 3-9
8. Return fan volume control loop 3-9
9. Humidifier control loop 3-11
10. The typical schematic 3-11
11. The typical ladder diagram 3-11
CEMP-E TI 810-11
30 November 1998
iii
Table of Contents (cont’d)
12. The typical equipment schedule 3-12
13. The typical data terminal strip (DTS) layout 3-13
CHAPTER 4. STANDARD HVACCONTROL SYSTEMS
Paragraph 1. General 4-1
2. Identification of control system devices 4-1
3. Project specific drawings 4-1
4. Space temperature controlled perimeter radiation control system 4-2
5. Unit heater temperature control system 4-2
6. Gas-fired infrared heater control system 4-2
7. Small packaged unitary system control system 4-3
8. Dual-temperature fan coil unit control system 4-3
9. Controlsystems that require control panels 4-4
10. Standard single-loop controller HVACcontrol panel 4-4
11. Central plant steam hydronic heating control system 4-6
12. Single building hydronic heating with hot water boiler control system 4-8
13. Central plant high-temperature hot water hydronic heating control system .4-10
14. Central plant steam dual-temperature hydronic control system 4-13
15. Central plant high-temperature hot water dual-temperature hydronic
control system 4-15
16. Single building dual-temperature hydronic control system 4-17
17. Heating and ventilating control system 4-20
18. Multizone HVACcontrol system with return fan 4-23
19. Dual-duct HVACcontrol system with return fan 4-28
20. Bypass multizone HVACcontrol system with return fan 4-32
21. Variable air volume (VAV) HVACcontrol system without return fan 4-37
CEMP-E TI 810-11
30 November 1998
iv
Table of Contents (cont’d)
22. Variable air volume (VAV) HVACcontrol system with return fan 4-42
23. Single zone HVACcontrol system 4-47
24. Dual-temperature coil single zone HVACcontrol system 4-51
25. Single zone HVACcontrol system with humidity control 4-56
26. Single zone HVACcontrol system with direct-expansion (DX) cooling coil .4-60
CHAPTER 5. CONTROL SYSTEM DESIGN VARIATIONS
Paragraph 1. General 5-1
2. Control system variations for 100-percent outside air (continuous
operation) 5-1
3. Control system variations for exhaust fans 5-2
4. Control system variations for smoke dampers 5-2
5. Control system variations for variable speed drives 5-3
6. Control system variations for steam preheat coil with face and bypass
damper 5-4
7. Control system variation for hot water or glycol preheat coil 5-4
8. Control system variation for combining hydronic system and air system
controls in the same control panel 5-4
9. Unoccupied mode space temperature setback control for terminal units 5-4
10. Control system variations for 2-way shutoff valves for fan coil units 5-4
11. Control system variation for building purge / flush cycle. 5-5
12. Control system variations for EMCS initiated building purge and
recirculation modes 5-5
13. Control system variations for smoke control and freeze protection 5-6
14. Control system variations for non-economizer HVACsystems 5-6
15. Control system variations for dual steam valves 5-7
16. Control system variations for hydronic systems with boilers requiring
constant flow 5-7
[...]... the HVACcontrol system (4) Control systems for HVAC often require connections to boiler control systems, chiller control systems, variable speed drives, fire alarm and smoke detection systems, and EMCS The schematic and the ladder diagram will show the interface points between field installed HVACcontrol systems, factory installed HVAC control systems, and other control systems (5) The ladder diagram... diagram for single zone HVAC system with humidity controlControl system equipment for single zone HVAC system with humidity controlControl panel interior door layout for single zone HVAC system with humidity controlControl panel back panel layout for single zone HVAC system with humidity controlControl panel terminal block layout for single zone HVAC system with humidity control DDC control system schematic... dual-duct HVAC system DDC control system schematic for dual-duct HVAC system DDC control system ladder diagram for dual-duct HVAC system DDC control system equipment for dual-duct HVAC system DDC control system I/O table and data terminal strip layout for dual-duct HVAC system Control system schematic for bypass multizone HVAC system Control system ladder diagram for bypass multizone HVAC system Control. .. heater temperature control system Small packaged unitary system control system Dual-temperature fan coil unit temperature control system Standard wall-mounted HVACcontrol panel arrangement Section "A-A" through standard HVACcontrol panel Standard HVACcontrol panel interior door Standard HVACcontrol panel back panel layout Standard HVACcontrol panel terminal block assignments Controller wiring Supply... for single zone HVAC system with humidity control DDC control system ladder diagram for single zone HVAC system with humidity control DDC control system equipment for single zone HVAC system with humidity control DDC control system I/O table and data terminal strip layout for single zone HVAC system with humidity controlControl system schematic for single zone HVAC system with DX coil Control system... schematic for multizone HVAC system Control system ladder diagram for multizone HVAC system Control system equipment for multizone HVAC system Control panel interior door layout for multizone HVAC system Control panel back panel layout for multizone HVAC system Control panel terminal block layout for multizone HVAC system DDC control system schematic for multizone HVAC system DDC control system ladder... multizone HVAC system Control panel interior door layout for bypass multizone HVAC system Control panel back panel layout for bypass multizone HVAC system Control panel terminal block layout for bypass multizone HVAC system DDC control system schematic for bypass multizone HVAC system DDC control system ladder diagram for bypass multizone HVAC system DDC control system equipment for bypass multizone HVAC. .. for single-zone HVAC system without economizer control mode Control panel interior door layout for single-zone HVAC system without economizer control mode Control panel back panel layout for single-zone HVAC system without economizer control mode Control panel terminal block layout for single-zone HVAC system without economizer control mode DDC control system schematic for single-zone HVAC system without... Humidity controls (8) Smoke dampers in HVAC supply air and return air ducts (9) Override of control of valves and dampers for freeze protection or smoke control systems (10) Startup and shutdown of HVAC fan systems by external systems such as smoke control (11) Variable speed fan drives (12) Combining systems in a common control panel (13) Unoccupied mode space temperature setback control of HVAC equipment... 4-19d 4-19e 4-19f DDC control system I/O table and data terminal strip layout for multizone HVAC system Control system schematic for dual-duct HVAC system Control system ladder diagram for dual-duct HVAC system Control system equipment for dual-duct HVAC system Control panel interior door layout for dual-duct HVAC system Control panel back panel layout for dual-duct HVAC system Control panel terminal . for each HVAC control system. The designer will not depend on any HVAC control system vendor for the design of the HVAC control systems. c. Control system vendor compliance. The HVAC control system. Open control loops 2-14 6. Closed control loops 2-14 7. Application of open-loop control and closed-loop control to HVAC systems. 2-15 8. Typical control modes 2-15 9. Standard HVAC system control. volume (VAV) HVAC control system with return fan 4-42 23. Single zone HVAC control system 4-47 24. Dual-temperature coil single zone HVAC control system 4-51 25. Single zone HVAC control system