Inverter operation command mode is set by parameter F0.02: There are two kinds of command mode: panel control start / stop and terminal control start / stop: 1 Panel control start/stop:

Trang 1

Please give the instructions to the final user and save it carefully

The technological standards of this product may be changed, but we will notmake a notice about it

2RI20191211 1.3 Version BBeginning date: December 11rd, 2019Number: XM-H0125

V1.3

Small Universal Inverter

INSTRUCTION MANUAL

Trang 2

1 / 31

Declaration

Thanks for choosing the inverter Before you use it, please read the instructions carefully, and making sure that you have known about all the safety precaution.

Safety Precaution:

1 Before wring, please make sure that the input power is off.

2 The wring work should be operated by the professional electrical engineer.

3 The grounding terminals must be connected with the ground.

4 Having paused circuit wiring emergently, please make sure that the check is effective.

5 Do not connect the output wire of the inverter with the shell, and pay attention that the output wire should not be short-circuited.

6 Please check whether the voltage of the AC main circuit power is consistent with the rated voltage of the inverter.

7 Do not do the voltage withstand test on the inverter.

8 Please connect the brake resistor according to the wiring diagram.

9 Do not connect the power to the U, V, W output terminals.

10 Do not connect the contactor with the output circuit.

11 Mare sure to install a protection cover before power-on When removing the cover, be sure to make the power off.

12 If you want to reset the inverter with the retry function, do not get close

to the mechanical equipment, because the inverter will restart suddenly when the alarm stops.

13 Confirmthat the operation signal is cut off Before reset the alarm device, or the inverter may start suddenly.

14 Do not touch the terminals of inverter, which are very dangerous because there is high voltage on them.

15 When power is on, do not change the wiring and terminal.

16 Cut off the main circuit power before doing some check and maintain work.

17 Do not arbitrarily reform the inverter.

Trang 3

2 / 31

Rated data of Inverter

L*W*H(mm)0.4G1-220V 0.4KW

SinglePhase AC220V-240V50Hz/60Hz

Three PhaseAC370V-440V50Hz/60Hz

Trang 4

3 / 31

Terminal Function Instructions

Terminal Function Setting and Instruction

R、S、T

Inverter input voltage:

380V Model connect with

is above 200mA and reaction period lastmore than 100ms

U、V、W Inverter output, connectedwith electrical machine In order to reduce the leakage of current,the connection wire should not be over

50 meters

P、B Connected with brakingresistor According to the list of brakingresistors, choose an appropriate one.

PE Connected with theground The inverter should be connected withthe ground well

Trang 5

4 / 31

Terminal Function Setting and Instruction

COM Digital signal commonport Zero potential of digital signalS1 Digital input S1 Set according to parameter F2.13, andfactory set defaults tobe FWD.S2 Digital input S2 Set according to parameter F2.14, andfactory set defaults tobe REVS3 Digital input S3 Set according to parameter F2.15, andfactory set defaults tobe the first one of

multistage speed

S4 Digital input S4 Set according to parameter F2.16, andfactory set defaults tobe the second one

of multistage speedS5 Digital input S5 Set according to parameter F2.17, andGND Analogl signal commonport Zero potential of analog signalAVI 0-10V signal input 0-10V, input resistance:>50KΩ10V Frequency Settingpotentiometer power

ACI 4-20mA analog input 4-10mA, input resistance: 100ΩA0 Analog output Set according to parameter F2.10RA、RB、RC Relay output Set according to parameter F2.20Contact rating: AC 250V/3A

DC 24V/2A

Trang 6

5 / 31

3、Operation

Attention:

If the power is on, it shows 0.0 on the panel (output frequency)

After setting parameter, the way to return the original:

1 When the power is off, make it on again

2 Select the parameter d-00, and click SET

3 Long press SET key for 3 S

Inverter operation command mode is set by parameter F0.02: There are two kinds

of command mode: panel control start / stop and terminal control start / stop:

(1) Panel control start/stop: (The factory set defaults to be controlled by panel.)

When you use the panel to control the inverter, you should remember thatclicking the green button means start the inverter and clicking the red button meansstop Before any operation, the inverter defaults to start FWD FWD and REV are set

by input terminal S1-S5 (the REV set is 4)

Panel and Methods

Inverter Operation Command Mode

Trang 7

6 / 31

(2) Terminal control Start/Stop

The inverter frequency setting mode is set by F0.03 When F0.03 = 0, the runningfrequency is set by potentiometer When F0.03 = 3, the running frequency is input byAVI (0-10V can be connected with potentiometer); when F0.03 = 5, the runningfrequency is input by ACI (4-20mA) When F0.03 = 2, it is controlled by the externalterminal (the switch value is set to frequency increment / decrement)

Para-meter Name Value Factory Set Scope Instruction

F0- The basic running parameter

F0.00 Inverter powerinverterAccording to

model 0.1-99.9kw The current power

F0.01 App version 1.0 1.0-99.9 The current version

Inverter Frequency Setting Mode

Trang 8

7 / 31

Para-meter Name Value Factory Set Scope Instruction

F0.02 Runningcommand 0 0-1 0: Panel running command1: Terminal running command

F0.03 Frequencysetting 0 0-5

0: panel potentiometer input1: number set, adjust by theup/down button on the panel2: number set, adjust by theterminal up/down3: AVI analog quantity set (0-10V)4: combination set (F1.15)5: ACI set (4-20mA)F0.04

F0.05 limit ofThe upper

The running frequency cannot beless than the lower limit.F0.07 when reachingSolutions

0: running at 01: running atlower limit2: stop

F0.08 frequencyRunning

0-the upperlimit the value is original one

F0.09 frequencyDigital

A place: power-down storage0: save, 1: do not saveTen: keep stop0: hold, 1: do not holdHundreds: UF / DOWN negativefrequency adjustment0: invalid, 1: validThousands digit: PID, PLCfrequency superposition0: invalid,

1: F0.03 + PID,2: F0.03 + PLCF0.10 Accelerationtime inverterAccording to 0-255s accelerate from zero to theThe time it takes for the inverter to

Trang 9

8 / 31

Para-meter Name Value Factory Set Scope Instruction

F0.11 Decelerationtime inverterAccording to

The time it takes for the inverter todecelerate from the maximumoutput frequency to zeroF0.12 directionRunning

0: FWD1: REV2: banned REVF0.13 V/F Curvesetting 0 0-2 0: Wirear curve 1: Square curve2: Multi-point VF curveF0.14 Torque LiftingValue the inverterAccording to

Manual torque listing value, iflarge torque is required, set to 0.0;this value set is the percentage ofrated voltage

F0.15 Value CutoffTorque Lifting

F0.17 V/F FrequencyValue F1 12.5Hz y value F20.1-frequenc

F0.18 V/F VoltageValue V1 25.0% value F20.1-voltage

F0.19 V/F FrequencyValue F2 25.0Hz value F1-F3Frequency

F0.20 V/F VoltageValue V2 50.0% value V1-V3Voltage

F0.21 V/F FrequencyValue F3 37.5Hz

FrequencyvalueF2-ratedfrequency(F4.03)F0.22 V/F VoltageValue V3 75% valueVoltage

Trang 10

F0.23 User’s code 0 0-9999 arbitrarily will be effective after 3Setting a number except for zero

minutes or power-off

F1- Assisted running parameters

F1.00 mode whenDC braking

Unit: Start mode0: Start from starting frequency1: First start DC braking andthenthe starting frequencyTens: Power-off or abnormalrestarting mode

0: invalid1: Started from the startingfrequency

Hundreds: Reserved Thousands:Reserved

F1.01 DC brakingstart frequency 1.0Hz 0.0-50.0Hz After the frequency reaches thedefaulting value, start DC brakingF1.02voltage whenDC brake

starting 0.0%

0.0-50.0%

ratingvoltage Apply DC braking voltage valueF1.03 DC brakingtime 0.0s 0.0-30.0s The time for applying DC brakingF1.04 Shutdownmode 0 0-1 0: deceleration and stop1: freely stopF1.05

DC brake

starting

frequency when

stop

0.0Hz upper limit0.0-the defaulting value, start DC brakingAfter the frequency reaches the

F1.06voltage whenDC brake

0.0-50.0%

ratingvoltage Apply DC braking voltage valueF1.07 DC braking 0.0s 0.0-30.0s The time for applying DC braking

HzMaximumoutputfrequency

Trang 11

10 / 31

Para-meter Name Value Factory Set Scope Instruction

time when stop

F1.08waiting timeDC brake

when stop 0.00s 0.00-99.99s

After reaching the brakingfrequency, delay a little while andthen start DC brakingF1.09frequencyFWD jog

F1.13 Jumpingfrequency 0.0Hz limit0.0-upper frequency and scope, make theThrough setting the jumping

inverter keep away from themechanical resonance point of theload

F1.14 Jumping scope 0.0Hz 0.0-10.0Hz

F1.15of frequencysetting model

0: potentiometer +digitalfrequency 1

1: potentiometer +digitalfrequency 2

2: potentiometer +AVI3: Digital frequency 1+AVI4: Digital frequency 2+AVI5: Digital frequency 1+ multistagespeed

6: Digital frequency 1+ multistagespeed

7: potentiometer + multistagespeed

1: continuous cycle,2: keep the final value after singlecycle Hundreds: start mode

Trang 12

11 / 31

Para-meter Name Value Factory Set Scope Instruction

0: restart from the first stage1: start when inverter stops2: Start when inverter stop andfrequency has been initiated.Thousands: Power-off storageselection

0: No storage,1: StorageF1.17 Multi-speedfrequency 1 5.0Hz limit- theThe lower

upper limit set the frequency of stage 1F1.18 Multi-speedfrequency 2 10.0Hz limit- theThe lower

upper limit set the frequency of stage 2F1.19 Multi-speedfrequency 3 15.0Hz limit- theThe lower

upper limit set the frequency of stage 3F1.20 Multi-speedfrequency 4 20.0Hz limit- theThe lower

upper limit set the frequency of stage 4F1.21 Multi-speedfrequency 5 25.0Hz limit- theThe lower

upper limit set the frequency of stage 5F1.22 Multi-speedfrequency 6 37.5Hz limit- theThe lower

upper limit set the frequency of stage 6F1.23 Multi-speedfrequency 7 50.0Hz limit- theThe lower

upper limit set the frequency of stage 7F1.24 Running timein stage 1 10.0s 0.0-999.9s (unit is chosen by [F1.35],set the running time of stage 1

defaulting to be second.)F1.25 Running timein stage 2 10.0s 0.0-999.9s (unit is chosen by [F1.35],set the running time of stage 2

defaulting to be second.)F1.26 Running timein stage 3 10.0s 0.0-999.9s (unit is chosen by [F1.35],set the running time of stage 3

defaulting to be second.)F1.27 Running time 10.0s 0.0-999.9s set the running time of stage 4

Trang 13

12 / 31

Para-meter Name Value Factory Set Scope Instruction

defaulting to be second.)F1.28 Running timein stage 5 10.0s 0.0-999.9s (unit is chosen by [F1.35],set the running time of stage 5

defaulting to be second.)F1.29 Running timein stage 6 10.0s 0.0-999.9s (unit is chosen by [F1.35],set the running time of stage 6

defaulting to be second.)F1.30 Running timein stage 7 10.0s 0.0-999.9s (unit is chosen by [F1.35],set the running time of stage 7

10.0s 0.1~255.0s set the acceleration anddeceleration time 2F1.34 Decelerationtime 2

F1.35 Time unitselection 000 000~211

Units: PID Procedural time unitTens: PLC Simple time unitHundreds: General accelerationand deceleration time unitThousands: Reserved0: Each unit is 1 second1: Each unit is 1 point1: Each unit is 0.1 seconds

F2- Analog and digital input and output parameter

F2.00 AVI input 0.00W 0.00~ set the maximum and minimum

Trang 14

13 / 31

Para-meter Name Value Factory Set Scope Instruction

voltage with

the lower limit 【F2.01】 AVI voltage

F2.01voltage withAVI input

the upper limit 10.0V

【F2.01】~

10.00VF2.02the lower limitRelevant set on

0.0%

set the relevant set according to themaximum and minimumfrequency, and the relevant set isthe percentage of the maximumfrequency [F0.05]

F2.03the upper limitrelevant set on

F2.04voltage withAVI input

the lower limit 0.00Ma

0.00~

【F2.05】

set the maximum and minimumACI input current

F2.05voltage withAVI input

the upper limit 20.00Ma

F2.04】~

20.00mAF2.06the lower limitRelevant set on

0.0%

set the relevant set according to themaximum and minimumfrequency, and the relevant set isthe percentage of the maximumfrequency [F0.05]

F2.07the upper limitRelevant set on

Trang 15

14 / 31

Para-meter Name Value Factory Set Scope Instruction

F2.11 The lower limitof A0 output 0.00V

8: External reset signal input(RST)

9: External fault input10: Increment frequency command(UP)

11: Decrement frequencycommand (DOWN)13: Multi-speed selection S114: Multi-speed selection S215: Multi-speed selection S316: Running command channelcompulsive terminal17: reserved18: DC braking command whenstop

19: Frequency switch to AVI20: Frequency switch to digitalfrequency 1

21: Frequency switch to digitalfrequency 2

22: Reserved23: Counter clear signal24: Counter triggering signal25: Timer clear signal26: Timer triggering signal27: Acceleration and decelerationtime selection

F2.14input terminalThe function of

Trang 16

15 / 31

Para-meter Name Value Factory Set Scope Instruction

3: three-wire control model 2F2.19

7: Frequency / speed leveldetection signal (FDT)8: The output frequency reachesthe upper limit

9: The output frequency reachesthe lower limit

10: Inverter overload warning11: Timer overflow signal12: Counter detection signal13: Counter reset signal14: Assisted motorF2.21 Reservation

F2.25 FDT-level setvalue 10.0Hz maximum0.0Hz~the

frequency

Trang 17

F2.28triggering modePulse input

0: means the electrical triggeringmode

1: means the pulse triggering mode

F2.29effectiveInput terminal

0: means positive logic, et it isvalid when Si terminal isconnected with the public terminalbut invalid when they aredisconnected

1: means inverse logic, et.It isvalid that Si terminal is connectedwith the public terminal but invalidwhen they are disconnected.F2.30 S1 Filter

coefficient 5 0~9999 terminals,used to set the sensitivity of input

If the digital input terminal iseasily disturbed and causemalfunction, increase thisparameter to increase theanti-interference ability However,

if the range of setting is too large,the sensitivity of the input terminalwill decrease 1: Represents 2MSscan time unit

F3- PID parameter setting

F3.00 PID functionalsetting 1010 0000~2122

Unit: PID adjustmentcharacteristic0: invalid, 1: negative feedback,2: positive feedbackTens digit: PID given quantityinput channel

0: keyboard potentiometer, 1:number given

Trang 18

17 / 31

Para-meter Name Value Factory Set Scope Instruction

PID quantity is given by thenumber, and set by the functioncode F3.01

2: Pressure given (MPa, Kg)

By setting F3.01, F3.18 givenpressure

Hundreds digit: FID feedbackinput channel 0: AVI, 1: ACIThousands digit: PID sleepselection

0: invalid, 1: normal hibernation,this method needs to set specificparameters such as F3.10 ~ F3.13.2: disturbance sleep

Same as the parameter settingwhen the sleep mode is selected as

0, if the PID feedback value iswithin the range of the F3.14setting value, the sleep delay timewill be maintained and thedisturbance sleep will be entered.When the feedback value is lessthan the wake-up threshold (PIDpolarity is positive), immediatelywake up

F3.01 The givenvalue is set 0.0% 0.0~100.0%

Use the keyboard to set the givenamount of PID control.Thisfunction is valid only when the PIDgiven channel selection digit isgiven (F3.00 ten's digit is 1).F3.02channelFeedback

benefit- gain 1.00 0.01~10.00

When thefeedback channelis notconsistent with the setting cannel,this function can be used to adjustthe signal of feedback channel.F3.03 Proportionalgain P 1.00 0.1~5.00 by two parameters, proportionalThe adjustment speed of PID is set

gain P and Integration Time Ti Ifyou want a higher speed, youshould increase the proportionalgain P and decrease the integrationtime; if you want a lower speed,you should decrease theproportional gain P and increaseF3.04 Integrationtime Ti 1.00 0.1~50.0s

F3.05 Derivative timeTd 2.0s 0.1~10.0s