Fault of bus or any circuit breaker results in shutdown of entire substation.. Any breaker can be taken out of service for maintenance.. Line breaker failure takes all circuits connected
Trang 3Imp considerations in substation design
– I.E rules, Environmental aspects
Trang 4System parameters
1000 mV(156kV)
1000 mV(320kV)
Radio interference voltage at 1MHZ (for
phase to earth voltage)
10
40kA40kA
Rated short ckt Current for 1 sec
8
25mm/kV25mm/kV
Min creepage distance
7
156kV320kV
Corona Extinction voltage
6
Effectively earthedSystem neutral earthing
5
33
Number of phases
4
50Hz50Hz
Rated frequency
3
245kV420kV
Max operating voltage
2
220kV400kV
Nominal system voltage
1
220kV 400kV
Description
Sr.
Trang 5System parameters Contd
Remarks 220kV
400kV Description
Sr.
(Line-ground) (open terminals)
460kV 460kV 530kV 460kV
680kV 520kV 610kV 630kV
iii) One min power freq.
withstand voltage (dry/wet)
for lines for CB / Isolator
for other equipments
1050kVp ii) Switching impulse
withstand voltage (dry/wet)
1050kVp 950kVp 1050kVp
1550kVp 1300kVp 1425kVp
Rated insulation levels
i) Full wave impulse
withstand voltage
for lines for reactor/ X’mer for other equipments 11.
Trang 6Substation Bird’s view
Trang 7400kV Circuit Breaker
Trang 8400kV Isolator
Trang 9400kV Current Transformer
Trang 10400kV CVT
Trang 11400kV Surge Arrester
Trang 12Shunt Reactor & NGR
Trang 13400/220 kV Auto Transformer
Trang 14400kV Bus Post Insulator
Trang 15Wave Trap
Trang 17Functions of substation equipments
To discharge lightning over voltages and switching over voltages to earth
Trang 18Functions of substation equipments Contd…
Compensation of long lines
Trang 19Functions of Associated system in substation
3 Illumination system (lighting)
for switchyard buildings
Arresters, overheads shielding wires etc with safe step-potential and touch
Trang 20To provide alarm or automatic tripping of faulty part from healthy part and also to minimize damage to faulty equipment and associated system
7 PLCC system power line
carries communication system
Trang 21To sense the occurrence of fire by sensors and to initiate water spray, to disconnect power supply to affected region to pin-point location of fire by indication in control room
8 Fire Fighting system
Sensors, detection system
water spray system
fire prot panels, alarm system
watertank and spray system
For internal and external communication
10 Telephone, telex, microwave, OPF
For supplying starting power, standby power for auxiliaries
9 Auxiliary standby power system
diesel generator sets
switchgear
distribution system
Trang 22Basic drawings for design/construction
Single Line Diagram
General Arrangement Drawing
Electrical Plan and Section
Control Room Architectural layout
Trang 24Single Line Diagram – 220kV
Trang 25General arrangement layout
Trang 26Electrical layout
Trang 27Electrical Section
Trang 28Control room layout
Trang 30Structural layout
Trang 32Civil layout
Trang 33Erection Key Diagram
R2
N 1
Trang 34Lighting Design
activities
- 20 Lux (balance Area / road @ ground level)
Trang 35Single Bus arrangement
Trang 36Single Bus System
4 Can be used only where loads can be interrupted or have other supply
arrangements
3 Sectionalizing increases flexibility
3 Bus cannot be extended without completely de-
Merits
Trang 37Main & Transfer Bus
Trang 38Main & transfer busbar system
3 Fault of bus or any circuit breaker results in shutdown of entire
substation
3 Potential devices may
be used on the main bus
2 Switching is somewhat complex when
maintaining a breaker
2 Any breaker can be
taken out of service for
maintenance
1 Used for 110kV substations where cost of duplicate bus bar system
Merits
Trang 39Double Busbar arrangement
Trang 40Double Bus Bar Single Breaker system
5 Bus couplers failure takes entire substation out of service
4 Line breaker failure takes all circuits connected to the bus out
of service
3 High exposure to bus fault
2 Bus protection scheme may cause loss of substation when it operates
2 Half of the feeders
connected to each bus
1 Most widely used for 66kV, 132kv, 220kV and
important 11kv, 6.6kV, 3.3kV substations
1 Extra bus-coupler circuit breaker necessary
1 High flexibility
Remarks Demerits
Merits
Trang 41Double Busbar with Double breaker
Trang 42Double Bus Bar Double Breaker system
4 High reliability
3 Any breaker can be
taken out of service for
maintenance
2 Used only for very important, high power, EHV substations
2 Would lose half of the circuits for breaker fault if circuits are not connected
to both the buses
1 Most expensive
1 Each has two
associated breakers
Remarks Demerits
Merits
Trang 43Double main & transfer
Trang 44Double main bus & transfer bus system
7 Bus fault does not remove any
feeder from the service
6 Either main bus can be taken out
of service at any time for
maintenance
5 Simple operation, no isolator
switching required
4 All switching done with breakers
3 Breaker failure on bus side breaker
removes only one ckt From service
2 Highly reliable
1 Preferred by some utilities for 400kV and
220kV important substations
1 High cost due to three buses
1 Most flexible in operation
Remarks Demerits
Merits
Trang 45One & half breaker scheme
Trang 466 Selective tripping
5 All switching by breaker
4 Each circuit fed by two
responsive to both associated circuits
2 Any breaker can be removed
from maintenance without
interruption of load
1 Used for 400kV
& 220kV substations
1 One and half breakers per circuit, hence higher cost
1 Flexible operation for breaker
maintenance
Remarks Demerits
Merits
Trang 47Ring Bus
Trang 48Mesh (Ring) busbar system
4 Breaker failure during fault on one circuit causes loss of additional circuit because of breaker failure
3 Requires VT’s on all circuits because there is no definite voltage reference point
These VT’s may be required in all cases for synchronizing live line or voltage indication
2.Auto-reclosing and protection complex
1 Most widely used for very large power stations having large no of incoming and outgoing lines and high power transfer
1 If fault occurs during bus maintenance, ring gets separated into two sections
1 Busbars gave
some operational
flexibility
Remarks Demerits
Merits
Trang 494000 mm(Conductor-conductor configuration)
Trang 52Clearance Diagram
Trang 53Bus Bar Design
Trang 54Gantry Structure Design
Clearances
No windMax
5
T <= 70% of UTS100%
Every Day4
T <= 22% of UTS
No windEvery Day
1
LimitsWind Pressure
TempSr
Sag / Tension calculation : as per IS: 802 1995
Trang 55Short Circuit Forces calculation
As per IEC : 865
Short circuit forces during short circuit
Short circuit forces after short circuit
Short circuit forces due to “Pinch” effect for Bundled conductor
Spacer span calculation
Factor of safety of 2.0 under normal condition and 1.5 under short circuit condition
Trang 56spacers
Trang 57Spacer span Vs Short Ckt forces
GRAPH OF SPACER SPAN Vs CONDUCTOR TENSION FOR
400 KV TWIN MOOSE ACSR CONDUCTOR
0.00 2000.00 4000.00 6000.00 8000.00 10000.00 12000.00
Trang 58Earthing Design
corrosion)
Trang 59Touch and step potential
Trang 60Lightning Protection – Ground Wire
Trang 61Lightning Protection – Lightning Mast