FRENIC LIFT Starting guide Starting guide FRENIC Lift Dedicated Inverter for Lift Applications 3 ph 400V 4 0 kW 45 kW 3 ph 200V 5 5 kW 22 kW 1 ph 200V 2 2 kW SG Lift EN 1 8 0 Page 2 of 42 Fuji Electri[.]
Starting guide FRENIC-Lift Dedicated Inverter for Lift Applications ph 400V 4.0 kW - 45 kW ph 200V 5.5 kW - 22 kW ph 200V 2.2 kW SG_Lift_EN_1.8.0 Version 0.1.0 1.0.0 1.0.1 1.0.2 1.0.3 1.0.4 1.0.5 1.0.6 1.1.0 1.2.0 1.2.1 1.2.2 1.2.3 1.3.0 1.3.1 1.3.2 1.3.3 1.4.0 1.5.0 1.6.0 1.6.1 1.6.2 1.7.0 1.7.1 1.8.0 Changes applied Draft st Release Spelling corrections Recommendations according to Lutz Added cover mounting / dismounting Recover the lift Update for 4.0, 37 and 45 kW Update for 4.0, 37 and 45 kW First English version Spelling corrections Most important functions in I/O terminal functions are added in table 16 200 V technical data added De-rating and over-rating added Layout changes applied OS formula corrected Caution added in chapter “conformity to European standards” “Maximum braking time” changed “Binary combination for speed selection” example modified “Signal timing diagram for travel using intermediate speeds” updated “Correspondence of functions for each phase of the sequence” table updated and general table added H64, H65 & L74 added in start & stop optimization table Figure 26 modified Rescue operation information modified Alarm codes updated L56 added to travel optimization table Figures 8, 9, 10 and 11 modified slightly Some information added to parameter F03 Specification tables revised Figure on page 11, 12, 18, 19, 20 and 22, slightly modified H67 definition improved on page 33 L56 definition added on page 39 Figure 23 modified Table 11 modified Title changed and text added on page 39 (soft start function) Alarm messages table modified Tables numbers corrected Small text corrections No-load current calculation formula is added Table 12 is updated Function L83 is added and a value is specified in functions F20 and F25 in table 11.4 Chapter numbers are included Small text corrections ROM version is included CE declaration is updated EN954-1 Cat is included 2,2kW -7 is included Specifications and over-rating changed Figure 26 is changed Some text is added or modified ROM version updated L07, H98(bit2) and L99(bit6) functions included Some text is added or modified Specifications modified Figure numbers are restructured Figure is modified Chapter 3.1 is corrected Information at 15 kHz of switching frequency is added in chapter 3.3 OPL trip is included in chapter 17 Definition of parameters F03 and F04 is changed in chapters 11.2, 11.3 and 11.4 F09 is added in chapter 11.4 Some text is modified Format of tables is changed and restructured EN1 and EN2 terminals included Safety standards updated Mistake corrected in figure 11 Firmware version updated ASR PI included on figure 29 Some information is added in Chapter (safety standards) Some values updated in table Some trips are included in chapter 17 Logo is updated Modifications regarding L80, H04 L76 added Some text is modified in chapter 3.1, 3.2 and 15 Date Written Checked Approved 10.05.2007 15.08.2007 16.08.2007 20.08.2007 20.08.2007 20.08.2007 24.10.2007 31.10.2007 20.11.2007 W Zinke A Schader A Schader A Schader A Schader A Schader A Schader A Schader D Bedford W Zinke A Schader A Schader A Schader A Schader A Schader A Schader A Schader D Bedford W Zinke A Schader A Schader A Schader A Schader A Schader A Schader A Schader D Bedford 21.02.2007 J Alonso D Bedford D Bedford 27.02.2008 28.03.2008 A Schader J Alonso D Bedford D Bedford D Bedford D Bedford 07.04.2008 J Alonso D Bedford D Bedford 14.07.2008 J Alonso J Català J Català 15.07.2008 J Català J Català J Català 16.07.2008 J Català J Català J Català 16.07.2008 J Alonso D Bedford D Bedford 25.11.2008 J Alonso D Bedford D Bedford 25.01.2010 J Alonso D Bedford D Bedford 24.12.2010 J Alonso D Bedford D Bedford 28.02.2011 J Alonso D Bedford D Bedford 12.03.2011 J Alonso D Bedford D Bedford 04.01.2012 J Alonso D Bedford D Bedford 12.07.2012 J Alonso J Català J Català 20.05.2014 J Alonso J Català J Català Dedicated to Mr Wilfred Zinke We would like to thank you for your valuable support and assistance in creating this Starting Guide, we are very grateful that you dedicated your time for this Page of 42 Fuji Electric Europe GmbH Contents Chapters Page About this manual Safety information Conformity to European standards Technical data 8 9 3.1 400 V series 3.2 200 V series (3ph and 1ph) 3.3 Over-rating in 400 V series Removing and mounting the terminal block and front covers (5.5 to 22 kW) 10 Connections 11 11 12 12 13 13 13 14 14 15 5.1 Power connections 5.2 Control signals connection 5.3 Use of input terminals for speed set point selection 5.4 Control terminals description a Analog inputs b Digital inputs c Relay outputs d Transistor outputs e Communication connections (keypad, DCP 3, PC, CANopen) Hardware configuration 16 Encoder 17 17 18 19 20 7.1 Standard (Built-in) input connection for 12/15 V incremental encoder 7.2 Option card OPC-LM1-IL for induction motors (with or without gear) 7.3 Option card OPC-LM1-PS1 for synchronous motors with ECN 1313 EnDat 2.1 7.4 Option card OPC-LM1-PR for synchronous motors with ERN 1387 Keypad operation 21 21 22 23 8.1 Overview 8.2 Keypad menus 8.3 Example of function setting Signals timing diagram for normal travel using high and creep speeds 24 10 Signals timing diagram for travel using intermediate speeds 25 11 Settings 25 25 26 27 28 29 29 31 11.1 Introduction 11.2 Specific settings for induction motors (with encoder) 11.3 Specific settings for permanent magnet synchronous motors 11.4 Specific settings for induction motors in open loop (geared motors without encoder) 11.5 Additional settings for induction motor in open loop 11.6 Setting the speed profile 11.7 Recommended values for acceleration and deceleration related functions 12 Function tables 12.1 Travel optimization 12.2 Start and stop optimization 12.3 Additional functions and settings if needed 12.4 Input and output terminals function settings 12.5 Bit assignment of functions H98 and L99 13 Special operation 32 32 33 33 34 34 35 35 37 13.1 Short floor operation 13.2 Creepless operation 14 Recovering the lift from speed limiter condition 37 15 Rescue operation 38 16 Soft start for closed loop installations (IM and PMSM) with high friction 39 17 Alarm messages 40 Page of 42 Fuji Electric Europe GmbH About this manual Thank you very much for choosing FRENIC-Lift inverter FRENIC-Lift series inverter is specially designed for operation of induction and permanent magnet synchronous motors used in lift applications Also induction motors without encoder (open loop) can be controlled obtaining good performance and high positioning accuracy at stop The main characteristics of FRENIC-Lift are: - Compact dimensions with high output power - Rescue operation with Battery or UPS with indication of recommended direction - Short floor operation with two different modes - 200% overload for 10 seconds - Communication protocols DCP or CANopen integrated - Modbus RTU Protocol is integrated as standard - Incremental encoder input (12 V or 15 V / Open Collector) - Optional cards for different encoder types (Line Driver, EnDat 2.1, SinCos ) - Pole tuning and Auto tuning without removing the ropes (load) - Multifunctional, detachable keypad - Braking transistor is integrated in all capacities - Operation of Induction motor without encoder (open loop) is possible This starting guide includes the important information and explanations about the connection and commissioning of FRENIC-Lift for elevator applications Inputs and outputs can be set to different functions using the corresponding functions By factory defaults these settings are already suitable for lift applications In this manual only the functions related to lift applications are described The factory default settings are suitable for induction motors (geared) In case of gearless synchronous motors the corresponding functions have to be set It is always possible revert the function values to factory default When setting back to factory default the value of the encoder offset (function L04) is lost In this case it is recommended to write down this value before setting to default settings, to be set back afterwards This saves the time of making again the pole tuning procedure Special functions are not described which are only used in special applications For questions please contact our technical staff This starting guide is based on firmware version 1950 and 1951 or later For other software versions, please contact with Fuji Electric technical department Page of 42 Fuji Electric Europe GmbH Safety information Read this manual thoroughly before proceeding with installation, connections (wiring), operation, or maintenance and inspection Ensure you have sound knowledge of the device and familiarize yourself with all safety information and precautions before proceeding to operate the inverter Safety precautions are classified into the following two categories in this manual Failure to heed the information indicated by this symbol may lead to dangerous conditions, possibly resulting in death or serious bodily injuries Failure to heed the information indicated by this symbol may lead to dangerous conditions, possibly resulting in minor or light bodily injuries and/or substantial property damage Failure to heed the information contained under the CAUTION title can also result in serious consequences These safety precautions are of utmost importance and must be observed at all times Application • FRENIC-Lift is designed to drive a three-phase induction motor Do not use it for single-phase motors or for other purposes Fire or an accident could occur • FRENIC-Lift may not be used for a life-support system or other purposes directly related to the human safety • Though FRENIC-Lift is manufactured under strict quality control, install safety devices for applications where serious accidents or material losses are foreseen in relation to the failure of it An accident could occur Installation • Install the inverter on a non-flammable material such as metal Otherwise fire could occur • Do not place flammable object nearby Doing so could cause fire • Do not support the inverter by its terminal block cover during transportation Doing so could cause a drop of the inverter and injuries • Prevent lint, paper fibres, sawdust, dust, metallic chips, or other foreign materials from getting into the inverter or from accumulating on the heat sink Otherwise, a fire or an accident might result • Do not install or operate an inverter that is damaged or lacking parts Doing so could cause fire, an accident or injuries • Do not stand on a shipping box • Do not stack shipping boxes higher than the indicated information printed on those boxes Doing so could cause injuries Page of 42 Fuji Electric Europe GmbH Safety information Wiring • When wiring the inverter to the power supply, insert a recommended moulded case circuit breaker (MCCB) or residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with overcurrent protection) in the path of power lines Use the devices within the recommended current range • Use wires of the specified size • When wiring the inverter to the power supply that is 500 kVA or more, be sure to connect an optional DC reactor (DCR) Otherwise, fire could occur • Do not use one multicore cable in order to connect several inverters with motors • Do not connect a surge killer to the inverter's output (secondary) circuit Doing so could cause fire • Ground the inverter in compliance with the national or local electric code Otherwise, electric shock could occur • Qualified electricians should carry out wiring • Disconnect power before wiring Otherwise, electric shock could occur • Install inverter before wiring Otherwise, electric shock or injuries could occur • Ensure that the number of input phases and the rated voltage of the product match the number of phases and the voltage of the AC power supply to which the product is to be connected Otherwise fire or an accident could occur • Do not connect the power supply wires to output terminals (U, V, and W) • Do not insert a braking resistor between terminals P (+) and N (-), P1 and N (-), P (+) and P1, DB and N (-), or P1 and DB Doing so could cause fire or an accident • Generally, control signal wires are not reinforced insulation If they accidentally touch any of live parts in the main circuit, their insulation coat may break for any reasons In such a case, ensure the signal control wire is protected from making contact with any high voltage cables Doing so could cause an accident or electric shock • Connect the three-phase motor to terminals U, V, and W of the inverter Otherwise injuries could occur • The inverter, motor and wiring generate electric noise Ensure preventative measures are taken to protect sensors and sensitive devices from RF noise Otherwise an accident could occur Operation • Be sure to install the terminal cover before turning the power ON Do not remove the covers while power is applied Otherwise electric shock could occur • Do not operate switches with wet hands Doing so could cause electric shock • If the auto-reset function has been selected, the inverter may automatically restart and drive the motor depending on the cause of tripping (Design the machinery or equipment so that human safety is ensured after restarting.) • If the stall prevention function (current limiter), automatic deceleration, and overload prevention control have been selected, the inverter may operate at an acceleration/deceleration time or frequency different from the commanded ones Design the machine so that safety is ensured even in such cases Otherwise an accident could occur • If an alarm reset is made with the Run command signal turned ON, the inverter may start immediately Ensure that the Run command signal is turned OFF in advance Otherwise an accident could occur • Ensure you have read and understood the manual before programming the inverter, incorrect parameter settings may cause damage to the motor or machinery An accident or injuries could occur • Do not touch the inverter terminals while the power is applied to the inverter even if the inverter is in stop mode Doing so could cause electric shock Page of 42 Fuji Electric Europe GmbH Safety information • Do not turn the main circuit power (circuit breaker) ON or OFF in order to start or stop inverter operation Doing so could cause failure • Do not touch the heat sink and braking resistor because they become very hot Doing so could cause burns • Before setting the speeds (frequency) of the inverter, check the specifications of the machinery • The brake function of the inverter does not provide mechanical holding means Injuries could occur Maintenance and inspection, and parts replacement • Turn the power OFF and wait for at least five minutes before starting inspection Further, check that the LED monitor is unlit and that the DC link bus voltage between the P (+) and N (-) terminals is lower than 25 VDC Otherwise, electric shock could occur • Maintenance, inspection, and parts replacement should be made only by qualified persons • Take off the watch, rings and other metallic objects before starting work • Use insulated tools Otherwise, electric shock or injuries could occur Disposal • Treat the inverter as an industrial waste when disposing of it Otherwise injuries could occur Others • Never attempt to modify the inverter Doing so could cause electric shock or injuries Conformity to European standards The CE marking on Fuji Electric products indicates that they comply with the essential requirements of the Electromagnetic Compatibility (EMC) Directive 2004/108/EC issued by the Council of the European Communities and the Low Voltage Directive 2006/95/EC Inverters with built-in EMC filter that bear a CE marking are in conformity with EMC directives Inverters having no built-in EMC filter can be in conformity with EMC directives if an optional EMC compliant filter is connected to them General purpose inverters are subject to the regulations set forth by the Low Voltage Directive in the EU Fuji Electric declares the inverters bearing a CE marking are compliant with the Low Voltage Directive FRENIC-Lift inverters are in accordance with the regulations of following council directives and their amendments: EMC Directive 2004/108/EC (Electromagnetic Compatibility) Low Voltage Directive 2006/95/EC (LVD) For assessment of conformity the following relevant standards have been taken into consideration: EN61800-3:2004 EN61800-5-1:2003 The FRENIC-Lift inverters are categorized as category C2 according to EN61800-3:2004 When you use these products in the domestic environment, you may need to take appropriate countermeasures to reduce or eliminate any noise emitted from these products Page of 42 Fuji Electric Europe GmbH Technical data 3.1 400 V series Output ratings Type: FRN□□□ LM1S-4□ Rated voltage (V) Rated frequency (Hz) Rated capacity at 440V (kVA) Typical Motor capacity (kW) *1 Rated current (A) Overload current rating (A) Overload capability (%) Input values Mains supply 4.0 5.5 6.8 18 for s 200% for s 10.2 5.5 13.5 27 for 10 s 7.5 11 15 18.5 22 30 3-phase 380 to 480 V (Output voltage cannot be higher than input voltage) 50-60 Hz 14 18 24 29 34 45 7.5 11 15 18.5 22 30 18.5 24.5 32 39 45 60 37 for 10 s 49 for 10 s 64 for 10 s 78 for 10 s 90 for 10 s 108 for s 200% for 10 s Auxiliary control power supply 45 57 37 75 135 for s 180% for s 69 45 91 163 for s 3-phase 380 to 480 V; 50/60 Hz; Voltage: -15% to +10%; Frequency: -5% to +5% External control supply Input current with DC reactor (A) Input current without DC reactor (A) Required power supply capacity (kVA) Input values for battery operation Battery operation voltage 37 1-phase 200 to 480 V; 50/60Hz 7.5 13 10.6 17.3 14.4 23.2 21.1 33 28.8 43.8 35.5 52.3 42.2 60.6 57 77.9 5.2 7.4 10 15 20 25 30 40 1-phase 380 to 480V; 50/60 Hz 68.5 83.2 94.3 114 48 58 48 VDC or higher 1-phase 200 to 480 V; 50/60 Hz Voltage/frequency variations Voltage: -15% to +10% (Voltage unbalance: 2% or less); Frequency: -5% to +5% Braking resistor values Maximum braking time (s) 60 Duty cycle (%ED) 50 Minimum resistor value ± 5% (Ω) 96 48 48 24 24 16 16 10 Options and Standards DC reactor (DCRE) Optional EMC – Filter Optional Safety standards EN 61800-5-1, EN 61800-5-2 (SIL 2), EN ISO 13849-1 (Cat 3, PL d) Protection degree (IEC60529) IP20 Cooling Fan cooling Mass (kg) 2.8 5.6 5.7 7.5 11.1 11.2 11.7 24.0 *1 For 10 kHz Switching frequency, 45 °C ambient temperature and 80%ED Page of 42 1-phase 380 to 480 V; 50/60 Hz 10 EN61800-5-1 IP00 33.0 34.0 Fuji Electric Europe GmbH Technical data 3.2 200 V series (3ph and 1ph) FRN□□□ LM1S-2□ Type: Output ratings FRN□□□ LM1S-7□ 5.5 7.5 Rated voltage (V) Rated frequency (Hz) Rated capacity at 220V (kVA) Typical Motor capacity (kW) *2 Rated current (A) Overload current rating for 10s (A) Overload capability for 10s (%) Input values 10.2 5.5 27 54 14 7.5 37 74 Mains supply 3-phase 200 to 240 V; 50/60 Hz; Voltage: -15% to +10%; Frequency: -5% to +5% *1 External control supply Input current with DC reactor (A) Input current without DC reactor (A) Required power supply capacity (kVA) Input values for battery operation Battery operation voltage Auxiliary control power supply 11 15 18.5 22 3-phase 200 to 240 V 50-60 Hz 18 24 28 34 11 15 18.5 22 49 63 74 90 98 126 148 180 for s 200 2.2 1-phase 200 to 240 V 4.1 2.2 11 22 for s 1-phase 200 to 240V; 50/60Hz; Voltage: -15% to +10%; Frequency: -5% to +5% 200 to 240 V; 50/60 Hz 21.1 28.8 42.2 57.6 31.5 42.7 60.7 80.1 71 97 84.4 112 17.5 24 7.4 25 30 3.5 10 15 20 24 VDC or higher 1-phase 200 to 240 V; 50/60 Hz ; Voltage: -15% to +10%; Frequency: -5% to +5% Braking resistor values Maximum braking time (s) 60 Duty cycle (%ED) 50 Minimum resistor value ± 5% (Ω) 15 10 7.5 3.5 33 Options and Standards DC reactor (DCRE) Optional EMC – Filter Optional Safety standards EN 61800-5-1, EN 61800-5-2 (SIL 2), EN ISO 13849-1 (Cat 3, PL d) Protection degree (IEC60529) IP20 Cooling Fan cooling Mass (kg) 5.6 5.7 7.5 11.1 11.2 11.7 3.0 *1 Output voltage cannot be higher than input voltage *2 For 10 kHz Switching frequency, 45 °C ambient temperature and 80%ED 3.3 Over-rating for 400 V series In table 1, different ratings are shown depending on the switching frequency Size INVERTER Maximum Motor POWER 4.0 5.5 7.5 11 15 18.5 22 30 37 45 kW 5.5 kW 7.5 kW 11 kW 15 kW 18.5 kW 22 kW 30kW 37 kW 45 kW Table Over-rating for 400 V series 40%ED 45 ºC Switching frequency: 10 kHz Switching frequency: 12 kHz I rated Overload Time I rated Overload Time (A) (%) (s) (A) (%) (s) 10.6 17.6 24.1 30.5 37.6 45 54.8 63.5 79.5 96 170 170 170 170 170 170 170 170 170 170 10 10 10 10 10 10 5 10 15 20.5 27.2 35.6 43.4 50 60 75 91 Page of 42 180 180 180 180 180 180 180 180 180 180 10 10 10 10 10 10 5 Switching frequency: 15 kHz I rated Overload Time (A) (%) (s) 9.5 14.2 19.4 25.7 33.6 41 47 60 75 91 190 190 190 190 190 190 190 180 180 180 10 10 10 10 10 10 5 Fuji Electric Europe GmbH Removing and mounting the terminal block and front covers (5.5 to 22 kW) Terminal block cover Terminal block cover fastening screw Front cover "PULL" Mark Figure 1: Removing the terminal block cover and the front cover Front cover Front cover Hinge Front cover Hole Hole Terminal block cover Cover fastening screw (terminal block cover) Latch Terminal block cover Figure 2: Mounting the terminal block cover and the front cover Page 10 of 42 Fuji Electric Europe GmbH ... using PNP Logic: FRENIC- Lift PLC (+24 V) Lift controller Up FWD Speed X1 Figure 6: Normal connection using free potential contacts of the lift controller FRENIC- Lift PLC (+24 V) Lift controller... very much for choosing FRENIC- Lift inverter FRENIC- Lift series inverter is specially designed for operation of induction and permanent magnet synchronous motors used in lift applications Also... Application • FRENIC- Lift is designed to drive a three-phase induction motor Do not use it for single-phase motors or for other purposes Fire or an accident could occur • FRENIC- Lift may not be