1. Trang chủ
  2. » Kỹ Thuật - Công Nghệ

Design of 400/220kV Sub-station

62 153 0

Đang tải... (xem toàn văn)

Tài liệu hạn chế xem trước, để xem đầy đủ mời bạn chọn Tải xuống

THÔNG TIN TÀI LIỆU

Thông tin cơ bản

Định dạng
Số trang 62
Dung lượng 5,54 MB

Nội dung

Fault of bus or any circuit breaker results in shutdown of entire substation.. Any breaker can be taken out of service for maintenance.. Line breaker failure takes all circuits connected

Trang 3

Imp considerations in substation design

– I.E rules, Environmental aspects

Trang 4

System parameters

1000 mV(156kV)

1000 mV(320kV)

Radio interference voltage at 1MHZ (for

phase to earth voltage)

10

40kA40kA

Rated short ckt Current for 1 sec

8

25mm/kV25mm/kV

Min creepage distance

7

156kV320kV

Corona Extinction voltage

6

Effectively earthedSystem neutral earthing

5

33

Number of phases

4

50Hz50Hz

Rated frequency

3

245kV420kV

Max operating voltage

2

220kV400kV

Nominal system voltage

1

220kV 400kV

Description

Sr.

Trang 5

System parameters Contd

Remarks 220kV

400kV Description

Sr.

(Line-ground) (open terminals)

460kV 460kV 530kV 460kV

680kV 520kV 610kV 630kV

iii) One min power freq.

withstand voltage (dry/wet)

for lines for CB / Isolator

for other equipments

1050kVp ii) Switching impulse

withstand voltage (dry/wet)

1050kVp 950kVp 1050kVp

1550kVp 1300kVp 1425kVp

Rated insulation levels

i) Full wave impulse

withstand voltage

for lines for reactor/ X’mer for other equipments 11.

Trang 6

Substation Bird’s view

Trang 7

400kV Circuit Breaker

Trang 8

400kV Isolator

Trang 9

400kV Current Transformer

Trang 10

400kV CVT

Trang 11

400kV Surge Arrester

Trang 12

Shunt Reactor & NGR

Trang 13

400/220 kV Auto Transformer

Trang 14

400kV Bus Post Insulator

Trang 15

Wave Trap

Trang 17

Functions of substation equipments

To discharge lightning over voltages and switching over voltages to earth

Trang 18

Functions of substation equipments Contd…

Compensation of long lines

Trang 19

Functions of Associated system in substation

3 Illumination system (lighting)

for switchyard buildings

Arresters, overheads shielding wires etc with safe step-potential and touch

Trang 20

To provide alarm or automatic tripping of faulty part from healthy part and also to minimize damage to faulty equipment and associated system

7 PLCC system power line

carries communication system

Trang 21

To sense the occurrence of fire by sensors and to initiate water spray, to disconnect power supply to affected region to pin-point location of fire by indication in control room

8 Fire Fighting system

Sensors, detection system

water spray system

fire prot panels, alarm system

watertank and spray system

For internal and external communication

10 Telephone, telex, microwave, OPF

For supplying starting power, standby power for auxiliaries

9 Auxiliary standby power system

diesel generator sets

switchgear

distribution system

Trang 22

Basic drawings for design/construction

 Single Line Diagram

 General Arrangement Drawing

 Electrical Plan and Section

 Control Room Architectural layout

Trang 24

Single Line Diagram – 220kV

Trang 25

General arrangement layout

Trang 26

Electrical layout

Trang 27

Electrical Section

Trang 28

Control room layout

Trang 30

Structural layout

Trang 32

Civil layout

Trang 33

Erection Key Diagram

R2

N 1

Trang 34

Lighting Design

activities

- 20 Lux (balance Area / road @ ground level)

Trang 35

Single Bus arrangement

Trang 36

Single Bus System

4 Can be used only where loads can be interrupted or have other supply

arrangements

3 Sectionalizing increases flexibility

3 Bus cannot be extended without completely de-

Merits

Trang 37

Main & Transfer Bus

Trang 38

Main & transfer busbar system

3 Fault of bus or any circuit breaker results in shutdown of entire

substation

3 Potential devices may

be used on the main bus

2 Switching is somewhat complex when

maintaining a breaker

2 Any breaker can be

taken out of service for

maintenance

1 Used for 110kV substations where cost of duplicate bus bar system

Merits

Trang 39

Double Busbar arrangement

Trang 40

Double Bus Bar Single Breaker system

5 Bus couplers failure takes entire substation out of service

4 Line breaker failure takes all circuits connected to the bus out

of service

3 High exposure to bus fault

2 Bus protection scheme may cause loss of substation when it operates

2 Half of the feeders

connected to each bus

1 Most widely used for 66kV, 132kv, 220kV and

important 11kv, 6.6kV, 3.3kV substations

1 Extra bus-coupler circuit breaker necessary

1 High flexibility

Remarks Demerits

Merits

Trang 41

Double Busbar with Double breaker

Trang 42

Double Bus Bar Double Breaker system

4 High reliability

3 Any breaker can be

taken out of service for

maintenance

2 Used only for very important, high power, EHV substations

2 Would lose half of the circuits for breaker fault if circuits are not connected

to both the buses

1 Most expensive

1 Each has two

associated breakers

Remarks Demerits

Merits

Trang 43

Double main & transfer

Trang 44

Double main bus & transfer bus system

7 Bus fault does not remove any

feeder from the service

6 Either main bus can be taken out

of service at any time for

maintenance

5 Simple operation, no isolator

switching required

4 All switching done with breakers

3 Breaker failure on bus side breaker

removes only one ckt From service

2 Highly reliable

1 Preferred by some utilities for 400kV and

220kV important substations

1 High cost due to three buses

1 Most flexible in operation

Remarks Demerits

Merits

Trang 45

One & half breaker scheme

Trang 46

6 Selective tripping

5 All switching by breaker

4 Each circuit fed by two

responsive to both associated circuits

2 Any breaker can be removed

from maintenance without

interruption of load

1 Used for 400kV

& 220kV substations

1 One and half breakers per circuit, hence higher cost

1 Flexible operation for breaker

maintenance

Remarks Demerits

Merits

Trang 47

Ring Bus

Trang 48

Mesh (Ring) busbar system

4 Breaker failure during fault on one circuit causes loss of additional circuit because of breaker failure

3 Requires VT’s on all circuits because there is no definite voltage reference point

These VT’s may be required in all cases for synchronizing live line or voltage indication

2.Auto-reclosing and protection complex

1 Most widely used for very large power stations having large no of incoming and outgoing lines and high power transfer

1 If fault occurs during bus maintenance, ring gets separated into two sections

1 Busbars gave

some operational

flexibility

Remarks Demerits

Merits

Trang 49

4000 mm(Conductor-conductor configuration)

Trang 52

Clearance Diagram

Trang 53

Bus Bar Design

Trang 54

Gantry Structure Design

Clearances

No windMax

5

T <= 70% of UTS100%

Every Day4

T <= 22% of UTS

No windEvery Day

1

LimitsWind Pressure

TempSr

 Sag / Tension calculation : as per IS: 802 1995

Trang 55

 Short Circuit Forces calculation

As per IEC : 865

Short circuit forces during short circuit

Short circuit forces after short circuit

Short circuit forces due to “Pinch” effect for Bundled conductor

Spacer span calculation

 Factor of safety of 2.0 under normal condition and 1.5 under short circuit condition

Trang 56

spacers

Trang 57

Spacer span Vs Short Ckt forces

GRAPH OF SPACER SPAN Vs CONDUCTOR TENSION FOR

400 KV TWIN MOOSE ACSR CONDUCTOR

0.00 2000.00 4000.00 6000.00 8000.00 10000.00 12000.00

Trang 58

Earthing Design

corrosion)

Trang 59

Touch and step potential

Trang 60

Lightning Protection – Ground Wire

Trang 61

Lightning Protection – Lightning Mast

Ngày đăng: 28/02/2016, 23:07

TỪ KHÓA LIÊN QUAN

TÀI LIỆU CÙNG NGƯỜI DÙNG

TÀI LIỆU LIÊN QUAN

w