30156286 pdf BRITISH STANDARD BS EN 50464 4 2007 Three phase oil immersed distribution transformers 50 Hz, from 50 kVA to 2 500 kVA with highest voltage for equipment not exceeding 36 kV — Part 4 Requ[.]
BS EN 50464-4:2007 +A1:2011 BRITISH STANDARD Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to 500 kVA with highest voltage for equipment not exceeding 36 kV — `,,```,,,,````-`-`,,`,,`,`,,` - Part 4: Requirements and tests concerning pressurised corrugated tanks ICS 29.180 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Not for Resale BS EN 50464-4:2007+A1:2011 National foreword This British Standard is the UK implementation of EN 50464-4:2007+A1:2011 It supersedes BS EN 50464-4:2007 which is withdrawn The UK participation in its preparation was entrusted to Technical Committee PEL/14, Power transformers A list of organizations represented on this committee can be obtained on request to its secretary This publication does not purport to include all the necessary provisions of a contract Users are responsible for its correct application This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 August 2007 © BSI 2011 Amendments/corrigenda issued since publication Date Comments 31 December 2011 Implementation of CENELEC amendment A1:2011: additional text in subclause 3.1 ISBN 978 580 75264 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Not for Resale `,,```,,,,````-`-`,,`,,`,`,,` - Compliance with a British Standard cannot confer immunity from legal obligations EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM EN 50464-4:2007+A1 October 2011 Supersedes HD 428.6 S1:2002 ICS 29.180 English version Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to 500 kVA with highest voltage for equipment not exceeding 36 kV Part 4: Requirements and tests concerning pressurised corrugated tanks Ölgefüllte Drehstrom-Verteilungstransformatoren 50 Hz, 50 kVA bis 500 kVA mit einer höchsten Spannung für Betriebsmittel bis 36 kV Teil 4: Anforderungen und Prüfungen für druckbeanspruchte Wellwandkessel Transformateurs triphasés de distribution immergés dans l'huile, 50 Hz, de 50 kVA 500 kVA, de tension la plus élevée pour le matériel ne dépassant pas 36 kV Partie 4: Prescriptions et essais relatifs aux cuves sous pression This European Standard was approved by CENELEC on 2006-12-01 CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration `,,```,,,,````-`-`,,`,,`,`,,` - Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member This European Standard exists in three official versions (English, French, German) A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom CENELEC European Committee for Electrotechnical Standardization Comité Européen de Normalisation Electrotechnique Europäisches Komitee für Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels © 2007 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC members Ref No EN 50464-4:2007 E Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Not for Resale BS EN 50464-4:2007+A1:2011 EN 50464-4:2007+A1:2011 (E) –2– Foreword The text of the Harmonization Document HD 428.6 S1:2002, prepared by the Technical Committee CENELEC TC 14, Power transformers, was submitted to the formal vote for conversion into a European Standard and was approved by CENELEC as EN 50464-4 on 2006-12-01 The following date was fixed: – latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2007-12-01 The EN 50464 series consists of the following parts, under the general title “Three-phase oil-immersed distribution transformers 50 Hz, from 50 kVA to 500 kVA with highest voltage for equipment not exceeding 36 kV”: `,,```,,,,````-`-`,,`,,`,`,,` - Part General requirements Part 2-1 Distribution transformers with cable boxes on the high-voltage and/or low-voltage side – General requirements Part 2-2 Distribution transformers with cable boxes on the high-voltage and/or low-voltage side – Cable boxes type for use on distribution transformers meeting the requirements of EN 50464-2-1 Part 2-3 Distribution transformers with cable boxes on the high-voltage and/or low-voltage side – Cable boxes type for use on distribution transformers meeting the requirements of EN 50464-2-1 Part Determination of the power rating of a transformer loaded with non-sinusoidal currents Part Requirements and tests concerning pressurised corrugated tanks Foreword to amendment A1 This document (EN 50464-4:2007/A1:2011) has been prepared by the CLC/TC 14, "Power transformers" The following dates are fixed: • • latest date by which the document h as to be implemented at national level by publication of an identical national standard or by endorsement latest date by which the national standards conflicting with the document have to be withdrawn (dop) 2012-10-10 (dow) 2014-10-10 Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent rights Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Not for Resale –3– BS EN 50464-4:2007+A1:2011 EN 50464-4:2007+A1:2011 (E) Content `,,```,,,,````-`-`,,`,,`,`,,` - Scope Normative references General conditions 4 3.1 3.2 3.3 Test Temperature variation Sealing temperature Calculation of the volume variation procedure 4.1 4.2 4.3 4.4 4.5 General Measurement of pressure range Endurance test Leakage test Evaluation of the tests Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Not for Resale BS EN 50464-4:2007+A1:2011 EN 50464-4:2007+A1:2011 (E) –4– Scope This Part of EN 50464 series is applicable to test procedures to verify the mechanical withstand capability of the corrugated tanks of completely oil filled and hermetically sealed distribution transformers NOTE Variations of oil temperature due to variations of ambient temperature and loading, result in deformation of tank walls Normative references For the purposes of this document, the normative references of EN 50464-1 apply General conditions 3.1 Temperature variation By agreement between manufacturer and purchaser the maximum temperature used for the endurance test shall be 40 °C plus 0,8 times the oil temperature rise determined by the temperature rise test 3.2 Sealing temperature When sealing the tank, the average oil temperature shall be chosen between 15 °C and 35 °C and recorded A manometer connected to the tank cover shall register the value zero 3.3 Calculation of the volume variation From the temperature variations above, the oil volume change from the relaxed stage at the sealing temperature shall be calculated using a volume expansion coefficient of 0,000 75 K-1 (for mineral oil) Test procedure 4.1 General These tests are considered as special tests These tests shall be carried out (in the sequence from 4.2 to 4.4) on a tank which is considered as representative of a range of tanks by agreement between purchaser and supplier 4.2 Measurement of pressure range The increase or decrease of the oil volume as calculated in 3.3 shall be added to or extracted from the relaxed tank, and the corresponding overpressure (P+) and underpressure (P-) shall be registered by a manometer connected to the tank cover The oil temperature during the measurement shall be the same value as used for sealing ± °C (see 3.2) Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Not for Resale `,,```,,,,````-`-`,,`,,`,`,,` - For the simulation of the seasonal and daily temperature variations, the average oil temperature is assumed to vary between -25 °C (minimum ambient temperature with disconnected transformer) and +88 °C (the sum of maximum ambient temperature +40 °C and maximum allowed average oil temperature rise: 0,8 x 60 K = 48 K) –5– BS EN 50464-4:2007+A1:2011 EN 50464-4:2007+A1:2011 (E) 4.3 Endurance test To simulate the volume expansion, the tank shall be subjected to 000 cycles with overpressure and underpressure Each cycle comprises one overpressure and one underpressure To achieve the overpressure and underpressure, the volume of oil calculated in 3.3 shall be added to and extracted from the tank in the quantity calculated in 3.3 The pressure P+ and P- shall be recorded during the test at intervals The reading of the manometer with the tank relaxed shall be recorded before (P0) and after the test (P1) and the tank shall be topped up with oil to reach the initial relaxing pressure P0 If requested for the test evaluation, the added volume shall be recorded NOTE To avoid mechanical impulses, the test duration should not be too short A minimum cycle duration of 120 s may be sufficient NOTE A pause in the test procedure does not affect the test result 4.4 Leakage test After the endurance test, the same tank shall be subjected to a 24 h static leakage test with an overpressure 1,2 times the value recorded during the measurement (see 4.2) 4.5 Evaluation of the tests After 4.4, the following events shall be observed: – the tank shall not show leakages as observed by appropriate detecting means; – no cracks shall occur in the tank; – heavy and unexplained discrepancies on the pressure readings taken before, during and after the tests under 4.2 and 4.3, have to be considered as possible indexes of abnormal events; – by agreement between manufacturer and purchaser, a limit for the volume of oil to be added at the end of the test may be specified for checking the permanent deformations of the tank `,,```,,,,````-`-`,,`,,`,`,,` - Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Not for Resale BS EN 50464-4:2007 +A1:2011 BSI - British Standards Institution BSI is the independent national body responsible for preparing British Standards It presents the UK view on standards in Europe and at the international level It is incorporated by Royal Charter Revisions British Standards are updated by amendment or revision Users of British Standards should make sure that they possess the latest amendments or editions It is the constant aim of BSI to improve the quality of our products and services We would be grateful if anyone finding an inaccuracy or ambiguity while using this British Standard would inform the Secretary of the technical committee responsible, the identity of which can be found on the inside front cover Tel: +44 (0)20 8996 9000 Fax: +44 (0)20 8996 7400 BSI offers members an individual updating service called PLUS which ensures that subscribers automatically receive the latest editions of standards Buying standards Orders for all BSI, international and foreign standards publications should be addressed to Customer Services Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001 Email: orders@bsigroup.com You may also buy directly using a debit/credit card from the BSI Shop on the Website http://www.bsigroup.com/shop In response to orders for international standards, it is BSI policy to supply the BSI implementation of those that have been published as British Standards, unless otherwise requested BSI provides a wide range of information on national, European and international standards through its Library and its Technical Help to Exporters Service Various BSI electronic information services are also available which give details on all its products and services Contact Information Centre Tel: +44 (0)20 8996 7111 Fax: +44 (0)20 8996 7048 Email: info@bsigroup.com Subscribing members of BSI are kept up to date with standards developments and receive substantial discounts on the purchase price of standards For details of these and other benefits contact Membership Administration Tel: +44 (0)20 8996 7002 Fax: +44 (0)20 8996 7001 Email: membership@bsigroup.com Information regarding online access to British Standards via British Standards Online can be found at http://www.bsigroup.com/BSOL Further information about BSI is available on the BSI website at http:// www.bsigroup.com Copyright BSI Group Headquarters 389 Chiswick High Road, London, W4 4AL, UK Tel +44 (0)20 8996 9001 Fax +44 (0)20 8996 7001 www.bsigroup.com/ standards Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy No reproduction or networking permitted without license from IHS Copyright subsists in all BSI publications BSI also holds the copyright, in the UK, of the publications of the international standardization bodies Except as permitted under the Copyright, Designs and Patents Act 1988 no extract may be reproduced, stored in a retrieval system or transmitted in any form or by any means – electronic, photocopying, recording or otherwise – without prior written permission from BSI This does not preclude the free use, in the course of implementing the standard, of necessary details such as symbols, and size, type or grade designations If these details are to be used for any other purpose than implementation then the prior written permission of BSI must be obtained Details and advice can be obtained from the Copyright and Licensing Manager Tel: +44 (0)20 8996 7070 Email: copyright@bsigroup.com Not for Resale `,,```,,,,````-`-`,,`,,`,`,,` - Information on standards